Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

SMART Transmitter Power Supply

KCD2-STC-Ex1
< 1-channel isolated barrier
< 24 V DC supply (Power Rail)
< Input for 2-wire SMART transmitters and current sources
< Output for 4 mA ... 20 mA or 1 V ... 5 V
< Housing width 12.5 mm
< SIL 2 (SC 3) acc. to IEC/EN 61508

Function
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire SMART transmitters in a hazardous area, and can also be used with 2-wire SMART current sources.
It transfers the analog input signal to the safe area as an isolated current value.
Digital signals may be superimposed on the input signal in the hazardous or safe area and are transferred bi-directionally.
Selectable output of current source, sink mode, or voltage output is available via DIP switches.
If the HART communication resistance in the loop is too low, the internal resistance of 250 Ω between terminals 6 and 8 can be used.
Test sockets for the connection of HART communicators are integrated into the terminals of the device.

Connection

KCD2-STC-Ex1

1+
HART

7-

2- 5-
HART

3+ V
6+
HART

250 Ω
mA 8+
Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf

4-

9+
10-
24 V DC

24 V DC
Zone 0, 1, 2 Zone 2
Power Rail
Div. 1, 2 Div. 2

Technical Data
General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 9+, 10-

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 1
SMART Transmitter Power Supply KCD2-STC-Ex1
Technical Data
Rated voltage Ur 19 ... 30 V DC
Ripple ≤ 10 %
Rated current Ir ≤ 45 mA at 24 V and 20 mA source mode output
Power dissipation ≤ 800 mW
Power consumption ≤ 1.1 W
Input
Connection side field side
Connection terminals 1+, 2-; 3+, 4-
Input signal 4 ... 20 mA limited to approx. 26 mA
Open circuit voltage/short-circuit current terminals 1+, 2-: 22 V / 26 mA
Voltage drop terminals 3+, 4- : approx. 5 V
Available voltage terminals 1+, 2-: ≥ 15 V at 20 mA ; ≥ 18 V at 4 mA
Output
Connection side control side
Connection terminals 5-, 6+
terminals 5-, 8+ for HART resistor
Load 0 ... 350 Ω (source mode)
Output signal 4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
4 ... 20 mA (sink mode), operating voltage 10 ... 30 V
Ripple 20 mV rms
Transfer characteristics
Deviation at 20 °C (68 °F)
< 0.1 % of full scale, incl. non-linearity and hysteresis (source mode and sink mode 4
... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
Influence of ambient temperature < 2 µA/K (-20 ... 70 °C (-4 ... 158 °F)); < 4 µA/K (-40 ... -20 °C (-40 ... -4 °F)) (source
mode and sink mode 4 ... 20mA)
< 0.5 mV/K (-20 ... 70 °C (-4 ... 158 °F)); < 1 mV/K (-40 ... -20 °C (-40 ... -4 °F)) (source
mode 1...5 V)

Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling time ≤ 50 ms
Rise time/fall time ≤ 10 ms
Galvanic isolation
Input/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LED
Control elements DIP switch
Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf

Configuration via DIP switches


Labeling space for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EU EN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibility NE 21:2017
EN 61326-3-2:2018
Degree of protection IEC 60529:2001
Protection against electrical shock UL 61010-1:2012
Ambient conditions
Ambient temperature -40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protection IP20
Connection screw terminals
Mass approx. 100 g

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 2
SMART Transmitter Power Supply KCD2-STC-Ex1
Technical Data
Dimensions 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Mounting on 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificate CESI 06 ATEX 021
Marking 1 II (1)G [Ex ia Ga] IIC
1 II (1)D [Ex ia Da] IIIC
1 I (M1) [Ex ia Ma] I
Input Ex ia
Supply
Maximum safe voltage Um 250 V AC (Attention! Um is no rated voltage.)
Equipment terminals 1+, 2-
Voltage Uo 25.2 V
Current Io 100 mA
Power Po 630 mW
Internal capacitance Ci 5.7 nF
Internal inductance Li negligible
Equipment terminals 3+, 4-
Voltage Ui 30 V
Current Ii 128 mA
Voltage Uo 7.2 V
Current Io 100 mA
Power Po 25 mW
Internal capacitance Ci 5.7 nF
Internal inductance Li negligible
Certificate CESI 19 ATEX 021 X
Marking 1 II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Output safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supply safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EU EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-7:2015
International approvals
FM approval
FM certificate FM 18 CA 0116 X , FM 19 US 0117 X
Control drawing 116-0469 (cFMus)
UL approval E106378
Control drawing 116-0459 (cULus)
IECEx approval
Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf

IECEx certificate IECEx CES 06.0001X


IECEx marking [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary information Observe the certificates, declarations of conformity, instruction manuals, and manuals
where applicable. For information see www.pepperl-fuchs.com.

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 3
SMART Transmitter Power Supply KCD2-STC-Ex1
Assembly

Front view

Removable terminals
blue

1 2
3 4

LED green:
KCD2-STC-
Ex1
Power supply

PWR

S1
S2
S3
S4
I II

Switch 1 ... 4
5 6
7 8
9 10

Removable terminals
green

Matching System Components


KFD2-EB2 Power Feed Module

UPR-03 Universal Power Rail with end caps and cover, 3 conductors, length: 2 m

UPR-03-M Universal Power Rail with end caps and cover, 3 conductors, length: 1,6 m

UPR-03-S Universal Power Rail with end caps and cover, 3 conductors, length: 0.8 m

K-DUCT-BU Profile rail, wiring comb field side, blue

K-DUCT-BU-UPR-03 Profile rail with UPR-03- * insert, 3 conductors, wiring comb field side, blue
Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf

Accessories
KC-ST-5GN Terminal block for KC modules, 2-pin screw terminal, green

KC-STP-5GN Terminal block for KC modules, 2-pin screw terminal, with test sockets, green

KC-STP-5BU Terminal block for KC modules, 2-pin screw terminal, with test sockets, blue

KF-CP Red coding pins, packaging unit: 20 x 6

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".


Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com 4
SMART Transmitter Power Supply KCD2-STC-Ex1

Application
The device supports the following SMART protocols:
• HART
• BRAIN

Configuration

PWR

S1
S2
S3
S4
I II

Output switch settings

Mode of operation S1 S2 S3 S4
Current source output 4 ... 20 mA II II I II
Voltage source output 1 ... 5 V II II I I
Current sink output 4 ... 20 mA II I II II

Factory setting: current source output 4 ... 20 mA


Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf

Refer to "General Notes Relating to Pepperl+Fuchs Product Information".

5
Pepperl+Fuchs Group USA: +1 330 486 0002 Germany: +49 621 776 2222 Singapore: +65 6779 9091
www.pepperl-fuchs.com pa-info@us.pepperl-fuchs.com pa-info@de.pepperl-fuchs.com pa-info@sg.pepperl-fuchs.com

You might also like