Plano - 01 - EJES Y COLUMNAS, DETALLES GENERALES

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

A B C D E F G A B C D E F G

29.60 29.60
14.80 7.79 3.14 1.05 2.10 0.73
14.80 7.79 3.14 1.05 2.10 0.73
1.00 1.00 0.55 29.05 0.55
Z4

0.55

0.55

0.55

0.55
1 1.00
Z4
1.00 1 1 1
C1 C1
0.55 0.55

0.60 2.10 0.60


0.25 2.45 0.25

0.25

0.25
0.60 0.60 C3

V-AM 1 (.30X.30)

V-AM 2 (.30X.30)
C2
Z5 Z5 V-AM 3 (.30X.30)

6.42

5.87

5.87

6.42
6.42 5.42

2.95

3.75

3.75
3.40

V-AM 1 (.30X.30)

0.25 V-AM 2 (.30X.30)


2.00
0.60 1.00 0.55 0.55
0.55
C2 C3
0.55

0.55

0.55

0.25

0.55
2 1.50 0.60 1.00 2 2 2
Z5
0.25 V-AM 3 (.30X.30) 0.25
2.45
Z6 Z4 C1
C1
0.55

V-AM 1 (.30X.30)

2 (.30X.30)
2.98

V-AM 2.98
2.63
2.18

4.50
4.50
0.60 2.10 0.60
C2 C3
V-AM 3 (.30X.30)

5.90

0.25

0.25

5.90

6.45
0.60 0.60
Z5 Z5 0.25 2.45 0.25
0.80 3.44 0.70 1.40 0.70
4.19 0.30 1.80 0.30

V-AM 1 (.30X.30)

(.30X.30)
V-AME (30x30)
Z1 Z1

0.30

0.30 0.90 0.30


3 2.17 0.70 V-AM3 (30x30) 0.70 3 3 3

2.97

2.97
2.62 C4 C4

1.20
1 2 3 4 5 6 7 8 9 10 11 12 13 14

1.20
1.20 2.00

V-AM 2
Z3

2.00 Z1 Z1
C1 0.30

0.30

0.30
4 0.55
0.60 0.70
V-AM4 (30x30) V-AM4 (30x30) 0.70 1.00 4 4 0.55
C4 C4
0.55 4

0.74
0.74 C2 C3 0.30 2.84 0.30 C4
0.80 2.39 0.70 2.25 0.70 V-AM 3 (.30X.30)
0.55

0.55
1.00

0.55

0.25

0.25

0.55
5 1.50 0.60 5 5 5
Z5 Z4 0.25 2.45 0.25
Z6 C1
0.55

V-AM 1 (.30X.30)

2 (.30X.30)
V-AMD (30x30)

V-AMF (30x30)
V-AMC (30x30)

4.35

4.35

4.35
3.90 3.82

3.65

V-AM 3.65
3.91
3.91 3.30
2.85

0.60 2.10 0.60 0.70 2.32 0.95 2.32 0.70


C2 C3
0.30 2.84 0.30 2.85 0.30
V-AM 3 (.30X.30)

33.60

7.25

0.25

0.25

7.25

7.80
0.30

0.30

0.30
6 33.60 0.60 0.60 0.70 V-AM6 (30x30) 0.95 V-AM6 (30x30) 0.70 6 6 C4 C4
6
Z5 Z5 Z1
Z2
Z1 0.25 2.45 0.25 C4

V-AM 1 (.30X.30)

2 (.30X.30)
2.85

3.89

3.65

V-AM 3.65
3.89 3.30

V-AMF (30x30)
V-AMD (30x30)
V-AMC (30x30)

4.35

4.35

4.35
3.90 3.82
2.00
0.60 1.00 0.55 0.55
0.55
C2 C3
V-AM 3 (.30X.30)
0.55

0.55
1.00

0.55

0.25

0.25

0.55
7 1.50 0.60 0.70 2.25 0.70 7 7 7

0.75
0.75 Z5 Z4 0.25 2.45 0.25 0.30 2.84 0.30 2.85 0.30
Z6 C1 C1

0.30

0.30

0.30 0.90 0.30


8 0.70
V-AM8 (30x30) V-AM8 (30x30) 0.70 0.55 8 8 C4 C4 8
C4

V-AME (30x30)

V-AM 1 (.30X.30)

2 (.30X.30)
Z1 Z1

1.20
1.20 2.00

1.20
Z3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 C4 C4

3.19

V-AM 3.19
2.84

0.30
9 2.39 0.70 V-AM9 (30x30) 0.70 9 9 9
Z1 Z1
4.19 0.30 1.80 0.30
0.80 3.44 0.70 1.40 0.70
0.60 2.10 0.60

5.90

5.90

6.45
C2 C3
V-AM 3 (.30X.30)

0.25

0.25
0.60 0.60
Z5 Z5
0.25 2.45 0.25

4.50
4.50

V-AM 1 (.30X.30)

2 (.30X.30)
1.96

3.19

V-AM 3.19
2.84
2.00
1.00
0.55 0.55 0.55
0.60 Z4
0.55

0.55

0.55

0.55
10 1.50 1.00 10 10 C2 C3
V-AM 3 (.30X.30)
10

0.25

0.25
0.60 C1
Z6 C1
Z5 0.55 0.25 2.45 0.25

V-AM 1 (.30X.30)

2 (.30X.30)
3.75

V-AM 3.75
3.38 3.40

6.48

5.93

5.93

6.48
6.48 5.48
0.60 2.10 0.60
C2 C3
V-AM 3 (.30X.30)

0.25

0.25
0.60 0.60 0.60
Z5 Z5
0.25 2.45 0.25

1.00 1.00 0.55 29.05 0.55


0.55
0.55

0.55

0.55

0.55
11 1.00 1.00 11 11 11
Z4 C1 C1
Z4
0.55

A B C D E F G A B C D E F G

DIRIGIDO A:
CIM
1
1 : 100 N+0.00
3
1 : 100

ESPECIFICACIONES RECUBRIMIENTOS ACEROS LONGITUDINALES TABLA DE GANCHOS ESTANDAR EQUIPO DE DISEÑO:

REGLAMENTO DE DISEÑO ZAPATAS: 7.5cm.


CANTIDAD VARILLAS
REGLAMENTO COLOMBIANO DE CONSTRUCCION SISMO RESISTENTE NSR-10 VIGAS DE CIMENTACION: 6.0cm.
LEY 400 DE 1997 (MODIFICADA LEY 1229 DE 2008) NUMERO VARILLAS
MUROS ESTRUCTURALES: 2.5cm.
DECRETO 926 DEL 19 DE MARZO DE 2010 LOSAS ENTREPISO: 2.5cm. E&C CONSTRUCCIONES
DECRETO 2525 DEL 13 DE JULIO DE 2010 VIGAS: 4.0cm. 2#4 L=3.60m
DECRETO 092 DE ENERO 17 DE 2011 COLUMNAS: 4.0cm.
LONGITUD EN METROS PROYECTO:
OTROS ELEMENTOS: LOS MOSTRADOS EN DETALLES.
CONCRETO:
GANCHOS ESTANDAR (cm)
CUBIERTA EL PALMAR
GANCHOS A 180º GANCHOS A 90º
SOLADOS: 21MPa BARRA Nº D
A G A G
CICLÓPEO (50%-50%): 17MPa ANCLAJE Y DESARROLLO DEL REFUERZO #2 3.8 10 5.0 10 11.6
CIMENTACIÓN: 21MPa #3 5.7 15 7.6 15 17.4
COLUMNAS: 21MPa TRASLAPOS MÍNIMOS COMPRESIÓN TRASLAPOS MÍNIMOS TENSIÓN #4 7.6 15 10.2 20 23.1
#5 9.5 20 12.7 25 29.0
VIGAS Y PLACAS: 21MPa #6 11.4 25 15.2 25 30.0
BARRAS No 2 300mm BARRAS No 2 350mm CONTENIDO:
#7 13.3 30 17.8 30 36.6
LA CONSTRUCCION DEL PRESENTE PROYECTO SE DEBE AJUSTAR A TODOS LOS BARRAS No 3 300mm BARRAS No 3 550mm #8 15.2 35 20.3 35 41.0
REQUISITOS DE LA NORMA SISMORESISTENTE COLOMBIANA NSR-10. BARRAS No 4 400mm BARRAS No 4 850mm #9 24.1 40 29.8 40 48.5 EJES Y COLUMNAS,
BARRAS No 5 500mm BARRAS No 5 1050mm
BARRAS No 6 600mm BARRAS No 6 1250mm
#10 27.3 45 33.7 45 54.0
DETALLES
CONCRETO CON AGREGADOS DE PESO NORMAL BARRAS No 7 700mm BARRAS No 7 1750mm
TABLA DE GANCHOS EN ESTRIBOS GENERALES
TAMAÑO MAXIMO DEL AGREGADO GRUESO 19mm BARRAS No 8 800mm BARRAS No 8 2000mm
TAMIZ QUE PASA EL AGREGADO GRUESO SEGUN NTC-144 (ASTIM C33): 67 BARRAS No 10 1000mm BARRAS No 10 2500mm PLANO:

ACERO DE REFUERZO: 01
LAS BARRAS DE REFUERZO DEBEN SER CORRUGADAS, ESTRIBOS ADICIONALES EN ZONA DE TRASLAPO DE VIGAS DES
DE ACERO DE BAJA ALEACIÓN FECHA:
QUE CUMPLAN LA NORMA NTC-2289 VIGAS CON CAPACIDAD DE
DISIPACION DE ENERGIA
27/08/2020
ESPECIAL (DES) GANCHOS EN ESTRIBOS (cm)
BARRAS DE REFUERZO: 420MPa
REFUERZO ELECTROSOLDADO DE ALAMBRE: 420MPa A 135º A 90º
BARRA Nº D
A A
(MALLA ELECTROSOLDADA) TRASLAPO MALLAS: L=.35m #2 2.5 7.5 7.5
AISLAMIENTO ESTRUCTURAL: 11cm #3 4 10 10
#4 5 11.5 11.5
#5 6.5 15 15 VERSION:

A ES LA DIMENSIÓN NECESARIA PARA FORMAR EL GANCHO


V-01