Professional Documents
Culture Documents
Design of A Solar PV System
Design of A Solar PV System
SESSION – 2
1. On site Survey and Sizing
2. Design of a Solar PV system
3. Connection of a PV plant to the grid
Certification Training Course
3
Design of solar PV systems
The PV systems family
4
Design of solar PV systems
The PV systems family
5
Design of solar PV systems
The PV systems family
6
Design of solar PV systems
The PV systems family
Indonesia
• 20 kWp PV
• 10 kW Wind
• 150 Households
7
Design of solar PV systems
The PV systems family
8
Design of solar PV systems
The PV systems family
DC AC
SWITCH GRID
AC GEAR WH WH
9
Certification Training Course
11
Design of solar PV systems
Limits to capacity of Renewable Generators
A Producer who wishes to connect one or more Renewable Generators to the Distribution
System shall ensure that the sum of the Maximum Capacity of Renewable Generators
connected by the Producer in a certain Plot does not exceed:
1) The applicable share of the Total Connected Load (TCL) resulting from the application of
the table below
As per the above table, the applicable share is 100% for the first 400 kW of TCL, and
gradually decreases for additional TCL slabs in excess of 400 kW. This implies that the
Maximum Capacity of Renewable Generators connected by the Producer in a certain Plot
cannot exceed 2,080 kW.
12
Design of solar PV systems
Limits on installation
As per Shams Dubai connection conditions, A Renewable Generator should be
located entirely in the Plot where the Hosting Account is located. Renewable
Generators shall be installed on rooftops, facades, and other existing structures.
Ground mounted installations are not envisaged.
Shams Dubai standard 2.1 General Rules, clause 3 - Arrays with voltages which
exceed the above mentioned value of 1,000 Vdc (but not exceeding 1,500 Vdc)
may be allowed only for ground mounted solutions*, canopies, urban design and
any other solutions that does not involve the installation of PV modules, inverters
or other related equipment on buildings. In any case, all the equipment must
withstand the maximum voltage reached for the system, as calculated at the
minimum outdoor temperature of 0 °C.
* Ground mounted installations are not envisaged
13
Design of solar PV systems
Sizing the PV array
14
Design of solar PV systems
Sizing the PV array
15
Design of solar PV systems
Sizing the PV array
16
PV Plants – Central vs. String Inverters (1)
• Single-inverter plants (also called «Central Inverter»)
Single inverter for the whole PV array when the PV modules are of the
same type and have the same azimuth and tilt
Problems with shading and overcurrent protection increased
Down of the whole PV generator, in case of failure
17
PV Plants – Central vs. String Inverters (3)
• String inverter plants
Each string is connected to its own inverter (string conversion)
Each string operates according to its own Maximum Power Point (MPP)
Coupling between PV modules and inverters improved
Losses due to shading reduced
Overcurrent protections and blocking diodes can be omitted diode
losses cancelled
Efficiency and reliability improved
18
PV Plants – Central vs. String Inverters (4)
Inverter provided with more than one MPPT (management of single string
indipendently of the others, e.g. because made of a different number of modules -
different module layout or tilt – shading on one string)
19
PV Plants – Central vs. String Inverters (5)
• Multi-inverter plants (large plants)
PV array divided into sub-arrays
Still possibility to group string with similar characteristics (number of
modules, layout)
Installation and maintenance cost reduced (lower number of inverters
with respect to string inverters)
Loss of production of only one single sub-array, in case of inverter failure
20
Design of solar PV systems
Sizing the PV array
• The voltage of the PV array shall not exceed the MPPT limits of
the inverter in any condition of irradiance and cell temperature
21
Coordination between inverter and PV generator (1)
22
Coordination between inverter and PV generator (3)
where:
Uoc max : Maximum PV string open circuit voltage @ min T (0°C)
(min - 25): Variation between minimum expected cell temperature (0 °C) and STC (25 °C)
23
Coordination between inverter and PV generator (4)
where:
Umpp : Voltage of PV module at maximum power
Uoc: Open-Circuit (no-load) voltage of PV module
NM : number of modules for each string
CtUoc: Temperature coefficient of Open-Circuit (no-load) voltage (%/°C)
: Temperature coefficient of Open-Circuit (no-load) voltage (V/°C)
(max - 25): Variation between maximum expected cell temperature (80 °C) and STC (25 °C)
• Maximum Temperature
Approximately max = air_max + (NOCT – 20) / 0.8
NOCT: Nominal Operating Cell Temperature
24
Coordination between inverter and PV generator (4)
where:
Umpp : Voltage of PV module at maximum power
Uoc: Open-Circuit (no-load) voltage of PV module
NM : number of modules for each string
CtUoc: Temperature coefficient of Open-Circuit (no-load) voltage (%/°C)
: Temperature coefficient of Open-Circuit (no-load) voltage (V/°C)
(min - 25): Variation between minimum expected cell temperature (0 °C) and STC (25 °C)
25
Coordination between inverter and PV generator (5)
where:
26
Coordination between inverter and PV generator (6)
A string consists of a number of PV modules which ensures that the string voltage is
always below the maximum input voltage of the inverter. If the string voltage exceeds
the input voltage of the inverter, yield losses can occur due to delayed starting or to
inverter damage for overvoltage. Likewise, the maximum string voltage must not
exceed the maximum permitted system voltage of the PV modules and the maximum
MPPT voltage of the inverter
min nmaxMODSTR ≤ Umax INV / Uoc max ; nmaxMODSTR ≤ UMPPT max INV / Umpp max
where:
nmaxMODSTR: Maximum number of PV modules per string
Umax INV: Maximum input voltage of inverter
Uoc max: Maximum PV module voltage (= Uoc as referred to min )
UMPPT max INV: Maximum MPPT Voltage of inverter
Umpp max: Maximum MPP Voltage of PV generator (as referred to min )
27
Coordination between inverter and PV generator (7)
A string should consist of that number of PV modules which ensures that the string
voltage is always above the minimum MPP voltage of the inverter. If the string voltage
falls below the minimum MPP voltage of the inverter, yield losses can occur through
suboptimal MPP tracking, or MPP tracking is not possible at all
where:
28
Coordination between inverter and PV generator (8)
The optimum number of PV modules must not be less than the minimum number of
PV modules per string and must not exceed the maximum number. As a rule of thumb:
the more PV modules per string, the more viable the planning of the PV array
where:
29
Coordination between inverter and PV generator (9)
• String Number
With a defined total power of the PV array and a predefined number of PV modules
per string, it is possible to calculate the minimum number of strings required to
achieve the total power. The minimum number of strings can be calculated from the
ratio of the total PV array power and the power of all the PV modules of a string
where:
nminSTR: Minimum number of strings
PDCGEN: PV array power
nMODSTR: Number of PV modules per string
PmaxMOD: Maximum power of PV module 30
Information on Equipment Data Sheet
31
Example 1: 100 kW PV Plant
Gen PV
Total N of modules 312
N of strings 24
Modules / string 13
P module (Wp) 335
P array(Wp) 104520
Uoc single module (Vdc) 67.9
Umpp single module (Vdc) 57.3 (Voltage @ Pmax point)
Sunpower X21-335
Ct Uo %/K -0.246
Isc (A) 6.23
Ct Isc %/K 0.056
Impp (A) 5.85
UMAX Inv (Vdc) 1000
Udc activation inv (Vdc) 485
N MPPT / inv module 1
Pmax (W) 110000 ABB PVI-110.0 (2x55 kW) OK
Max Input current /MPPT (A) 123
UMPPT min 485
UMPPT max 950
String check
UocxNtot (Vdc) 882.7
N of strings 1
Modules / string 13
Uoc max @ STC 882.7 OK
32
Example 1: 100 kW PV Plant
33
Information on Equipment Data Sheet
34
Example 2: 300 kW PV Plant
Gen PV
Total N of modules 936
N of strings 72
Modules / string 13
P module (Wp) 335
P array(Wp) 313560
Uoc single module (Vdc) 67.9
Umpp single module (Vdc) 57.3 (Voltage @ Pmax point)
Sunpower X21-335
Ct Uo %/K -0.246
Isc (A) 6.23
Ct Isc %/K 0.056
Impp (A) 5.85
UMAX Inv (Vdc) 1000
Udc activation inv (Vdc) 485
N MPPT / inv module 1
Pmax (W) 330000 ABB PVI-330.0 OK
Max Input current /MPPT (A) 123
UMPPT min 485
UMPPT max 950
String check
UocxNtot (Vdc) 882.7
N of strings 1
Modules / string 13
Uoc max @ STC 882.7 OK
35
Example 2: 300 kW PV Plant
36
Certification Training Course
38
Design of solar PV systems
Effects of the partial shading
39
Design of solar PV systems
Effects of the partial shading
40
Design of solar PV systems
Effects of the partial shading
41
Design of solar PV systems
Effects of the partial shading
42
Design of solar PV systems
Effects of the partial shading
43
Design of solar PV systems
Effects of the partial shading
44
Design of solar PV systems
Effects of the partial shading
45
Design of solar PV systems
Effects of the partial shading
• As a rule, the reciprocal shading can be considered acceptable or negligible if In
the 2-3 hours around noon at 21 December the sun height angle h is greater or
equal to the obstruction angle L
• This angle may be calculated or read on a sun-paths diagram
• It can be also estimated considering that the sun height at noon of the 21
December is h_21_Dec_Noon = 90 –(+ 23.45)
This value should be decreased of 2-3° in order to take into account the
variations of h around noon
46