SMART Transmitter Power Supply KCD2-STC-Ex1: Function
SMART Transmitter Power Supply KCD2-STC-Ex1: Function
KCD2-STC-Ex1
< 1-channel isolated barrier
< 24 V DC supply (Power Rail)
< Input for 2-wire SMART transmitters and current sources
< Output for 4 mA ... 20 mA or 1 V ... 5 V
< Housing width 12.5 mm
< SIL 2 (SC 3) acc. to IEC/EN 61508
Function
This isolated barrier is used for intrinsic safety applications.
The device supplies 2-wire SMART transmitters in a hazardous area, and can also be used with 2-wire SMART current sources.
It transfers the analog input signal to the safe area as an isolated current value.
Digital signals may be superimposed on the input signal in the hazardous or safe area and are transferred bi-directionally.
Selectable output of current source, sink mode, or voltage output is available via DIP switches.
If the HART communication resistance in the loop is too low, the internal resistance of 250 Ω between terminals 6 and 8 can be used.
Test sockets for the connection of HART communicators are integrated into the terminals of the device.
Connection
KCD2-STC-Ex1
1+
HART
7-
2- 5-
HART
3+ V
6+
HART
250 Ω
mA 8+
Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf
4-
9+
10-
24 V DC
24 V DC
Zone 0, 1, 2 Zone 2
Power Rail
Div. 1, 2 Div. 2
Technical Data
General specifications
Signal type Analog input
Functional safety related parameters
Safety Integrity Level (SIL) SIL 2
Systematic capability (SC) SC 3
Supply
Connection Power Rail or terminals 9+, 10-
Frequency range field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Settling time ≤ 50 ms
Rise time/fall time ≤ 10 ms
Galvanic isolation
Input/Output basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input/power supply reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output/power supply basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elements LED
Control elements DIP switch
Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf
Front view
Removable terminals
blue
1 2
3 4
LED green:
KCD2-STC-
Ex1
Power supply
PWR
S1
S2
S3
S4
I II
Switch 1 ... 4
5 6
7 8
9 10
Removable terminals
green
UPR-03 Universal Power Rail with end caps and cover, 3 conductors, length: 2 m
UPR-03-M Universal Power Rail with end caps and cover, 3 conductors, length: 1,6 m
UPR-03-S Universal Power Rail with end caps and cover, 3 conductors, length: 0.8 m
K-DUCT-BU-UPR-03 Profile rail with UPR-03- * insert, 3 conductors, wiring comb field side, blue
Release date: 2022-06-01 Date of issue: 2022-06-01 Filename: 316910_eng.pdf
Accessories
KC-ST-5GN Terminal block for KC modules, 2-pin screw terminal, green
KC-STP-5GN Terminal block for KC modules, 2-pin screw terminal, with test sockets, green
KC-STP-5BU Terminal block for KC modules, 2-pin screw terminal, with test sockets, blue
Application
The device supports the following SMART protocols:
• HART
• BRAIN
Configuration
PWR
S1
S2
S3
S4
I II
Mode of operation S1 S2 S3 S4
Current source output 4 ... 20 mA II II I II
Voltage source output 1 ... 5 V II II I I
Current sink output 4 ... 20 mA II I II II
5