Professional Documents
Culture Documents
Jetline: Theoretical Working Point Performance Chart
Jetline: Theoretical Working Point Performance Chart
In-line fan for circular duct with low profile compact casing manufactured from galvanised sheet steel and rubber
gasket on the flanges. High performance impeller, guide vane and outlet diffuser manufactured from injection-
moulded plastic, to increase performances and lower the sound level. IP65 terminal box fixed on the casing.
Mounting bracket supplied with the fan, enabling to mount the fan in two different positions and any shaft orientation
Motor
Single-phase external rotor motor assembled with antivibration mount to reduce vibration and noise level, 220-240V
50/60Hz, IP44, class F, with thermal protection and speed regulable by tension.
Working temperature -20/60ºC
Model JETLINE-160 (220-240V50/60HZ) N8 for an airflow 109 l/s and static pressure 95 Pa.
Input Power
Temperature 20 °C
(kW)
0,05
Altitude 0m
Density 1,2 kg/m³
0,00
Frequency 50 Hz
500
Working Point
Airflow 109 l/s 400
Static Pressure (Pa)
Static Pressure 95 Pa
Dynamic pressure 17,7 Pa 300
Total Pressure 113 Pa
Input power 0,059 kW 200
Outlet speed 5,4 m/s
Fan speed 2025 rpm 100
Specific Fan Power 0,55 W/l/s
Specific Fan Power reg 0,48 W/l/s 0 100V 140V 170V 230V
Construction 3000
Discharge diameter 160 mm 2000
Speed
(RPM)
Inlet (LwA) 31 41 48 56 52 54 53 43 60
Inlet LpA @ 3m 10 20 28 35 31 34 33 22 40
Outlet (LwA) 35 38 52 59 55 55 56 47 63
Outlet LpA @ 3m 14 17 31 38 34 34 35 26 42
Breakout (LwA) 19 5 18 28 29 33 35 28 39
Breakout LpA @ 3m - - - 7 8 12 15 7 18
A B1 B2 C1 C2 øD E F G
H øJ K
130 15 6.5
C/ Llevant, 4 08150 Parets del Vallès (Barcelona)- Tel. +34 93 571 93 00 - Fax. +34 93 571 93 01 consultas@solerpalau.com - www.solerpalau.es
1/1
8/2/2022, 9:13:17 AM - EasyVent v.9/6/2022 Rev.18099 | Selection Id 7004eed6-6af2-4d1d-89a1-d31efaf03fd7