For Diesel Driven Fire Pumps: Series FD4
For Diesel Driven Fire Pumps: Series FD4
Series FD4
All photographs and graphics are typical and may not represent actual product supplied
FUEL SPILL LOW PURGE PRESSURE Controller Operation
FUEL TANK RUPTURE LOW GEAR OIL PRESSURE Automatic Mode:
LOW PUMP ROOM TEMP LOW COOLANT LEVEL Starting conditions such as pressure drop, and deluge valve start,
RESERVOIR LOW HIGH GEAR OIL TEMP will cause the user adjustable sequential start delay timer to begin
RESERVOIR EMPTY HIGH VIBRATION operation. After start delay is completed the engine will start and
RESERVOIR HIGH LOW FUEL PRESSURE the operation will be recorded in the event log. In addition to the
FLOW METER ON HIGH EXHAUST TEMP sequential start timer the Automatic Weekly Test Start, AC Power
RELIEF VALVE OPEN HIGH FUEL TEMP Fail Start are programmable by the user through the OlD. All
LOW SUCTION PRESSURE PUMP ON DEMAND system statistics are continuously monitored and changes are
logged into the internal logs. System statistics include, but are not
Data logging: limited to, battery charger volts/amps, battery voltage, and system
Pressure Log: The Pressure log provides a continuous pressure pressure are continuously monitored and changes are logged.
recording for one month of data. Each time the pressure log
records a pressure it includes the time and date of the reading and Stopping conditions: Auto engine stop delay, engine lockout, low
is stored on the SD memory card. suction shutdown, automatic stop during automatic weekly test for
low oil pressure and high water temperature are all OlD user
The data recorded in the pressure log can be searched by each programmable features.
sample, by minute, or by hour allowing for easy access to specific
data. Manual Mode:
If a control logic failure occurs, two crank pushbuttons are provided
Event Log: The event log is also stored on the SD memory card. It that will bypass all internal logic and allow manual operation of the
will hold a maximum of 3000 events. These events include any of engine.
the following events/alarms:
BATTERY 1 FAULT
BATTERY 2 FAULT
SYSTEM AUTO MODE
ENGINE LOCKOUT SIGNAL
Options
BATTERY 1 LOW VOLTAGE SYSTEM AUTO MODE Option H: Space Heater
BATTERY 2 LOW VOLTAGE SYSTEM MANUAL MODE If the ambient atmosphere is especially damp or humid, a space
CHARGER 1 FAULT SYSTEM OFF MODE heater rated at 100 watts may be supplied to reduce moisture in the
CHARGER 2 FAULT SYSTEM TEST RUN cabinet. A thermostat is supplied as standard with this option. A
AC POWER FAIL ALARM RESET humidistat may be substituted at no additional charge.
ENGINE OVERSPEED LOW PRESSURE CONDITION
ENGINE FAILED TO START LOW PRESSURE START Option N: Step-down Transformer
ENGINE QUIT DELUGE START When AC voltage exceeds 240 VAC single phase, an integral
ENGINE LOW OIL PRESSURE REMOTE START transformer may be provided for operation from 380 to 600 VAC
ENGINE HIGH WATER TEMP AC POWER FAIL START 50/60 Hz input. Exact voltage and frequency must be specified
PRESSURE DROP HORN SILENCED when ordering.
STOP PUSHBUTTON PRESSURE TRANSDUCER Option W: 24 Inch (609.6 mm) Legs
PRESSED FAULT Provided for free standing installations when wall mounting is not
SPEED SWITCH FAILURE CONTACTOR COIL FAILURE practical. If specified, lifting eyes may also be supplied.
Plus any of the 8 programmable auxiliary alarms listed above
Enclosure
Every event or alarm that is recorded includes the following data The following NEMA type enclosures are also available: 3R, 4, 4X
with the recorded event or alarm: (Painted Cold Rolled Steel), 4X (304 or 316 Stainless Steel), and
• Time and Date of Event or Alarm 12.
• System Pressure
• Descriptive Text Message of the Event/Alarm
• System Auto Mode Status
• Engine Running Status
• Charger 1 Status
• Charger 2 Status
• Battery 1 Status
• Battery 2 Status
Fire Pump Controller
For Diesel Driven Fire Pumps
_____________________________________________________________________________________________________________
Metron, Inc. • 1505 West 3rd Ave., • Denver, Colorado 80223 • (303) 592-1903 • EMAIL: sales@metroninc.com • FAX (303) 534-1947
Bulletin FD4 04/09