Doc No G41000107

Document Type Preventative Maintenance Plan Revision B


Created By J. McEwan
Approved By A. Moodie
Equipment Type Y.Cube 2.0- Variant 0 and 1
Approval Date 30/08/2019

Assign. Error Error Action R & M Documentation


Interval Tolerance Description
Type Symptom Cause Code Reference
Check
Batteries and HVAC:
Remote
N/A 50 N/A C0087 A0013  Alarm & trip log. Investigate any abnormalities. WebUI Operating Manual
Monitoring
 Ambient temperature in vicinity of batteries (should be 23±5°C)
 Humidity in battery room and record (0.85% recommended).
Check
Fire Suppression System:
 Check pipe connections to ensure all pipe runs are intact and joints and
supports are firm.
HVAC System:
±2  Clean air filters and replace as required (site condition based). P06000992
6 Months 50 506M C0087 A0013
Weeks  Clean heating coils.
 Visually inspect coolant and refrigerant hoses.
Container Enclosure:
 Grease container door and hinges if required.
Inverter Flex Convert FC1000:
P06000995
 Clean heat exchanger (Condition based).

Page 1 of 3
Doc No G41000107
Document Type Preventative Maintenance Plan Revision B
Created By J. McEwan
Approved By A. Moodie
Equipment Type Y.Cube 2.0- Variant 0 and 1
Approval Date 30/08/2019

Assign. Error Error Action R & M Documentation


Interval Tolerance Description
Type Symptom Cause Code Reference
Check
Circuit Breaker:
 Carry out NW25 circuit breaker maintenance. P06000993
Inverter Flex Convert FC1000:
 Draw coolant sample and test using refractometer. P06000995
 Top up cooling system if pressure <0.8 Bar.
 Inspect cooling system for leaks and hoses for cracks.
 Listen for humming noises from cooling pump and fan motor.
 Open inspection panels and vacuum clean if required.
Batteries Samsung M2f / P3 (264S):
WebUI Operating Manual
 Check 1-year accumulated battery information logged by EMS (Energy
Monitoring System).
 Measure the insulation resistance between battery (+) and GND and
± 500
battery (-) and GND (with DC 1000 for 60 seconds.
Yearly Operating 50 50Y C0087 A0013
Fire Suppression System: P06000996
Hours
 Check pressure on Novec 1230 Cylinder
 Recertify Fire Suppression System certification by authorised fire
suppression system technician.
 Check air flow to determine if flow rate has reduced.
 Conduct smoke tests and verify detector performance.
DTG 800/1 Transformer1:
 Inspect windings/cooling ducts surfaces. Clean if required.
 Measure temperature sensor resistance.
 Insulation Condition.
 Windings are arranged symmetrically and fitted tightly.
 No foreign matter such as nuts, bolts, tools left on the transformer
surface, windings, cooling ducts and between windings and core. Clean
if required.
Check
Batteries Samsung M2f / P3 (264S): WebUI Operating Manual
2 Years ± 73 Days 50 5012K C0087 A0013  Calibrate temperature and humidity sensors and check for any
abnormalities.
Inverter Flex Convert FC1000:
 Draw coolant sample and send to lab for brine testing. P06000995

1 DTG 800/1 Transformer check is only applicable to the Y.Cube 2.0 Variant 0.
Page 2 of 3
Doc No G41000107
Document Type Preventative Maintenance Plan Revision B
Created By J. McEwan
Approved By A. Moodie
Equipment Type Y.Cube 2.0- Variant 0 and 1
Approval Date 30/08/2019

Assign. Error Error Action R & M Documentation


Interval Tolerance Description
Type Symptom Cause Code Reference
Replace
Inverter Flex Convert FC1000: P06000995
±1,000  Replace coolant hoses.
5 Years Operating 50 50G60 C0087 A0013  Replace coolant.
Hours HVAC System:
 PRV Valve. Must be inspected by an approved body that complies with
the pressure equipment directive 97/23/EC.

Revision History
Revision Prepared Reviewed Approved
Revision Details of Changes
Date By By By
A 20/03/2019 First Issue J. McEwan R. Davies M. Bjorkman
B 30/08/2019 Interval amended for NW25 Circuit breaker maintenance, changed from 6 months to yearly. J. McEwan J. Noble A. Moodie