Professional Documents
Culture Documents
4520 MKII Data Sheet (US Size)
4520 MKII Data Sheet (US Size)
4520 MKII Data Sheet (US Size)
DSE4520 MKII
SPECIFICATIONS
DC SUPPLY
CONTINUOUS VOLTAGE RATING
AUTO MAINS FAILURE CONTROL MODULE 8 V to 35 V Continuous
CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
KEY FEATURES • Engine speed protection KEY BENEFITS
• Configurable for use as an auto • Engine hours counter • Automatically transfers between FREQUENCY RANGE
start and AMF control module • Engine pre-heat mains (utility) and generator 3.5 Hz to 75 Hz
• J1939-75 support and CAN alarm • Engine run-time scheduler • Hours counter provides accurate OUTPUTS
ignore functon • Engine idle control for starting & information for monitoring and OUTPUT A (FUEL)
• Alternator frequency & CAN speed stopping maintenance periods 10 A short term, 5 A continuous,
sensing in one variant • Tier 4 engine instrumentation • User-friendly set-up and button at supply voltage
• Largest back-lit icon display in its screens layout for ease of use OUTPUT B (START)
class • Battery voltage monitoring • Multiple parameters are monitored 10 A short term, 5 A continuous,
• Heated display option • Start on low battery voltage simultaneously which are clearly at supply voltage
• Real time clock provides accurate • Configurable remote start input displayed on the large back-lit AUXILIARY OUTPUTS C, D, E & F
event logging • 1 alternative configuration icon display. 2 A DC at supply voltage
• Fully configurable via the fascia or • Comprehensive warning, electrical • The module can be configured to
trip or shutdown protection upon GENERATOR
PC using USB communication suit a wide range of applications
VOLTAGE RANGE
• Extremely efficient power save fault condition • Uses DSE Configuration 15 V to 415 V AC (Ph to N)
mode • LCD alarm indication Suite PC Software for simplified 26 V to 719 V AC (Ph to Ph)
• 3 phase generator sensing • Event log (50) configuration
FREQUENCY RANGE
• 3 phase mains (utility) sensing • Fuel solenoid pulling circuit • Compatible with a wide range of 3.5 Hz to 75 Hz
• Compatible with 600 V ph to ph • On-screen line diagram on/off CAN engines including Tier 4
nominal systems functionality • Licence-free PC software DIMENSIONS
OVERALL
• Generator/load power monitoring • Configurable CAN instrumentation • IP65 rating (with optional gasket) 140 mm x 113 mm x 43 mm
(kW, kV A, kV Ar, pf) (10) offers increased resistance to water 5.5’’ x 4.4” x 1.7”
• Accumulated power monitoring • Water in fuel digital input ingress
(kW h, kVA h, kVAr h) • Tank bund alarm digital input PANEL CUT-OUT
118 mm x 92 mm
• Generator overload protection (kW) • Generator at rest output 4.6’’ x 3.6”
• Generator/load current monitoring • ECU periodic wake-up for
and protection information retrieval MAXIMUM PANEL THICKNESS
8 mm
• Fuel and start outputs (configurable • Back-light power-save mode 0.3”
when using CAN) • Adjustable delay crank timer
• 4 configurable DC outputs • Pre/post heat functionality STORAGE TEMPERATURE RANGE
• 3 configurable analogue/digital • Overload protection -40 °C to +85 °C
-40 °F to +185 °F
inputs • Mains/generator A/C system
• 4 configurable digital inputs selection OPERATING TEMPERATURE RANGE
• Configurable staged loading • Output timer for external audible -30 °C to +70 °C
-22 °F to +158 °F
outputs alarm
• 3 engine maintenance alarms
DSE4520 MKII
ENVIRONMENTAL TESTING STANDARDS
ELECTRO-MAGNETIC COMPATIBILITY
BS EN 61000-6-2
AUTO MAINS FAILURE CONTROL MODULE EMC Generic Immunity Standard for
the Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for
the Industrial Environment
ELECTRICAL SAFETY
BS EN 60950
The DSE4520 MKII Auto Mains (Utility) The module provides electronic J1939 Safety of Information Technology Equipment,
Failure Control Module is suitable (CAN) and non-electronic (alternator * AVAILABLE VARIANTS including Electrical Business Equipment
for a wide variety of single gen-set frequency sensing) engine support for 4520-05 Auto Mains Failure (Rtc) TEMPERATURE
applications. diesel, gas and petrol engines all in BS EN 60068-2-1
one variant. With a number of flexible Ab/Ae Cold Test -30 ºC
BS EN 60068-2-2
Whilst maintaining functions included inputs, outputs and protections, the Bb/Be Dry Heat +70 ºC
within higher end controllers, such as module can be easily adapted to suit
generator and load power monitoring, a wide range of applications. VIBRATION
BS EN 60068-2-6
the DSE4520 MKII provides the user
Ten sweeps in each of three major axes
with an outstanding size to feature Through USB communication the 5 Hz to 8 Hz at +/-7.5 mm,
ratio. module can be easily configured 8 Hz to 500 Hz at 2 gn
using the DSE Configuration Suite PC
HUMIDITY
Monitoring engine speed, oil pressure, Software or can be fully configured BS EN 60068-2-30
coolant temperature, frequency, through the module’s front panel Db Damp Heat Cyclic 20/55 ºC
voltage, current, power and fuel level, editor. at 95% RH 48 Hours
BS EN 60068-2-78
the modules will give comprehensive Cab Damp Heat Static 40 ºC
engine and alternator protection. This All DSE products are supported by at 93% RH 48 Hours
will be indicated on the largest back-lit our dedicated technical support team,
LCD icon display in its class via an which gives customers and end users SHOCK
BS EN 60068-2-27
array of warning, electrical trip and access to 24 hour help and advice. Three shocks in each of three major axes
shutdown alarms. 15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the optional sealing gasket.
4 4 3
DEUTZ
DSE4520 MKII ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) DC OUTPUT GENERATOR/ DC OUTPUT GENERATOR CHARGE FUEL & START ELECTRONIC
SENSING LOAD CURRENT SENSING ALTERNATOR OUTPUTS ENGINE CAN
(Flexible with CAN)
VOLTS VOLTS
D+ +
+ + W/ L