INSTALLATION INSTRUCTIONS FOR THE MODEL ASBL ADDRESSABLE SOUNDER BASE

The information contained in this installation instruction is a quick reference guide. For detailed system information refer
to the panel manufacturer's installation manual. This instruction will not address specific programming procedures.

GENERAL DESCRIPTION
This instruction applies to the model ASBL addressable low frequency MOUNTING REQUIREMENTS
(520Hz) sounder base, which is to be connected to a DCP Signaling Line
Circuit (SLC). The ASBL is to be used with the ALG-V, ALK-V, ACA-V, BOX MOUNTING
AIE-EA, ATG-EA, ATJ-EA, ALN-V, ACC-V, and ACD-V model sensors BASE
only. The ASBL provides an audible, low-frequency alarm in the immediate 3" OCT 4" OCT 4" SQR*
vicinity. Typical applications are "sleeping areas in hotels, apartments, ALL MODELS NO NO YES
etc."

WIRING AND ADDRESSING FEATURES


NOTE: All wiring must conform to local codes, ordinances
and regulations. Command selectable evacuation codes - Continuous, March or
1) Connect wiring to terminals as shown. Do Not loop wire under Temporal Code 3 and Temporal Code 4 patterns.
terminals. Break wire run to provide supervision of connections. Program activation by General Event Type, by Zone,
2) Install base wiring in accordance with the applicable drawings by Cause and Effect or a combination between the three.
and appropriate wiring diagram (see following page).
High sound pressure level (85 dB SPL at 10 feet).
3) "The address of the ASBL will automatically be set as the host Low frequency (520Hz) alarm in compliance with NFPA
sensor's address + 127. For example, if the address of the
attached host sensor is 3, the address of the ASBL will be requirements for sleeping areas.
automatically set as 130 (3 + 127) with no loop power applied or
the loop wires disconnected."

CAUTION ! CAUTION !
To ensure proper operation If this base will be installed in
connect this base to a an existing operational
SPECIFICATIONS compatible Fire Control system, inform the operator
Model ASBL Panel only. Refer to panel and local authority that the
DCP Voltage Range instructions for proper system will be temporarily out
17 - 41VDC
connection and of service. Disconnect power
DCP Loop Idle Current 154uA compatibility. to the control panel before
DCP Loop Low Frequency Alarm installing the base.
154uA
Current
Aux. Power Supply Voltage 24VDC (16 - 33VDC)
Range
Aux. Power Supply Voltage CAUTION
24VDC (16 - 33VDC) Install the bases in this instruction in accordance with
Range FWR
applicable NFPA standards, local codes, and the
Auxiliary Idle Current 2.26mA authorities having jurisdiction. Failure to follow these
140mA @ 16VDC instructions may result in failure of the sensor and
Auxiliary Low Frequency Alarm
95mA @ 24VDC bases to initiate an alarm condition. Hochiki America
Current
72mA @ 33VDC is not responsible for sensors that have been
203mA @ 16VFWR improperly installed, tested, or maintained.
Auxiliary Low Frequency Alarm
149mA @ 24VFWR For testing and cleaning information refer to NFPA-72
Current FWR
92mA @ 33VFWR for Automatic Fire Detectors for installation guidelines,
Sound Pressure Level at 10ft. 85dB testing, and maintenance.
Maximum Humidy 93%RH (non-condensing)
Use "3M" Weatherban # 606 nonflammable sealing
compound to seal field wiring conduit openings in the
Operating Temperature Rang 32°F (0°C) - 100°F (38°C) mounting back box. Compliance with this request may
Storage Temperature -22°F (30°C) - 158°F (70°C) reduce the occurrence of the "STACK EFFECT".
Base Diameter 6.6"
Base Height (without sensor) 1.34" (not including terminal block)
Weight 0.455lb
ALG-V, ALK-V, ACA-V, AIE-EA,
Compatible Sensors ATG-EA, ATJ-EA, ALN-V, ACC-V &
ACD-V
* SEE SHEET 2 OF 2 FOR SPECIFIC BACK BOX REQUIREMENTS

HOCHIKI AMERICA CORPORATION DWG. # HA-06-361


7051 VILLAGE DRIVE SUITE 100 (PG 1 of 2, 03/18)
BUENA PARK, CA 90621-2268 PART# 1700-12120
ASBL SLC WIRING, ONLY WIRING BOARD AND LABEL SHOWN

Hochiki America Corporation Hochiki America Corporation Hochiki America Corporation


ASBL ASBL ASBL
CONTROL S1383 FIRE ALARM EQUIPMENT SUBASSEMBLY
S1383 FIRE ALARM EQUIPMENT SUBASSEMBLY S1383 FIRE ALARM EQUIPMENT SUBASSEMBLY
ISSUE NO. 0021096 ISSUE NO. 0021096 ISSUE NO. 0021096
PANEL DETECTOR BASE WITH INTEGRAL
AUDIBLE SIGNAL FOR USE WITH A
DETECTOR BASE WITH INTEGRAL
AUDIBLE SIGNAL FOR USE WITH A
DETECTOR BASE WITH INTEGRAL
AUDIBLE SIGNAL FOR USE WITH A
HOCHIKI AMERICA UL LISTED HEAD. HOCHIKI AMERICA UL LISTED HEAD. HOCHIKI AMERICA UL LISTED HEAD.
MAXIMUM 100°F AMBIENT MAXIMUM 100°F AMBIENT MAXIMUM 100°F AMBIENT
OPERATING TEMPERATURE. OPERATING TEMPERATURE. OPERATING TEMPERATURE.
TB2 TB2 TB2
S/N 910300001 S/N 910300001 S/N 910300001

AUX -

AUX -

AUX -
N I M Bd 5 8 LEVEL ERUSSERP DNUOS N I M Bd 5 8 LEVEL ERUSSERP DNUOS
AUX -
AUX -
MRALA YCNEUQERF WOL MRALA YCNEUQERF WOL
N I M Bd 5 8 LEVEL ERUSSERP DNUOS
AUX -
MRALA YCNEUQERF WOL
: TNERRUC MRALA AUX, V24VDC
4 2 DET(-)
ALUGER : TNERRUC MRALA AUX, V24VDC
4 2 DET(-)
ALUGER : TNERRUC MRALA AUX, V24VDC
4 2 DET(-)
ALUGER
XAM RWF Am3 0 2 AUX, 24VFWR
XAM CD Am(-)0 4 1 XAM RWF Am3 0 2 AUX, 24VFWR (-)0 4 1

AUX +

AUX +

AUX +
XAM CD Am XAM RWF Am3 0 2 AUX, 24VFWR
XAM CD Am(-)0 4 1
AUX + FOR INSTALLATION OR MAINTENANCE AUX + FOR INSTALLATION OR MAINTENANCE AUX + FOR INSTALLATION OR MAINTENANCE
LOOP OUT AUX 24VDC (+)
AUX 24VFWR (+)
SEE DWG # HA-06-361 REV 03/18
USE ONLY WITH AIE-EA, ALG-V, ALK-V,
AUX 24VDC (+)
AUX 24VFWR (+)
SEE DWG # HA-06-361 REV 03/18
USE ONLY WITH AIE-EA, ALG-V, ALK-V,
AUX 24VDC (+)
SEE DWG # HA-06-361 REV 03/18
AUX 24VFWR (+) USE ONLY WITH AIE-EA, ALG-V, ALK-V,
ALK-V2, ALN-V, ATG-EA, ATJ-EA,

SC

SC

SC
ALK-V2, ALN-V, ATG-EA, ATJ-EA, ALK-V2, ALN-V, ATG-EA, ATJ-EA,
DCP S- ACA-V, ACC-V, ACD-V SENSORS DCP S- ACA-V, ACC-V, ACD-V SENSORS DCP S- ACA-V, ACC-V, ACD-V SENSORS
For service, return to: For service, return to: For service, return to:
Hochiki America Corporation Hochiki America Corporation Hochiki America Corporation

S
7051 Village Drive, Suite 100 7051 Village Drive, Suite 100 7051 Village Drive, Suite 100
DCP S+ Buena Park, CA 90621-2268 DCP S+ Buena Park, CA 90621-2268 DCP S+ Buena Park, CA 90621-2268

WIRING VIEWED FROM REAR

LOOP IN

AUX 24VDC

NOTE: Class X wire configuration requires the installation of short circuit isolation.
DASHED LINES DRAWN FOR CLASS A/X. DO NOT CONNECT FOR CLASS B WIRING.

ASBL Mounting Instructions


The ASBL sounder base mounts to a 4” extension ring (not supplied) with two 8-32, 2” mounting screws (supplied). The extension ring mounts to the 4” back box with two
mounting screws (both 4” box and screws not included).

2" MOUNTING SCREWS


(SUPPLIED)

For Installations which extend beyond the mounting surface, or


do not have sufficient mounting box depth, an optional trim
ring is available. Insert the ASBL into the trim ring prior to
mounting to the electrical box.
ASBL

MOUNTING SCREWS
(NOT SUPPLIED)
8-32, 3.5" Suggested

3"
MIN. 1-1/2" OPTIONAL TRIM RING
EXTENSION RING P/N: 1400-04540
(NOT SUPPLIED)

MOUNTING SCREWS
(NOT SUPPLIED)

4" SQUARE BOX,


2" DEPTH RECOMMENDED
FIGURE 2
(NOT SUPPLIED)
OPTIONAL TRIM RING MOUNTING VIEW

FIGURE 1
DWG. # HA-06-361
MOUNTING EXPLODED VIEW (PG 2 of 2, 03/18)
PART# 1700-12120