Rakesh Report

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 81

DHANUSH ENGG SERVICES (INDIA) PVT.LTD.

HYDERABAD

This is to certify that Project report entitled HVAC for Multi-storeyedCommercial building

consisting of G+2Floors the bonafide work done by RAKESH KUMAR SHARMA in the partial

fulfillment of the HVAC Design& Drafting Course

Course duration 21/02/2022 to 06/04/2022.

Under the Guidance of:

Mrs.D.T.S.Gayatri Mr.ChakradharMajety.

(HVAC Design& Drafting Faculty) Director

DHANUSH ENGG SERVICES INDIA PVT.LTD.


Dhanush MEP Centre, 2nd Floor,H.No:6-3-788/A/9, Durga Nagar Colony,
Opp: Sitara Paradise Lane, Ameerpet, Hyderabad, Telangana, INDIA
www.meptrainings.com;www.mepjobsindia.com
M: 09908080813 , PH: 040-40064413
ABSTRACT
PROJECT TITLE: - Air conditioning for Commercial building consisting of G+2 floors with
cellar.

NOVELTY:-
This Project is about Air conditioning for G+2 levels with XXXX Zones. Each Zones consist two
Bedrooms i.e. Bedroom, Master Bedroom. Every floor need to be supplied with different Air condition
system provided as requested.

DESCRIPTION :-

➢ ∆U can be calculated based on specification for material used by the Architecture/Civil designer for the project.

➢ ∆T can be calculated based on specification for material and in direction to be used i.e. North, South, East, West,
North West, North East, South West, South East.
➢ Watts per square feet can be calculated based on Power load consumption data given by the electrical designers for
different usage Area i.e. Lighting, Appliances in an Area.

➢ Heat Load Calculation can be done in E20 form Sheets i.e. calculation of Solar heat gain, Transmission heat gain,
Transmission Heat gain except walls & roof, Room sensible heat,

Room latent heat, Effective room total heat, Infiltration, outside Air total heat, CFM Ventilation, Effective room
sensible heat factor (ESHRF).

➢ Selection of Equipment can be calculated based on type of refrigeration i.e Direct refrigeration based on maximum TR
for room required, Indirect Refrigeration based on CFM values of the area.

➢ Duct Sizing can be done using duct sizer McQuay Software. Static pressure calculation can be done By calculating St.
Pressure in Straight duct & Standard equipments used in Ducts i.e. reducer, elbow, VCD, FCD, SA etc. Values of
static pre

➢ ssure help in determine Blower size of AHU. BOQ can be calculated using details of width and height and length of
straight ducts.

➢ Piping Size Calculation for Chiller Units can be done by using Friction chart based on GPM and velocity of the water.

➢ Pump Calculation can be done for Chiller Units by calculating GPM, total suction head loss, total discharge head
loss, total dynamic head loss.

➢ Finally SLD & DLD details have been shown on AutoCAD Software with all details require for Installation on site.
TABLE OF CONTENT
1. ABSTRACT

2. INTRODUCTION

3. PROJECT CONSIDERATIONS

4. CIVIL PLANS

5. E – 20 FORMS

6. HLC SUMMARY SHEETS

7. SINGLE LINE AND DOUBLE LINE DIAGRAMS

8. DUCTING BILL OF QUANTITIES

9. PIPING INTRODUCTION

10. PUMP HEAD CALCULATIONS

11. PIPING LAYOUTS SLD & DLD

12. PIPING BILL OF QUANTITIES

13. MASTER BILL OF QUANTITIES

14. COMPANY CATALOGUES

15. CONCLUSION
INTRODUCTION

Introduction:
Heating, Ventilating and Air Conditioning, HVAC, is a huge field. HVAC systems include a range from the simplest
hand-stoked stove, used for comfort heating, to the extremely reliable total air-conditioning systems found in
submarines and space shuttles. Cooling equipment varies from the small domestic unit to refrigeration machines that
are 10,000 times the size, which are used in industrial processes. Depending on the complexity of the requirements,
the HVAC designer must consider many more issues than simply keeping temperatures comfortable. This chapter will
introduce you to the fundamental concepts that are used by designers to make decisions about system design,
operation, and maintenance.

Brief History of HVAC:

For millennia, people have used fire for heating. Initially, the air required to keep the fire going ensured adequate
ventilation for the occupants. However, as central furnaces with piped steam or hot water became available for
heating, the need for separate ventilation became apparent. By the late 1880s, rules of thumb for ventilation design
were developed and used in many countries. In 1851 Dr. John Gorrie was granted U.S. patent 8080 for a refrigeration
machine. By the 1880s, refrigeration became available for industrial purposes. Initially, the two main uses were
freezing meat for transport and making ice. However, in the early 1900s there was a new initiative to keep buildings
cool for comfort. Cooling the New York Stock Exchange, in 1902, was one of the first comfort cooling systems.
Comfort cooling was called “air conditioning.” Our title, “HVAC,” thus captures the development of our industry. The
term “air conditioning” has gradually changed, from meaning just cooling, to the total control of:
Temperature
Moisture in the air (humidity)
Supply of outside air for ventilation
Filtration of airborne particles
Air movement in the occupied space
Throughout the rest of this text we will use the term “air conditioning” to include all of these issues and continue to
use “HVAC” where only some of the elements of full air conditioning are being controlled.

Introduction to Air-conditioning Processes:

As mentioned earlier, the term “air conditioning,” when properly used, now means the total control of temperature,
moisture in the air (humidity), supply of outside air for ventilation, filtration of airborne particles, and air movement in
the occupied space. There are seven main processes required to achieve full air conditioning and they are listed and
explained below:
The processes are:

1. Heating—the process of adding thermal energy (heat) to the conditioned space for the purposes of raising or
maintaining the temperature of the space.
2. Cooling—the process of removing thermal energy (heat) from the conditioned space for the purposes of lowering
or maintaining the temperature of the space.
3. Humidifying—the process of adding water vapor (moisture) to the air in the conditioned space for the purposes of
raising or maintaining the moisture content of the air.
4. Dehumidifying—the process of removing water vapor (moisture) from the air in the conditioned space for the
purposes of lowering or maintaining the moisture content of the air.
5. Cleaning—the process of removing particulates, (dust etc.,) and biological contaminants, (insects, pollen etc.,)
from the air delivered to the conditioned space for the purposes of improving or maintaining the air quality.
Introduction to HVAC 3 4 Fundamentals of HVAC
6. Ventilating—the process of exchanging air between the outdoors and the conditioned space for the purposes of
diluting the gaseous contaminants in the air and improving or maintaining air quality, composition and freshness.
Ventilation can be achieved either through natural ventilation or mechanical ventilation. Natural ventilation is driven
by natural draft, like when you open a window. Mechanical ventilation can be achieved by using fans to draw air in
from outside or by fans that exhaust air from the space to outside.
7. Air Movement—the process of circulating and mixing air through conditioned spaces in the building for the
purposes of achieving the proper ventilation and facilitating the thermal energy transfer.
The requirements and importance of the seven processes varies. In a climate that stays warm all year, heating may not
be required at all. Conversely, in a cold climate the periods of heat in the summer may be so infrequent as to make
cooling unnecessary. In a dry desert climate, dehumidification may be redundant, and in a hot, humid climate
dehumidification may be the most important design aspect of the air-conditioning system.

Defining Air conditioning:

The actual use of the words “air conditioning” varies considerably, so it is always advisable to check what is really
meant. Consider, for example, “window air conditioners.” The vast majority provide cooling, some dehumidification,
some filtering, and some ventilation when the outside temperature is well above freezing. They have no ability to heat
or to humidify the conditioned space and do not cool if it is cold outside. In colder climates, heating is often provided
by a separate, perimeter heating system that is located within the outside walls. The other functions: cooling,
humidification, dehumidification, cleaning, ventilating and air movement, are all provided by a separate air system,
often referred to as the “air-conditioning system.” It is important to remember that both the heating and the air system
together form the “air-conditioning” system for the space.
Location and Thermal Conditions
Building Location : lakhnow
Orientation : Equal Share of Wall on All Sides
Application : Commercial building
Longitude : 26.52
Latitude : 26.52
Elevation : 111Mtr

Sp.Humidity
Condition DBT(°F) WBT(°F) RH (%) Daily Range(°F)
(Gr/Lb)
Ambient/Surroundings 109 79 26 102 30 F
Room Thermal
75 62 50 66 Correction Value -18
Conditions
Difference( ∆ ) 34 17 24 36

Note: Room Comfort thermal Conditions are 22 to 27 Degree centigrade @ Rh is up to 70%

MATERIAL SPECIFICATIONS (CIVIL BUILDING MATERIALS)


Many materials are used for the buildings such as material for walls (i.e. Concrete hollow blocks, cement, sand etc.), Window
materials (type of glass), Door’s (type of door, i.e. wooden, glass etc.), material for roof, floor, and partition walls. So for this 6
floors project specification we have list of material to be utilized by civil contractor.

WINDOW MATERIALS:

Ordinary glass- outside awning (vented sides top) medium color.

Dimensions of Window :(3FX 4ft) Height

DOOR MATERIALS:

Wooden door are utilized for this project.

Dimensions of Door (L x B): (3FX7ft) Height

MASONRY WALL MATERIAL:

Solid brick- Common only- 8" Thick wall - 80lb/sft weight- 1" Insulating Board plain on furring

Weight of such walls is expressed in Lb/sq ft – 60


MASONARY PARTITION WALL MATERIAL:

Hollow Gypsum tile-4"thick (13lb/sft weight) Both sides finished- 1" insulating board plain on furring (4lb/sft)

Weight of such partition walls is expressed in Lb/sq ft – 13

MASONARY ROOF MATERIAL:

Concrete (sand and gravel agg)-8" Thick-93lb/sft-suspended acou tile(2lb/sft) 3" insulation on top of deck

Weight of such roof is expressed in Lb/sq ft – 70

MASONARY FLOOR MATERIAL:

Concrete (sand and gravel agg)-8" Thick-93lb/sft- acou tile of furring (2lb/sft) 3/4" insulation on top of deck

Weight of such roof is expressed in Lb/sq ft – 70

TRANSMISSION COEFFICIENT ∆U
Transmission coefficient value changes for each type of material used for the civil building.

So, as per ISHRAE /ASHRAE standards, see below data table of ∆U for different material used for our project.

Coefficient
∆U
Factor
∆U Glass .65
∆U Masonry Wall 0.43
∆U Roof 0.28
∆U Partition Wall 0.31
∆U Floor 0.57

CHANGE IN TEMPERATURE ∆T
Similarly for different building materials temperature change will vary. See below calculation data table for our project load
calculation based on different direction consideration i.e. North, South, East, and West etc.

∆T Change in Temperature in °F
∆T
Direction ∆T Wall Direction ∆T Glass Condition Roof
North 12 F North 14F
South 26 F South 12 F Exposed
46
East 10 F East 12 F to Sun
West 26 F West 164 F
CORRECTION FACTOR FOR WALLS & PARTION WALLS:

This correction factor is used for walls and partition walls when exposed to sun. so the change in temperature will be sum of
correction factor and temperature average at 8AM to 4PM of any direction.

So, for the basis of Load calculation for project, refer below table:

Correction Factor for


Wall & Roof 14
Temperature (°F)
Civil plans
Ground Floor
First floor
Second Floor
Terrors plan
E 20 SHEET
Ground floor
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 1
CLIENT XYZ AREA ( SqFt) (WxH) 192.92
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 1,736.28
Area or Sun Gain or Estimate for Summer
Item Factor (U) Btu/Hour Watts
Quantity Temp. Diff. Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x x 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x x 0.00 CFM Per SqFt 0.33 Sqft x 192.92 = 63.66
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 1,736.28 x 3.00 x1/60 = 86.81
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 103.80 SqFt x 24.00 F x 0.43 1,071.22 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 210.60 SqFt x 40.00 F x 0.43 3,622.32 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 0.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 192.92 SqFt x 29.00 F x 0.57 3,188.97 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 742.51 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 348.98 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 192.92 SqFt x 1.50 W/SqFt x 3.415 988.23 Grand Total Heat = 2.02 TR
Equipments 192.92 2.00 Watts x 3.415 1,317.64
Power kW/Hp x 0.00
Sub Total 13,632.46
Factor 5-10% 1,363.25
Effective Room Sensible Heat 14,995.71 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.02 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 17,177.23
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 23,488.99
Factor 1 - 3% 704.67
GRAND TOTAL HEAT 24,193.66
TONS=GRAND TOTAL HEAT/12000 2.02
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor


LOCATION Lakhnow (UP) SPACE REFERENCE shop no 2
CLIENT XYZ AREA ( SqFt) (WxH) 237.26
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,135.30
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 237.26 = 78.29
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 2,135.30 x 3.00 x1/60 = 106.76
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 141.48 SqFt x 24.00 F x 0.43 1,460.07 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.85
Roof 0.00 SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 237.26 SqFt x 29.00 F x 0.57 3,921.91 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 635.18 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 298.53 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 237.26 SqFt x 1.50 W/SqFt x 3.415 1,215.34 Grand Total Heat = 1.83 TR
Equipments 237.26 2.00 Watts x 3.415 1,620.49
Power kW/Hp x 0.00
Sub Total 11,661.89
Factor 5-10% 1,166.19
Effective Room Sensible Heat 12,828.07 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.83 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53
EFFECTIVE ROOM TOTAL HEAT 15,009.60
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 21,321.36
Factor 1 - 3% 639.64
GRAND TOTAL HEAT 21,961.00
TONS=GRAND TOTAL HEAT/12000 1.83
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 3
CLIENT XYZ AREA ( SqFt) (WxH) 229.27
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,063.43
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 229.27 = 75.66
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 2,063.43 x 3.00 x1/60 = 103.17
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 136.32 SqFt x 24.00 F x 0.43 1,406.82 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.86
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 127.32 SqFt x 29.00 F x 0.30 1,107.68 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 229.27 SqFt x 29.00 F x 0.57 3,789.83 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 637.57 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 299.66 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 229.27 SqFt x 1.00 W/SqFt x 3.415 782.96 Grand Total Heat = 1.83 TR
Equipments 229.27 1.50 Watts x 3.415 1,174.44
Power kW/Hp x 0.00
Sub Total 11,705.81
Factor 5-10% 1,170.58
Effective Room Sensible Heat 12,876.39 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.83 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53
EFFECTIVE ROOM TOTAL HEAT 15,057.92
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 21,369.68
Factor 1 - 3% 641.09
GRAND TOTAL HEAT 22,010.77
TONS=GRAND TOTAL HEAT/12000 1.83
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 4
CLIENT XYZ AREA ( SqFt) (WxH) 169.32
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 1,523.88
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 169.32 = 55.88
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 1,523.88 x 3.00 x1/60 = 76.19
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 184.32 SqFt x 24.00 F x 0.43 1,902.18 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.86
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 299.52 SqFt x 29.00 F x 0.30 2,605.82 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 169.32 SqFt x 29.00 F x 0.57 2,798.86 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 664.30 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 312.22 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 169.32 SqFt x 1.00 W/SqFt x 3.415 578.23 Grand Total Heat = 1.88 TR
Equipments 169.32 1.50 Watts x 3.415 867.34
Power kW/Hp x 0.00
Sub Total 12,196.52
Factor 5-10% 1,219.65
Effective Room Sensible Heat 13,416.17 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.88 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53
EFFECTIVE ROOM TOTAL HEAT 15,597.70
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 21,909.46
Factor 1 - 3% 657.28
GRAND TOTAL HEAT 22,566.74
TONS=GRAND TOTAL HEAT/12000 1.88
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 5
CLIENT XYZ AREA ( SqFt) (WxH) 241.17
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,170.51
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 5.00 = 150.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 241.17 = 79.59
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 2,170.51 x 3.00 x1/60 = 108.53
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 140.88 SqFt x 24.00 F x 0.43 1,453.88 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.86
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 241.56 SqFt x 29.00 F x 0.30 2,101.57 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 241.17 SqFt x 29.00 F x 0.57 3,986.54 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 732.86 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 150.00 CFM x 34.00 x BFX1.08 826.20
Internal Heat = 344.44 L/s
People 5.00 Nos. x 245.00 Btu/Hour Per Person 1,225.00 TOTAL HEAT CAPACITY
Lighting 241.17 SqFt x 1.00 W/SqFt x 3.415 823.59 Grand Total Heat = 2.16 TR
Equipments 241.17 1.50 Watts x 3.415 1,235.39
Power kW/Hp x 0.00
Sub Total 13,455.30
Factor 5-10% 1,345.53
Effective Room Sensible Heat 14,800.83 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.16 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 150.00 CFM x 37.00 Gr/Lb x BFx0.68 566.10
People 5.00 Nos. x 205.00 Btu/Hour Per Person 1,025.00
Sub Total 2,446.54
Factor 2.5 - 5% 61.16
Effective Room Latent Heat 2,507.70
EFFECTIVE ROOM TOTAL HEAT 17,308.53
OUTSIDE AIR HEAT
Sensible 150.00 CFM x 34.00 F(TD) x CF x 1.08 4,681.80
Latent 150.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,207.90
OUTSIDE AIR TOTAL HEAT 7,889.70 Notes:
GRAND SUB-TOTAL HEAT 25,198.23
Factor 1 - 3% 755.95
GRAND TOTAL HEAT 25,954.18
TONS=GRAND TOTAL HEAT/12000 2.16
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 6
CLIENT XYZ AREA ( SqFt) (WxH) 233.97
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,105.73
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 233.97 = 77.21
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 2,105.73 x 3.00 x1/60 = 105.29
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 136.32 SqFt x 24.00 F x 0.43 1,406.82 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.85
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 233.97 SqFt x 29.00 F x 0.57 3,867.52 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 627.18 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 294.77 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 233.97 SqFt x 1.50 W/SqFt x 3.415 1,198.51 Grand Total Heat = 1.82 TR
Equipments 233.97 2.00 Watts x 3.415 1,598.02
Power kW/Hp x 0.00
Sub Total 11,514.95
Factor 5-10% 1,151.50
Effective Room Sensible Heat 12,666.45 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.82 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 14,847.98
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 21,159.74
Factor 1 - 3% 634.79
GRAND TOTAL HEAT 21,794.53
TONS=GRAND TOTAL HEAT/12000 1.82
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 7
CLIENT XYZ AREA ( SqFt) (WxH) 233.97
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,105.73
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 233.97 = 77.21
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 2,105.73 x 3.00 x1/60 = 105.29
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 215.16 SqFt x 26.00 F x 0.43 2,405.49 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 127.32 SqFt x 24.00 F x 0.43 1,313.94 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 233.97 SqFt x 29.00 F x 0.57 3,867.52 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 753.14 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 353.97 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 233.97 SqFt x 1.50 W/SqFt x 3.415 1,198.51 Grand Total Heat = 2.03 TR
Equipments 233.97 2.00 Watts x 3.415 1,598.02
Power kW/Hp x 0.00
Sub Total 13,827.56
Factor 5-10% 1,382.76
Effective Room Sensible Heat 15,210.32 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.03 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 17,391.85
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 23,703.61
Factor 1 - 3% 711.11
GRAND TOTAL HEAT 24,414.71
TONS=GRAND TOTAL HEAT/12000 2.03
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 8
CLIENT XYZ AREA ( SqFt) (WxH) 265.96
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,393.64
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N 12.00 SqFt x 14.00 x 0.65 109.20
Glass - NE SqFt x x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt0.33 Sqft x 265.96 = 87.77
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,393.64
Cu.ftx 3.00 x1/60 = 119.68
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 159.96 SqFt x 26.00 F x 0.43 1,788.35 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.88
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 150.96 SqFt x 29.00 F x 0.30 1,313.35 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 265.95 SqFt x 29.00 F x 0.57 4,396.15 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 769.96 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 361.88 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 265.96 SqFt x 1.50 W/SqFt x 3.415 1,362.38 Grand Total Heat = 2.06 TR
Equipments 265.96 2.00 Watts x 3.415 1,816.51
Power kW/Hp x 0.00
Sub Total 14,136.43
Factor 5-10% 1,413.64
Effective Room Sensible Heat 15,550.07 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.06 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 17,731.60
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 24,043.36
Factor 1 - 3% 721.30
GRAND TOTAL HEAT 24,764.66
TONS=GRAND TOTAL HEAT/12000 2.06
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 9
CLIENT XYZ AREA ( SqFt) (WxH) 280.07
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,520.63
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N 12.00 SqFt x 14.00 x 0.65 109.20
Glass - NE SqFt x x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 280.07 = 92.42
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 2,520.63 x 3.00 x1/60 = 126.03
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 169.08 SqFt x 26.00 F x 0.43 1,890.31 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.89
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 160.08 SqFt x 29.00 F x 0.30 1,392.70 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 280.07 SqFt x 29.00 F x 0.57 4,629.56 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 801.73 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 376.81 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 280.07 SqFt x 1.50 W/SqFt x 3.415 1,434.66 Grand Total Heat = 2.10 TR
Equipments 280.07 2.00 Watts x 3.415 1,912.88
Power kW/Hp x 0.00
Sub Total 14,719.78
Factor 5-10% 1,471.98
Effective Room Sensible Heat 16,191.76 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.10 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 3.00 Nos. x 205.00 Btu/Hour Per Person 615.00
Sub Total 1,923.32
Factor 2.5 - 5% 48.08
Effective Room Latent Heat 1,971.40 2.00
EFFECTIVE ROOM TOTAL HEAT 18,163.17
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 24,474.93
Factor 1 - 3% 734.25
GRAND TOTAL HEAT 25,209.17
TONS=GRAND TOTAL HEAT/12000 2.10
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 10
CLIENT XYZ AREA ( SqFt) (WxH) 222.60
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,003.40
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt 0.33 Sqft x 222.60 = 73.46
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft
2,003.40 x 3.00 x1/60 = 100.17
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 132.00 SqFt x 26.00 F x 0.43 1,475.76 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 201.60 SqFt x 40.00 F x 0.43 3,467.52 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.89
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 222.60 SqFt x 29.00 F x 0.57 3,679.58 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 866.73 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 407.36 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 222.60 SqFt x 1.50 W/SqFt x 3.415 1,140.27 Grand Total Heat = 2.23 TR
Equipments 222.60 2.00 Watts x 3.415 1,520.36
Power kW/Hp x 0.00
Sub Total 15,913.16
Factor 5-10% 1,591.32
Effective Room Sensible Heat 17,504.48 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.23 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 19,686.01
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 25,997.77
Factor 1 - 3% 779.93
GRAND TOTAL HEAT 26,777.70
TONS=GRAND TOTAL HEAT/12000 2.23
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 11
CLIENT XYZ AREA ( SqFt) (WxH) 243.38
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,190.38
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 4.00 = 120.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt0.33 Sqft x 243.38 = 80.31
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,190.38
Cu.ftx 3.00 x1/60 = 109.52
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 145.44 SqFt x 40.00 F x 0.43 2,501.57 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.88
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 243.38 SqFt x 29.00 F x 0.57 4,023.07 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 765.97 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 360.01 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 243.38 SqFt x 1.50 W/SqFt x 3.415 1,246.69 Grand Total Heat = 2.06 TR
Equipments 243.38 2.00 Watts x 3.415 1,662.29
Power kW/Hp x 0.00
Sub Total 14,063.30
Factor 5-10% 1,406.33
Effective Room Sensible Heat 15,469.63 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.06 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 17,651.16
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 23,962.92
Factor 1 - 3% 718.89
GRAND TOTAL HEAT 24,681.80
TONS=GRAND TOTAL HEAT/12000 2.06
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 12
CLIENT XYZ AREA ( SqFt) (WxH) 229.27
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,063.43
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 4.00 = 120.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt0.33 Sqft x 229.27 = 75.66
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,063.43
Cu.ftx 3.00 x1/60 = 103.17
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 136.32 SqFt x 40.00 F x 0.43 2,344.70 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.89
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 349.92 SqFt x 29.00 F x 0.30 3,044.30 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 229.27 SqFt x 29.00 F x 0.57 3,789.83 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 901.35 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 423.64 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 229.27 SqFt x 1.50 W/SqFt x 3.415 1,174.44 Grand Total Heat = 2.29 TR
Equipments 229.27 2.00 Watts x 3.415 1,565.91
Power kW/Hp x 0.00
Sub Total 16,548.87
Factor 5-10% 1,654.89
Effective Room Sensible Heat 18,203.76 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.29 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 20,385.29
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 26,697.05
Factor 1 - 3% 800.91
GRAND TOTAL HEAT 27,497.96
TONS=GRAND TOTAL HEAT/12000 2.29
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 13
CLIENT XYZ AREA ( SqFt) (WxH) 236.32
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,126.88
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 4.00 = 120.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt0.33 Sqft x 236.32 = 77.99
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,126.88
Cu.ftx 3.00 x1/60 = 106.34
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 140.88 SqFt x 40.00 F x 0.43 2,423.14 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.89
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 354.48 SqFt x 29.00 F x 0.30 3,083.98 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 236.32 SqFt x 29.00 F x 0.57 3,906.37 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 918.72 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 431.80 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 236.32 SqFt x 1.50 W/SqFt x 3.415 1,210.55 Grand Total Heat = 2.32 TR
Equipments 236.32 2.00 Watts x 3.415 1,614.07
Power ss x 0.00
Sub Total 16,867.78
Factor 5-10% 1,686.78
Effective Room Sensible Heat 18,554.55 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.32 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 20,736.08
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 27,047.84
Factor 1 - 3% 811.44
GRAND TOTAL HEAT 27,859.28
TONS=GRAND TOTAL HEAT/12000 2.32
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 14
CLIENT XYZ AREA ( SqFt) (WxH) 244.19
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,197.67
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.65 0.00 CFM Per SqFt0.33 Sqft x 244.19 = 80.58
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,197.67
Cu.ftx 3.00 x1/60 = 109.88
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 187.20 SqFt x 40.00 F x 0.43 3,219.84 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x 40.00 F x 0.43 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.88
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 178.20 SqFt x 29.00 F x 0.30 1,550.34 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 244.19 SqFt x 29.00 F x 0.57 4,036.46 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 826.22 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 388.32 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 244.19 SqFt x 1.50 W/SqFt x 3.415 1,250.84 Grand Total Heat = 2.16 TR
Equipments 244.19 2.00 Watts x 3.415 1,667.82
Power ss x 0.00
Sub Total 15,169.38
Factor 5-10% 1,516.94
Effective Room Sensible Heat 16,686.32 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.16 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 18,867.85
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 25,179.61
Factor 1 - 3% 755.39
GRAND TOTAL HEAT 25,935.00
TONS=GRAND TOTAL HEAT/12000 2.16
PROJECT Dhanush Engg Services Ltd. FLOOR Ground Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 15
CLIENT XYZ AREA ( SqFt) (WxH) 250.34
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,253.06
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.65 0.00 CFM Per SqFt0.33 Sqft x 250.34 = 82.61
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,253.06
Cu.ftx 3.00 x1/60 = 112.65
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 169.09 SqFt x 40.00 F x 0.43 2,908.35 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x 40.00 F x 0.43 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.88
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 160.08 SqFt x 29.00 F x 0.30 1,392.70 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor 250.34 SqFt x 29.00 F x 0.57 4,138.12 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 810.21 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 380.80 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 250.34 SqFt x 1.50 W/SqFt x 3.415 1,282.37 Grand Total Heat = 2.13 TR
Equipments 250.34 2.00 Watts x 3.415 1,709.82
Power ss x 0.00
Sub Total 14,875.43
Factor 5-10% 1,487.54
Effective Room Sensible Heat 16,362.98 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.13 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,128.32
Factor 2.5 - 5% 53.21
Effective Room Latent Heat 2,181.53 2.00
EFFECTIVE ROOM TOTAL HEAT 18,544.50
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,745.44 3.00
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,566.32 4.00
OUTSIDE AIR TOTAL HEAT 6,311.76 Notes:
GRAND SUB-TOTAL HEAT 24,856.26
Factor 1 - 3% 745.69
GRAND TOTAL HEAT 25,601.95
TONS=GRAND TOTAL HEAT/12000 2.13
First Floor

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor


LOCATION Lakhnow (UP) SPACE REFERENCE shop no 20&21
CLIENT XYZ AREA ( SqFt) (WxH) 437.22
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 3,935.01
Area or Sun Gain or Estimate for Summer
Item Factor (U) Btu/Hour Watts
Quantity Temp. Diff. Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 9.00 = 270.00
Glass - W SqFt x x 0.00 CFM Per SqFt 0.33 Sqft x 437.22 = 144.28
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 3,935.01 x 3.00 x1/60 = 196.75
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 210.60 SqFt x 24.00 F x 0.43 2,173.39 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 282.84 SqFt x 40.00 F x 0.43 4,864.85 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 0.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 1,114.03 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 270.00 CFM x 34.00 x BFX1.08 1,982.88
Internal Heat = 523.59 L/s
People 9.00 Nos. x 245.00 Btu/Hour Per Person 2,205.00 TOTAL HEAT CAPACITY
Lighting 437.22 SqFt x 1.50 W/SqFt x 3.415 2,239.68 Grand Total Heat = 3.35 TR
Equipments 437.22 2.00 Watts x 3.415 2,986.24
Power kW/Hp x 0.00
Sub Total 19,250.43
Factor 5-10% 1,925.04
Effective Room Sensible Heat 21,175.48 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 3.35 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 270.00 CFM x 37.00 Gr/Lb x BFx0.68 1,358.64
People 9.00 Nos. x 205.00 Btu/Hour Per Person 1,845.00
Sub Total 4,361.00
Factor 2.5 - 5% 109.03
Effective Room Latent Heat 4,470.03 2.00
EFFECTIVE ROOM TOTAL HEAT 25,645.50
OUTSIDE AIR HEAT
Sensible 270.00 CFM x 34.00 F(TD) x CF x 1.08 7,931.52 3.00
Latent 270.00 CFM x 37.00 Gr/Lb x CF x 0.68 5,434.56 4.00
OUTSIDE AIR TOTAL HEAT 13,366.08 Notes:
GRAND SUB-TOTAL HEAT 39,011.58
Factor 1 - 3% 1,170.35
GRAND TOTAL HEAT 40,181.93
TONS=GRAND TOTAL HEAT/12000 3.35
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor


LOCATION Lakhnow (UP) SPACE REFERENCE shop no 22
CLIENT XYZ AREA ( SqFt) (WxH) 229.28
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,063.50
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 5.00 = 150.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 229.28 = 75.66
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 2,063.50 x 3.00 x1/60 = 103.18
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 136.32 SqFt x 24.00 F x 0.43 1,406.82 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof 0.00 SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 127.32 SqFt x 29.00 F x 0.30 1,107.68 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 543.09 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 150.00 CFM x 34.00 x BFX1.08 1,101.60
Internal Heat = 255.25 L/s
People 5.00 Nos. x 245.00 Btu/Hour Per Person 1,225.00 TOTAL HEAT CAPACITY
Lighting 229.28 SqFt x 1.50 W/SqFt x 3.415 1,174.48 Grand Total Heat = 1.76 TR
Equipments 229.28 2.00 Watts x 3.415 1,565.97
Power kW/Hp x 0.00
Sub Total 9,384.67
Factor 5-10% 938.47
Effective Room Sensible Heat 10,323.14 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.76 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 150.00 CFM x 37.00 Gr/Lb x BFx0.68 754.80
People 5.00 Nos. x 205.00 Btu/Hour Per Person 1,025.00
Sub Total 2,635.24
Factor 2.5 - 5% 65.88
Effective Room Latent Heat 2,701.12
EFFECTIVE ROOM TOTAL HEAT 13,024.26
OUTSIDE AIR HEAT
Sensible 150.00 CFM x 34.00 F(TD) x CF x 1.08 4,406.40
Latent 150.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,019.20
OUTSIDE AIR TOTAL HEAT 7,425.60 Notes:
GRAND SUB-TOTAL HEAT 20,449.86
Factor 1 - 3% 613.50
GRAND TOTAL HEAT 21,063.36
TONS=GRAND TOTAL HEAT/12000 1.76
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lucknow (UP) SPACE REFERENCE shop no 23
CLIENT XYZ AREA ( SqFt) (WxH) 169.43
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 1,524.87
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 169.43 = 55.91
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 1,524.87 x 3.00 x1/60 = 76.24
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 184.44 SqFt x 24.00 F x 0.43 1,903.42 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 175.44 SqFt x 29.00 F x 0.30 1,526.33 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 527.74 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 881.28
Internal Heat = 248.04 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 169.43 SqFt x 1.50 W/SqFt x 3.415 867.91 Grand Total Heat = 1.57 TR
Equipments 169.43 2.00 Watts x 3.415 1,157.21
Power kW/Hp x 0.00
Sub Total 9,119.26
Factor 5-10% 911.93
Effective Room Sensible Heat 10,031.19 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.57 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 603.84
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,279.28
Factor 2.5 - 5% 56.98
Effective Room Latent Heat 2,336.26
EFFECTIVE ROOM TOTAL HEAT 12,367.45
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,525.12
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,415.36
OUTSIDE AIR TOTAL HEAT 5,940.48 Notes:
GRAND SUB-TOTAL HEAT 18,307.93
Factor 1 - 3% 549.24
GRAND TOTAL HEAT 18,857.17
TONS=GRAND TOTAL HEAT/12000 1.57
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor


LOCATION Lakhnow (UP) SPACE REFERENCE shop no 24
CLIENT XYZ AREA ( SqFt) (WxH) 148.32
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 1,334.84
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 3.00 = 90.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 148.32 = 48.94
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 1,334.84 x 3.00 x1/60 = 66.74
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 159.96 SqFt x 24.00 F x 0.43 1,650.79 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 150.96 SqFt x 29.00 F x 0.30 1,313.35 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 459.26 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 90.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 215.85 L/s
People 3.00 Nos. x 245.00 Btu/Hour Per Person 735.00 TOTAL HEAT CAPACITY
Lighting 148.32 SqFt x 1.50 W/SqFt x 3.415 759.75 Grand Total Heat = 1.30 TR
Equipments 148.32 2.00 Watts x 3.415 1,013.00
Power kW/Hp x 0.00
Sub Total 7,935.97
Factor 5-10% 793.60
Effective Room Sensible Heat 8,729.56 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.30 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 90.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 3.00 Nos. x 205.00 Btu/Hour Per Person 615.00
Sub Total 1,923.32
Factor 2.5 - 5% 48.08
Effective Room Latent Heat 1,971.40
EFFECTIVE ROOM TOTAL HEAT 10,700.97
OUTSIDE AIR HEAT
Sensible 90.00 CFM x 34.00 F(TD) x CF x 1.08 2,643.84
Latent 90.00 CFM x 37.00 Gr/Lb x CF x 0.68 1,811.52
OUTSIDE AIR TOTAL HEAT 4,455.36 Notes:
GRAND SUB-TOTAL HEAT 15,156.33
Factor 1 - 3% 454.69
GRAND TOTAL HEAT 15,611.02
TONS=GRAND TOTAL HEAT/12000 1.30
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor


LOCATION Lakhnow (UP) SPACE REFERENCE shop no 25
CLIENT XYZ AREA ( SqFt) (WxH) 151.42
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 1,362.79
W
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour a
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 4.00 = 120.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 151.42 = 49.97
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 1,362.79 x 3.00 x1/60 = 68.14
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 163.56 SqFt x 24.00 F x 0.43 1,687.94 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 154.56 SqFt x 29.00 F x 0.30 1,344.67 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 488.98 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 120.00 CFM x 34.00 x BFX1.08 881.28
Internal Heat = 229.82 L/s
People 4.00 Nos. x 245.00 Btu/Hour Per Person 980.00 TOTAL HEAT CAPACITY
Lighting 151.42 SqFt x 1.00 W/SqFt x 3.415 517.10 Grand Total Heat = 1.51 TR
Equipments 241.17 1.50 Watts x 3.415 1,235.39
Power kW/Hp x 0.00
Sub Total 8,449.51
Factor 5-10% 844.95
Effective Room Sensible Heat 9,294.46 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.51 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 120.00 CFM x 37.00 Gr/Lb x BFx0.68 603.84
People 4.00 Nos. x 205.00 Btu/Hour Per Person 820.00
Sub Total 2,279.28
Factor 2.5 - 5% 56.98
Effective Room Latent Heat 2,336.26
EFFECTIVE ROOM TOTAL HEAT 11,630.72
OUTSIDE AIR HEAT
Sensible 120.00 CFM x 34.00 F(TD) x CF x 1.08 3,525.12
Latent 120.00 CFM x 37.00 Gr/Lb x CF x 0.68 2,415.36
OUTSIDE AIR TOTAL HEAT 5,940.48 Notes:
GRAND SUB-TOTAL HEAT 17,571.20
Factor 1 - 3% 527.14
GRAND TOTAL HEAT 18,098.34
TONS=GRAND TOTAL HEAT/12000 1.51
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 26
CLIENT XYZ AREA ( SqFt) (WxH) 148.21
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 1,333.91
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 3.00 = 90.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 148.21 = 48.91
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft1,333.91 x 3.00 x1/60 = 66.70
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 159.84 SqFt x 24.00 F x 0.43 1,649.55 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.81
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 150.84 SqFt x 29.00 F x 0.30 1,312.31 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 492.95 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 90.00 CFM x 34.00 x BFX1.08 660.96
Internal Heat = 231.69 L/s
People 3.00 Nos. x 245.00 Btu/Hour Per Person 735.00 TOTAL HEAT CAPACITY
Lighting 148.21 SqFt x 1.50 W/SqFt x 3.415 759.22 Grand Total Heat = 1.36 TR
Equipments 233.97 2.00 Watts x 3.415 1,598.02
Power kW/Hp x 0.00
Sub Total 8,518.17
Factor 5-10% 851.82
Effective Room Sensible Heat 9,369.98 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.36 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 90.00 CFM x 37.00 Gr/Lb x BFx0.68 452.88
People 3.00 Nos. x 205.00 Btu/Hour Per Person 615.00
Sub Total 1,923.32
Factor 2.5 - 5% 48.08
Effective Room Latent Heat 1,971.40 2.00
EFFECTIVE ROOM TOTAL HEAT 11,341.39
OUTSIDE AIR HEAT
Sensible 90.00 CFM x 34.00 F(TD) x CF x 1.08 2,643.84 3.00
Latent 90.00 CFM x 37.00 Gr/Lb x CF x 0.68 1,811.52 4.00
OUTSIDE AIR TOTAL HEAT 4,455.36 Notes:
GRAND SUB-TOTAL HEAT 15,796.75
Factor 1 - 3% 473.90
GRAND TOTAL HEAT 16,270.65
TONS=GRAND TOTAL HEAT/12000 1.36
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 26 A
CLIENT XYZ AREA ( SqFt) (WxH) 241.16
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,170.44
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 5.00 = 150.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt0.33 Sqft x 241.16 = 79.58
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,170.44
Cu.ftx 3.00 x1/60 = 108.52
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 140.88 SqFt x 24.00 F x 0.43 1,453.88 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 131.48 SqFt x 29.00 F x 0.30 1,143.88 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 556.13 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 150.00 CFM x 34.00 x BFX1.08 1,101.60
Internal Heat = 261.38 L/s
People 5.00 Nos. x 245.00 Btu/Hour Per Person 1,225.00 TOTAL HEAT CAPACITY
Lighting 241.16 SqFt x 1.50 W/SqFt x 3.415 1,235.34 Grand Total Heat = 1.78 TR
Equipments 241.16 2.00 Watts x 3.415 1,647.12
Power kW/Hp x 0.00
Sub Total 9,609.94
Factor 5-10% 960.99
Effective Room Sensible Heat 10,570.94 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.78 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 150.00 CFM x 37.00 Gr/Lb x BFx0.68 754.80
People 5.00 Nos. x 205.00 Btu/Hour Per Person 1,025.00
Sub Total 2,635.24
S 2.5 - 5% 65.88
Effective Room Latent Heat 2,701.12 2.00
EFFECTIVE ROOM TOTAL HEAT 13,272.06
OUTSIDE AIR HEAT
Sensible 150.00 CFM x 34.00 F(TD) x CF x 1.08 4,406.40 3.00
Latent 150.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,019.20 4.00
OUTSIDE AIR TOTAL HEAT 7,425.60 Notes:
GRAND SUB-TOTAL HEAT 20,697.66
Factor 1 - 3% 620.93
GRAND TOTAL HEAT 21,318.59
TONS=GRAND TOTAL HEAT/12000 1.78
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 27
CLIENT XYZ AREA ( SqFt) (WxH) 475.33
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 4,277.97
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N 12.00 SqFt x 14.00 x 0.65 109.20
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 10.00 = 300.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 475.33 = 156.86
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 4,277.97 x 3.00 x1/60 = 213.90
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 215.16 SqFt x 26.00 F x 0.43 2,405.49 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 289.32 SqFt x 24.00 F x 0.43 2,985.78 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 1,072.91 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 300.00 CFM x 34.00 x BFX1.08 2,203.20
Internal Heat = 504.27 L/s
People 10.00 Nos. x 245.00 Btu/Hour Per Person 2,450.00 TOTAL HEAT CAPACITY
Lighting 475.33 SqFt x 1.50 W/SqFt x 3.415 2,434.88 Grand Total Heat = 3.44 TR
Equipments 475.33 2.00 Watts x 3.415 3,246.50
Power kW/Hp x 0.00
Sub Total 18,539.85
Factor 5-10% 1,853.99
Effective Room Sensible Heat 20,393.84 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 3.44 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 300.00 CFM x 37.00 Gr/Lb x BFx0.68 1,509.60
People 10.00 Nos. x 205.00 Btu/Hour Per Person 2,050.00
Sub Total 4,716.96
Factor 2.5 - 5% 117.92
Effective Room Latent Heat 4,834.88 2.00
EFFECTIVE ROOM TOTAL HEAT 25,228.72
OUTSIDE AIR HEAT
Sensible 300.00 CFM x 34.00 F(TD) x CF x 1.08 8,812.80 3.00
Latent 300.00 CFM x 37.00 Gr/Lb x CF x 0.68 6,038.40 4.00
OUTSIDE AIR TOTAL HEAT 14,851.20 Notes:
GRAND SUB-TOTAL HEAT 40,079.92
Factor 1 - 3% 1,202.40
GRAND TOTAL HEAT 41,282.32
TONS=GRAND TOTAL HEAT/12000 3.44
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 28
CLIENT XYZ AREA ( SqFt) (WxH) 265.96
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,393.64
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N 12.00 SqFt x 14.00 x 0.65 109.20
Glass - NE SqFt x x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 6.00 = 180.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt0.33 Sqft x 265.96 = 87.77
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,393.64
Cu.ftx 3.00 x1/60 = 119.68
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 159.96 SqFt x 26.00 F x 0.43 1,788.35 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 150.96 SqFt x 29.00 F x 0.30 1,313.35 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 630.28 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 180.00 CFM x 34.00 x BFX1.08 1,321.92
Internal Heat = 296.23 L/s
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 265.96 SqFt x 1.50 W/SqFt x 3.415 1,362.38 Grand Total Heat = 2.06 TR
Equipments 265.96 2.00 Watts x 3.415 1,816.51
Power kW/Hp x 0.00
Sub Total 10,891.23
Factor 5-10% 1,089.12
Effective Room Sensible Heat 11,980.35 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.06 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 180.00 CFM x 37.00 Gr/Lb x BFx0.68 905.76
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 2,991.20
Factor 2.5 - 5% 74.78
Effective Room Latent Heat 3,065.98 2.00
EFFECTIVE ROOM TOTAL HEAT 15,046.33
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 34.00 F(TD) x CF x 1.08 5,287.68 3.00
Latent 180.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,623.04 4.00
OUTSIDE AIR TOTAL HEAT 8,910.72 Notes:
GRAND SUB-TOTAL HEAT 23,957.05
Factor 1 - 3% 718.71
GRAND TOTAL HEAT 24,675.77
TONS=GRAND TOTAL HEAT/12000 2.06
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR S
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 29
CLIENT XYZ AREA ( SqFt) (WxH) 280.07
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,520.63
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N 12.00 SqFt x 14.00 x 0.65 109.20
Glass - NE SqFt x x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 6.00 = 180.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt0.33 Sqft x 280.07 = 92.42
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,520.63
Cu.ftx 3.00 x1/60 = 126.03
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 169.08 SqFt x 26.00 F x 0.43 1,890.31 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 160.08 SqFt x 29.00 F x 0.30 1,392.70 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 650.53 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 180.00 CFM x 34.00 x BFX1.08 1,321.92
Internal Heat = 305.75 L/s
People 6.00 Nos. x 245.00 Btu/Hour Per Person 1,470.00 TOTAL HEAT CAPACITY
Lighting 280.07 SqFt x 1.50 W/SqFt x 3.415 1,434.66 Grand Total Heat = 2.09 TR
Equipments 280.07 2.00 Watts x 3.415 1,912.88
Power kW/Hp x 0.00
Sub Total 11,241.19
Factor 5-10% 1,124.12
Effective Room Sensible Heat 12,365.31 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.09 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 180.00 CFM x 37.00 Gr/Lb x BFx0.68 905.76
People 6.00 Nos. x 205.00 Btu/Hour Per Person 1,230.00
Sub Total 2,991.20
Factor 2.5 - 5% 74.78
Effective Room Latent Heat 3,065.98 2.00
EFFECTIVE ROOM TOTAL HEAT 15,431.29
OUTSIDE AIR HEAT
Sensible 180.00 CFM x 34.00 F(TD) x CF x 1.08 5,287.68 3.00
Latent 180.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,623.04 4.00
OUTSIDE AIR TOTAL HEAT 8,910.72 Notes:
GRAND SUB-TOTAL HEAT 24,342.01
Factor 1 - 3% 730.26
GRAND TOTAL HEAT 25,072.27
TONS=GRAND TOTAL HEAT/12000 2.09
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 10
CLIENT XYZ AREA ( SqFt) (WxH) 472.83
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 4,255.47
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N 12.00 SqFt x 14.00 x 0.65 109.20
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 10.00 = 300.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt 0.33 Sqft x 472.83 = 156.03
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft
4,255.47 x 3.00 x1/60 = 212.77
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 210.60 SqFt x 26.00 F x 0.43 2,354.51 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 293.88 SqFt x 40.00 F x 0.43 5,054.74 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 0.00 SqFt x 29.00 F x 0.30 0.00 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 1,256.57 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 300.00 CFM x 34.00 x BFX1.08 2,203.20
Internal Heat = 590.59 L/s
People 10.00 Nos. x 245.00 Btu/Hour Per Person 2,450.00 TOTAL HEAT CAPACITY
Lighting 472.83 SqFt x 1.50 W/SqFt x 3.415 2,422.07 Grand Total Heat = 5.36 TR
Equipments 472.83 2.00 Watts x 3.415 3,229.43
Power kW/Hp x 0.00
Sub Total 21,713.54
Factor 5-10% 2,171.35
Effective Room Sensible Heat 23,884.90 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 5.36 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 300.00 CFM x 37.00 Gr/Lb x BFx0.68 1,509.60
People 100.00 Nos. x 205.00 Btu/Hour Per Person 20,500.00
Sub Total 23,166.96
Factor 2.5 - 5% 579.17
Effective Room Latent Heat 23,746.13 2.00
EFFECTIVE ROOM TOTAL HEAT 47,631.03
OUTSIDE AIR HEAT
Sensible 300.00 CFM x 34.00 F(TD) x CF x 1.08 8,812.80 3.00
Latent 300.00 CFM x 37.00 Gr/Lb x CF x 0.68 6,038.40 4.00
OUTSIDE AIR TOTAL HEAT 14,851.20 Notes:
GRAND SUB-TOTAL HEAT 62,482.23
Factor 1 - 3% 1,874.47
GRAND TOTAL HEAT 64,356.70
TONS=GRAND TOTAL HEAT/12000 5.36
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 31
CLIENT XYZ AREA ( SqFt) (WxH) 229.27
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,063.43
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 5.00 = 150.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt0.33 Sqft x 229.27 = 75.66
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,063.43
Cu.ftx 3.00 x1/60 = 103.17
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 136.32 SqFt x 40.00 F x 0.43 2,344.70 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 127.32 SqFt x 29.00 F x 0.30 1,107.68 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 671.55 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 150.00 CFM x 34.00 x BFX1.08 1,101.60
Internal Heat = 315.63 L/s
People 5.00 Nos. x 245.00 Btu/Hour Per Person 1,225.00 TOTAL HEAT CAPACITY
Lighting 229.27 SqFt x 1.50 W/SqFt x 3.415 1,174.44 Grand Total Heat = 1.96 TR
Equipments 243.38 2.00 Watts x 3.415 1,662.29
Power kW/Hp x 0.00
Sub Total 11,604.43
Factor 5-10% 1,160.44
Effective Room Sensible Heat 12,764.87 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.96 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 150.00 CFM x 37.00 Gr/Lb x BFx0.68 754.80
People 5.00 Nos. x 205.00 Btu/Hour Per Person 1,025.00
Sub Total 2,635.24
Factor 2.5 - 5% 65.88
Effective Room Latent Heat 2,701.12 2.00
EFFECTIVE ROOM TOTAL HEAT 15,465.99
OUTSIDE AIR HEAT
Sensible 150.00 CFM x 34.00 F(TD) x CF x 1.08 4,406.40 3.00
Latent 150.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,019.20 4.00
OUTSIDE AIR TOTAL HEAT 7,425.60 Notes:
GRAND SUB-TOTAL HEAT 22,891.59
Factor 1 - 3% 686.75
GRAND TOTAL HEAT 23,578.34
TONS=GRAND TOTAL HEAT/12000 1.96
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 32
CLIENT XYZ AREA ( SqFt) (WxH) 506.05
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 4,554.45
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 10.00 = 300.00
Glass - W 24.00 SqFt x 164.00 x 0.65 2,558.40 CFM Per SqFt0.33 Sqft x 506.05 = 167.00
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 4,554.45
Cu.ftx 3.00 x1/60 = 227.72
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 514.68 SqFt x 40.00 F x 0.43 8,852.50 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 782.40 SqFt x 29.00 F x 0.30 6,806.88 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 1,824.70 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 300.00 CFM x 34.00 x BFX1.08 2,203.20
Internal Heat = 857.61 L/s
People 10.00 Nos. x 245.00 Btu/Hour Per Person 2,450.00 TOTAL HEAT CAPACITY
Lighting 506.05 SqFt x 1.50 W/SqFt x 3.415 2,592.24 Grand Total Heat = 4.67 TR
Equipments 506.05 2.00 Watts x 3.415 3,456.32
Power kW/Hp x 0.00
Sub Total 31,530.74
Factor 5-10% 3,153.07
Effective Room Sensible Heat 34,683.81 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 4.67 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 300.00 CFM x 37.00 Gr/Lb x BFx0.68 1,509.60
People 10.00 Nos. x 205.00 Btu/Hour Per Person 2,050.00
Sub Total 4,716.96
Factor 2.5 - 5% 117.92
Effective Room Latent Heat 4,834.88 2.00
EFFECTIVE ROOM TOTAL HEAT 39,518.70
OUTSIDE AIR HEAT
Sensible 300.00 CFM x 34.00 F(TD) x CF x 1.08 8,812.80 3.00
Latent 300.00 CFM x 37.00 Gr/Lb x CF x 0.68 6,038.40 4.00
OUTSIDE AIR TOTAL HEAT 14,851.20 Notes:
GRAND SUB-TOTAL HEAT 54,369.90
Factor 1 - 3% 1,631.10
GRAND TOTAL HEAT 56,000.99
TONS=GRAND TOTAL HEAT/12000 4.67
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 33
CLIENT XYZ AREA ( SqFt) (WxH) 236.32
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,126.88
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 5.00 = 150.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt0.33 Sqft x 236.32 = 77.99
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,126.88
Cu.ftx 3.00 x1/60 = 106.34
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 140.88 SqFt x 40.00 F x 0.43 2,423.14 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 354.48 SqFt x 29.00 F x 0.30 3,083.98 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 789.76 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 150.00 CFM x 34.00 x BFX1.08 1,101.60
Internal Heat = 371.19 L/s
People 5.00 Nos. x 245.00 Btu/Hour Per Person 1,225.00 TOTAL HEAT CAPACITY
Lighting 236.32 SqFt x 1.50 W/SqFt x 3.415 1,210.55 Grand Total Heat = 2.16 TR
Equipments 236.32 2.00 Watts x 3.415 1,614.07
Power ss x 0.00
Sub Total 13,647.05
Factor 5-10% 1,364.70
Effective Room Sensible Heat 15,011.75 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 2.16 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 150.00 CFM x 37.00 Gr/Lb x BFx0.68 754.80
People 5.00 Nos. x 205.00 Btu/Hour Per Person 1,025.00
Sub Total 2,635.24
Factor 2.5 - 5% 65.88
Effective Room Latent Heat 2,701.12 2.00
EFFECTIVE ROOM TOTAL HEAT 17,712.87
OUTSIDE AIR HEAT
Sensible 150.00 CFM x 34.00 F(TD) x CF x 1.08 4,406.40 3.00
Latent 150.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,019.20 4.00
OUTSIDE AIR TOTAL HEAT 7,425.60 Notes:
GRAND SUB-TOTAL HEAT 25,138.47
Factor 1 - 3% 754.15
GRAND TOTAL HEAT 25,892.63
TONS=GRAND TOTAL HEAT/12000 2.16
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 34
CLIENT XYZ AREA ( SqFt) (WxH) 244.19
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,197.67
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 5.00 = 150.00
Glass - W SqFt x 164.00 x 0.65 0.00 CFM Per SqFt0.33 Sqft x 244.19 = 80.58
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,197.67
Cu.ftx 3.00 x1/60 = 109.88
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 164.50 SqFt x 40.00 F x 0.43 2,829.40 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x 40.00 F x 0.43 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 155.52 SqFt x 29.00 F x 0.30 1,353.02 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 649.93 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 150.00 CFM x 34.00 x BFX1.08 1,101.60
Internal Heat = 305.47 L/s
People 5.00 Nos. x 245.00 Btu/Hour Per Person 1,225.00 TOTAL HEAT CAPACITY
Lighting 244.19 SqFt x 1.50 W/SqFt x 3.415 1,250.84 Grand Total Heat = 1.93 TR
Equipments 244.19 2.00 Watts x 3.415 1,667.82
Power ss x 0.00
Sub Total 11,230.80
Factor 5-10% 1,123.08
Effective Room Sensible Heat 12,353.88 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.93 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 150.00 CFM x 37.00 Gr/Lb x BFx0.68 754.80
People 5.00 Nos. x 205.00 Btu/Hour Per Person 1,025.00
Sub Total 2,635.24
Factor 2.5 - 5% 65.88
Effective Room Latent Heat 2,701.12 2.00
EFFECTIVE ROOM TOTAL HEAT 15,055.01
OUTSIDE AIR HEAT
Sensible 150.00 CFM x 34.00 F(TD) x CF x 1.08 4,406.40 3.00
Latent 150.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,019.20 4.00
OUTSIDE AIR TOTAL HEAT 7,425.60 Notes:
GRAND SUB-TOTAL HEAT 22,480.61
Factor 1 - 3% 674.42
GRAND TOTAL HEAT 23,155.02
TONS=GRAND TOTAL HEAT/12000 1.93
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY
PROJECT Dhanush Engg Services Ltd. FLOOR Frist Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 35
CLIENT XYZ AREA ( SqFt) (WxH) 250.34
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 2,253.06
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design ConditionsDB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Area
Solar Gain - Glass ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x 0.00 x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.20
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.80
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person
30.00 No = 5.00 = 150.00
Glass - W SqFt x 164.00 x 0.65 0.00 CFM Per SqFt0.33 Sqft x 250.34 = 82.61
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM 2,253.06
Cu.ftx 3.00 x1/60 = 112.65
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x 26.00 F x 0.43 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 169.09 SqFt x 40.00 F x 0.43 2,908.35 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x 40.00 F x 0.43 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof SqFt x 46.00 F x 0.28 0.00 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 12.00 SqFt x 34.00 F x 1.13 461.04 Selected ADP (F) = 53.00
Partition 160.08 SqFt x 29.00 F x 0.30 1,392.70 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 17.60
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 661.05 CFM
Infiltration 34.00 CFM x 34.00 T.Diff x 1.08 1,248.48 Dehumidified Rise x 1.08
Outside Air 150.00 CFM x 34.00 x BFX1.08 1,101.60
Internal Heat = 310.69 L/s
People 5.00 Nos. x 245.00 Btu/Hour Per Person 1,225.00 TOTAL HEAT CAPACITY
Lighting 250.34 SqFt x 1.50 W/SqFt x 3.415 1,282.37 Grand Total Heat = 1.95 TR
Equipments 250.34 2.00 Watts x 3.415 1,709.82
Power ss x 0.00
Sub Total 11,422.95
Factor 5-10% 1,142.30
Effective Room Sensible Heat 12,565.25 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 1.95 TR
Infiltration 34.00 CFM x 37.00 Gr/Lb x 0.68 855.44 12,000.00
Outside Air 150.00 CFM x 37.00 Gr/Lb x BFx0.68 754.80
People 5.00 Nos. x 205.00 Btu/Hour Per Person 1,025.00
Sub Total 2,635.24
Factor 2.5 - 5% 65.88
Effective Room Latent Heat 2,701.12 2.00
EFFECTIVE ROOM TOTAL HEAT 15,266.37
OUTSIDE AIR HEAT
Sensible 150.00 CFM x 34.00 F(TD) x CF x 1.08 4,406.40 3.00
Latent 150.00 CFM x 37.00 Gr/Lb x CF x 0.68 3,019.20 4.00
OUTSIDE AIR TOTAL HEAT 7,425.60 Notes:
GRAND SUB-TOTAL HEAT 22,691.97
Factor 1 - 3% 680.76
GRAND TOTAL HEAT 23,372.73
TONS=GRAND TOTAL HEAT/12000 1.95
Second Floor

INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT Dhanush Engg Services Ltd. FLOOR Second Floor


LOCATION Lakhnow (UP) SPACE REFERENCE SF OFFICE -1
CLIENT XYZ AREA ( SqFt) (WxH) 1,980.98
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 17,828.80
Area or Sun Gain or Estimate for Summer
Item Factor (U) Btu/Hour Watts
Quantity Temp. Diff. Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 40.00 = 1,200.00
Glass - W 12.00 SqFt x 164.00 x 0.65 1,279.20 CFM Per SqFt 0.33 Sqft x 1,980.98 = 653.72
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 17,828.80 x 3.00 x1/60 = 891.44
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x 24.00 F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 555.48 SqFt x 40.00 F x 0.43 9,554.26 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 490.68 SqFt x 40.00 F x 0.43 8,439.70 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 87.00
Roof 1,980.98 SqFt x 46.00 F x 0.28 25,515.02 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 546.48 SqFt x 29.00 F x 0.30 4,754.38 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 5,029.12 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 1,200.00 CFM x 34.00 x BFX1.08 6,609.60
Internal Heat = 2,363.69 L/s
People 40.00 Nos. x 245.00 Btu/Hour Per Person 9,800.00 TOTAL HEAT CAPACITY
Lighting 1,980.98 SqFt x 1.50 W/SqFt x 3.415 10,147.56 Grand Total Heat = 15.36 TR
Equipments 1,980.98 2.00 Watts x 3.415 13,530.08
Power kW/Hp x 0.00
Sub Total 92,334.59
Factor 5-10% 9,233.46
Effective Room Sensible Heat 1,01,568.05 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 15.36 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 1,200.00 CFM x 37.00 Gr/Lb x BFx0.68 4,528.80
People 40.00 Nos. x 205.00 Btu/Hour Per Person 8,200.00
Sub Total 13,886.16
Factor 2.5 - 5% 347.15
Effective Room Latent Heat 14,233.31 2.00
EFFECTIVE ROOM TOTAL HEAT 1,15,801.36
OUTSIDE AIR HEAT
Sensible 1,200.00 CFM x 34.00 F(TD) x CF x 1.08 37,454.40 3.00
Latent 1,200.00 CFM x 37.00 Gr/Lb x CF x 0.68 25,663.20 4.00
OUTSIDE AIR TOTAL HEAT 63,117.60 Notes:
GRAND SUB-TOTAL HEAT 1,78,918.96
Factor 1 - 3% 5,367.57
GRAND TOTAL HEAT 1,84,286.53
TONS=GRAND TOTAL HEAT/12000 15.36
INPUT VALUES ARE TO BE GIVEN IN BLUE COLOR BOXES ONLY

PROJECT Dhanush Engg Services Ltd. FLOOR Second Floor


LOCATION Lakhnow (UP) SPACE REFERENCE SF OFFICE -2
CLIENT XYZ AREA ( SqFt) (WxH) 2,002.53
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 18,022.77
Area or Sun Gain or Factor W Estimate for Summer
Item Btu/Hour aDesign Conditions
Quantity Temp. Diff. (U) DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S 12.00 SqFt x 12.00 x 0.65 93.60 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 40.00 = 1,200.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 2,002.53 = 660.83
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 18,022.77 x 3.00 x1/60 = 901.14
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 555.96 SqFt x 24.00 F x 0.43 5,737.51 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S 495.72 SqFt x 40.00 F x 0.43 8,526.38 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof 2,002.53 SqFt x 46.00 F x 0.28 25,792.59 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 486.72 SqFt x 29.00 F x 0.30 4,234.46 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 4,762.21 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 1,200.00 CFM x 34.00 x BFX1.08 6,609.60
Internal Heat = 2,238.24 L/s
People 40.00 Nos. x 245.00 Btu/Hour Per Person 9,800.00 TOTAL HEAT CAPACITY
Lighting 2,002.53 SqFt x 1.50 W/SqFt x 3.415 10,257.96 Grand Total Heat = 14.89 TR
Equipments 2,002.53 2.00 Watts x 3.415 13,677.28
Power kW/Hp x 0.00
Sub Total 87,434.18
Factor 5-10% 8,743.42
Effective Room Sensible Heat 96,177.60 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 14.89 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 1,200.00 CFM x 37.00 Gr/Lb x BFx0.68 4,528.80
People 40.00 Nos. x 205.00 Btu/Hour Per Person 8,200.00
Sub Total 13,886.16
Factor 2.5 - 5% 347.15
Effective Room Latent Heat 14,233.31
EFFECTIVE ROOM TOTAL HEAT 1,10,410.91
OUTSIDE AIR HEAT
Sensible 1,200.00 CFM x 34.00 F(TD) x CF x 1.08 37,454.40
Latent 1,200.00 CFM x 37.00 Gr/Lb x CF x 0.68 25,663.20
OUTSIDE AIR TOTAL HEAT 63,117.60 Notes:
GRAND SUB-TOTAL HEAT 1,73,528.51
Factor 1 - 3% 5,205.86
GRAND TOTAL HEAT 1,78,734.37
TONS=GRAND TOTAL HEAT/12000 14.89
PROJECT Dhanush Engg Services Ltd. FLOOR Second Floor
LOCATION Lucknow (UP) SPACE REFERENCE shop no 3
CLIENT XYZ AREA ( SqFt) (WxH) 1,077.43
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 9,696.87
Area or Sun Gain or Factor W Estimate for Summer
Item Btu/Hour aDesign Conditions
Quantity Temp. Diff. (U) DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E 24.00 SqFt x 12.00 x 0.65 187.20 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 22.00 = 660.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 1,077.43 = 355.55
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 9,696.87 x 3.00 x1/60 = 484.84
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 714.36 SqFt x 24.00 F x 0.43 7,372.20 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x F x 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof 1,077.43 SqFt x 46.00 F x 0.28 13,877.30 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 240.00 SqFt x 34.00 F x 1.13 9,220.80 Selected ADP (F) = 53.00
Partition 705.36 SqFt x 29.00 F x 0.30 6,136.63 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 3,333.03 CFM
Infiltration 68.00 CFM x 34.00 T.Diff x 1.08 2,496.96 Dehumidified Rise x 1.08
Outside Air 660.00 CFM x 34.00 x BFX1.08 3,635.28
Internal Heat = 1,566.52 L/s
People 22.00 Nos. x 245.00 Btu/Hour Per Person 5,390.00 TOTAL HEAT CAPACITY
Lighting 1,077.43 SqFt x 1.50 W/SqFt x 3.415 5,519.14 Grand Total Heat = 9.52 TR
Equipments 1,077.43 2.00 Watts x 3.415 7,358.85
Power kW/Hp x 0.00
Sub Total 61,194.35
Factor 5-10% 6,119.43
Effective Room Sensible Heat 67,313.78 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 9.52 TR
Infiltration 68.00 CFM x 37.00 Gr/Lb x 0.68 1,710.88 12,000.00
Outside Air 660.00 CFM x 37.00 Gr/Lb x BFx0.68 2,490.84
People 22.00 Nos. x 205.00 Btu/Hour Per Person 4,510.00
Sub Total 8,711.72
Factor 2.5 - 5% 217.79
Effective Room Latent Heat 8,929.51
EFFECTIVE ROOM TOTAL HEAT 76,243.30
OUTSIDE AIR HEAT
Sensible 660.00 CFM x 34.00 F(TD) x CF x 1.08 20,599.92
Latent 660.00 CFM x 37.00 Gr/Lb x CF x 0.68 14,114.76
OUTSIDE AIR TOTAL HEAT 34,714.68 Notes:
GRAND SUB-TOTAL HEAT 1,10,957.98
Factor 1 - 3% 3,328.74
GRAND TOTAL HEAT 1,14,286.71
TONS=GRAND TOTAL HEAT/12000 9.52
PROJECT Dhanush Engg Services Ltd. FLOOR Second Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 4
CLIENT XYZ AREA ( SqFt) (WxH) 1,933.69
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 17,403.21
Area or Sun Gain or Factor W Estimate for Summer
Item Btu/Hour aDesign Conditions
Quantity Temp. Diff. (U) DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N 12.00 SqFt x 14.00 x 0.65 109.20
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 39.00 = 1,170.00
Glass - W SqFt x 164.00 x 0.00 CFM Per SqFt 0.33 Sqft x 1,933.69 = 638.12
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 17,403.21 x 3.00 x1/60 = 870.16
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 490.80 SqFt x 26.00 F x 0.43 5,487.14 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E 541.18 SqFt x 24.00 F x 0.43 5,584.98 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W SqFt x 40.00 F x 0.43 0.00 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof 1,933.69 SqFt x 46.00 F x 0.28 24,905.93 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 267.58 SqFt x 29.00 F x 0.30 2,327.95 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 4,369.92 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 1,170.00 CFM x 34.00 x BFX1.08 6,444.36
Internal Heat = 2,053.86 L/s
People 39.00 Nos. x 245.00 Btu/Hour Per Person 9,555.00 TOTAL HEAT CAPACITY
Lighting 1,933.69 SqFt x 1.50 W/SqFt x 3.415 9,905.33 Grand Total Heat = 14.05 TR
Equipments 1,933.69 2.00 Watts x 3.415 13,207.10
Power kW/Hp x 0.00
Sub Total 80,231.78
Factor 5-10% 8,023.18
Effective Room Sensible Heat 88,254.96 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 14.05 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 1,170.00 CFM x 37.00 Gr/Lb x BFx0.68 4,415.58
People 39.00 Nos. x 205.00 Btu/Hour Per Person 7,995.00
Sub Total 13,567.94
Factor 2.5 - 5% 339.20
Effective Room Latent Heat 13,907.14
EFFECTIVE ROOM TOTAL HEAT 1,02,162.10
OUTSIDE AIR HEAT
Sensible 1,170.00 CFM x 34.00 F(TD) x CF x 1.08 36,518.04
Latent 1,170.00 CFM x 37.00 Gr/Lb x CF x 0.68 25,021.62
OUTSIDE AIR TOTAL HEAT 61,539.66 Notes:
GRAND SUB-TOTAL HEAT 1,63,701.76
Factor 1 - 3% 4,911.05
GRAND TOTAL HEAT 1,68,612.81
TONS=GRAND TOTAL HEAT/12000 14.05
PROJECT Dhanush Engg Services Ltd. FLOOR Second Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 5
CLIENT XYZ AREA ( SqFt) (WxH) 1,933.69
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 17,403.21
Area or Sun Gain or Factor W Estimate for Summer
Item Btu/Hour aDesign Conditions
Quantity Temp. Diff. (U) DB (°F) WB (°F) RH (%) SH (Gr/Lb)
t
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.65 0.00
Glass - NE SqFt x x 0.00
Glass - E 12.00 SqFt x 12.00 x 0.65 93.60 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 39.00 = 1,170.00
Glass - W 12.00 SqFt x 164.00 x 0.65 0.00 CFM Per SqFt 0.33 Sqft x 1,933.69 = 638.12
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 17,403.21 x 3.00 x1/60 = 870.16
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N 541.18 SqFt x 26.00 F x 0.43 6,050.39 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x 24.00 F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 490.80 SqFt x 40.00 F x 0.43 8,441.76 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.87
Roof 1,933.69 SqFt x 46.00 F x 0.28 24,905.93 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 490.80 SqFt x 29.00 F x 0.30 4,269.96 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 4,656.03 CFM
Infiltration 46.00 CFM x 34.00 T.Diff x 1.08 1,689.12 Dehumidified Rise x 1.08
Outside Air 1,170.00 CFM x 34.00 x BFX1.08 6,444.36
Internal Heat = 2,188.33 L/s
People 39.00 Nos. x 245.00 Btu/Hour Per Person 9,555.00 TOTAL HEAT CAPACITY
Lighting 1,933.69 SqFt x 1.50 W/SqFt x 3.415 9,905.33 Grand Total Heat = 14.55 TR
Equipments 1,933.69 2.00 Watts x 3.415 13,207.10
Power kW/Hp x 0.00
Sub Total 85,484.63
Factor 5-10% 8,548.46
Effective Room Sensible Heat 94,033.09 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 14.55 TR
Infiltration 46.00 CFM x 37.00 Gr/Lb x 0.68 1,157.36 12,000.00
Outside Air 1,170.00 CFM x 37.00 Gr/Lb x BFx0.68 4,415.58
People 39.00 Nos. x 205.00 Btu/Hour Per Person 7,995.00
Sub Total 13,567.94
Factor 2.5 - 5% 339.20
Effective Room Latent Heat 13,907.14
EFFECTIVE ROOM TOTAL HEAT 1,07,940.23
OUTSIDE AIR HEAT
Sensible 1,170.00 CFM x 34.00 F(TD) x CF x 1.08 36,518.04
Latent 1,170.00 CFM x 37.00 Gr/Lb x CF x 0.68 25,021.62
OUTSIDE AIR TOTAL HEAT 61,539.66 Notes:
GRAND SUB-TOTAL HEAT 1,69,479.89
Factor 1 - 3% 5,084.40
GRAND TOTAL HEAT 1,74,564.29
TONS=GRAND TOTAL HEAT/12000 14.55
PROJECT Dhanush Engg Services Ltd. FLOOR Second Floor
LOCATION Lakhnow (UP) SPACE REFERENCE shop no 6
CLIENT XYZ AREA ( SqFt) (WxH) 869.81
CONSULTANT ABC Falce Ceiling Height (Ft) 9.00
126.00 Volume (CuFt) 7,828.33
Area or Sun Gain or Factor Estimate for Summer
Item Btu/Hour Watts
Quantity Temp. Diff. (U) Design Conditions DB (°F) WB (°F) RH (%) SH (Gr/Lb)
ROOM HEAT Q= U*A*ΔT Ambient(Out Side) 109.00 79.00 26.00 102.00
ROOM SENSIBLE HEAT Room (InDoor) 75.00 62.00 50.00 65.00
Solar Gain - Glass Area ΔT U Difference Δ 34.00 17.00 24.00 37.00
Glass - N SqFt x 14.00 x 0.00
Glass - NE SqFt x x 0.00
Glass - E SqFt x 12.00 x 0.65 0.00 By Pass Factor (BF) = 0.15
Glass - SE SqFt x x 0.00 Contact Factor (CF = 1 - BF) = 0.85
Glass - S SqFt x 12.00 x 0.65 0.00 CFM Ventilation
Glass - SW SqFt x x 0.00 CFM Per Person 30.00 No = 18.00 = 540.00
Glass - W 24.00 SqFt x 164.00 x 0.65 0.00 CFM Per SqFt 0.33 Sqft x 869.81 = 287.04
Glass - NW SqFt x x 0.00 Air Change Per Hour (CFM) = 3.00
Skylight SqFt x x 0.00 CFM Cu.ft 7,828.33 x 3.00 x1/60 = 391.42
Solar & Transmission Gain - Walls & Roof CFM Infiltration
Wall - N SqFt x F x 0.00 Swinging x cfm/door = 0.00
Wall - NE SqFt x F x 0.00 Revolving Doors (People) x cfm/door = 0.00
Wall - E SqFt x 24.00 F x 0.43 0.00 Open Doors x 1.00 cfm/door = 0.00
Wall - SE SqFt x F x 0.00 Crack (feet) x cfm/ft = 0.00
Wall - S SqFt x F x 0.43 0.00 0.00
Wall - SW SqFt x F x 0.00 Supply CFM from Machine
Wall - W 503.16 SqFt x 40.00 F x 0.43 8,654.35 Effective Room Sensible Heat Factor =
Wall - NW SqFt x F x 0.00 Effective Room Sensible Heat/Eff Room Total Heat = 0.81
Roof 869.81 SqFt x 46.00 F x 0.28 11,203.15 Apparatus Dew Point (ADP)
Transmission Gain - Except Walls & Roof Indicated ADP (F) =
All Glass 24.00 SqFt x 34.00 F x 1.13 922.08 Selected ADP (F) = 53.00
Partition 960.36 SqFt x 29.00 F x 0.30 8,355.13 Dehumidified Rise
Ceiling SqFt x F x 0.00 (Room DB - ADP) x CF = 18.70
Floor SqFt x 29.00 F x 0.57 0.00 DEHUMIDIFIED AIR QUANTITY
INFILTRATION AND BY PASSED AIR Effective Room Sensible Heat = 2,691.31 CFM
Infiltration 68.00 CFM x 34.00 T.Diff x 1.08 2,496.96 Dehumidified Rise x 1.08
Outside Air 540.00 CFM x 34.00 x BFX1.08 2,974.32
Internal Heat = 1,264.92 L/s
People 18.00 Nos. x 245.00 Btu/Hour Per Person 4,410.00 TOTAL HEAT CAPACITY
Lighting 869.81 SqFt x 1.50 W/SqFt x 3.415 4,455.62 Grand Total Heat = 7.76 TR
Equipments 869.81 2.00 Watts x 3.415 5,940.83
Power kW/Hp x 0.00
Sub Total 49,412.45
Factor 5-10% 4,941.24
Effective Room Sensible Heat 54,353.69 1.00 SENSIBLE HEAT CAPACITY
ROOM LATENT HEAT Grand Sensible Heat = 7.76 TR
Infiltration 68.00 CFM x 37.00 Gr/Lb x 0.68 1,710.88 12,000.00
Outside Air 540.00 CFM x 37.00 Gr/Lb x BFx0.68 2,037.96
People 18.00 Nos. x 205.00 Btu/Hour Per Person 3,690.00
Sub Total 7,438.84
Factor 2.5 - 5% 185.97
Effective Room Latent Heat 7,624.81 2.00
EFFECTIVE ROOM TOTAL HEAT 61,978.50
OUTSIDE AIR HEAT
Sensible 540.00 CFM x 34.00 F(TD) x CF x 1.08 16,854.48 3.00
Latent 540.00 CFM x 37.00 Gr/Lb x CF x 0.68 11,548.44 4.00
OUTSIDE AIR TOTAL HEAT 28,402.92 Notes:
GRAND SUB-TOTAL HEAT 90,381.42
Factor 1 - 3% 2,711.44
GRAND TOTAL HEAT 93,092.87
TONS=GRAND TOTAL HEAT/12000 7.76
Room Dimentions
Summery sheets No.Of Light Load Equipments Diffuser VENTILATION
Sr. No Floor No Room Name AC Non AC ERSH ERLH ESHF ADP TR CFM SAD Qty RAD Qty CFM EACH D L/S EACH D(L/S)
Width(Ft) Length(Ft) Height(Ft) Area(SqfT) People (Watt) (Watts) Size AIR
1 Ground Floor Shop no 1 10.4 18.55 9 192.92 Yes 4 14995.71 2181.53 0.87 53 2.02 742.51 12"x12" 2 2 371.255 348.98 120 174.48985 child water system
2 Ground Floor Shop no 2 12.79 18.55 9 237.2545 Yes 5 12828.07 2181.53 0.85 53 1.83 635.18 12"x12" 2 2 317.59 299.613 120 149.8066038 child water system
3 Ground Floor Shop no 3 12.36 18.55 9 229.278 Yes 5 12876.39 2181.53 0.86 53 1.83 637.57 12"x12" 2 2 318.785 300.741 120 150.370283 child water system
4 Ground Floor Shop no 4 16.3 10.35 9 168.705 Yes 4 13416.17 2181.53 0.86 53 1.88 664.3 12"x12" 2 2 332.15 313.349 120 156.6745283 child water system
5 Ground Floor Shop no 5 12.74 18.93 9 241.1682 Yes 5 14800.83 2507.7 0.86 53 2.16 732.86 12"x12" 2 2 366.43 345.689 150 172.8443396 child water system
6 Ground Floor Shop no 6 12.36 18.93 9 233.9748 Yes 5 12666.45 2181.53 0.85 53 1.82 627.18 12"x12" 2 2 313.59 295.84 120 147.9198113 child water system
7 Ground Floor Shop no 7 12.36 18.93 9 233.9748 Yes 5 15210.32 2181.53 0.87 53 2.03 753.14 12"x12" 2 2 376.57 355.255 120 177.6273585 child water system
8 Ground Floor Shop no 8 18.56 14.33 9 265.9648 Yes 5 15550.07 2181.53 0.88 53 2.06 769.96 12"x12" 2 2 384.98 363.189 120 181.5943396 child water system
9 Ground Floor Shop no 9 18.56 15.09 9 280.0704 Yes 6 16191.76 1971.4 0.89 53 2.10 801.73 12"x12" 2 2 400.865 378.175 120 189.0872642 child water system
10 Ground Floor Shop no 10 12 18.55 9 222.6 Yes 5 17504.48 2181.53 0.89 53 2.23 866.73 12"x12" 2 2 433.365 408.835 120 204.4174528 child water system
11 Ground Floor Shop no 11 13.12 18.55 9 243.376 Yes 5 15.469.63 2181.53 0.88 53 2.06 765.97 12"x12" 2 2 382.985 361.307 120 180.6533019 child water system
12 Ground Floor Shop no 12 12.36 18.55 9 229.278 Yes 5 18203.76 2181.53 0.89 53 2.29 901.35 12"x12" 2 2 450.675 425.165 120 212.5825472 child water system
13 Ground Floor Shop no 13 12.74 18.55 9 236.327 Yes 5 18554.55 2181.53 0.89 53 2.32 918.72 12"x12" 2 2 459.36 433.358 120 216.6792453 child water system
14 Ground Floor Shop no 14 16.6 14.71 9 244.186 Yes 5 16686.32 2181.53 0.88 53 2.16 826.22 12"x12" 2 2 413.11 389.726 120 194.8632075 child water system
15 Ground Floor Shop no 15 15.09 16.59 9 250.3431 Yes 5 16362.98 2181.53 0.88 53 2.13 810.21 12"x12" 2 2 405.105 382.175 120 191.0872642 child water system
30.92 11453.63 30 30 5402.66 60 T
1 First Floor Shop no 20&21 23.57 18.55 9 437.2235 yes 9 20630.19 4121.87 0.87 53 3.35 1114.03 15"X15" 2 2 557.015 523.594 270 261.79705 child water system
2 First Floor Shop no 22 12.36 18.55 229.278 yes 5 10020.2 2507.7 0.87 53 1.76 543.09 15"X15" 1 1 543.09 255.252 150 255.2523 child water system
3 First Floor Shop no 23 16.37 10.35 169.4295 yes 4 9788.83 2181.53 0.87 53 1.57 527.74 12"x12" 1 1 527.74 248.038 120 248.0378 child water system
4 First Floor Shop no 24 14.33 10.35 148.3155 yes 3 8547.8 1855.35 0.87 53 1.3 459.26 12"x12" 1 1 459.26 215.852 90 215.8522 child water system
5 First Floor Shop no 25 14.69 10.35 152.0415 yes 3 9052.11 2181.53 0.87 53 1.51 448.21 12"x12" 1 1 448.21 210.659 120 210.6587 child water system
6 First Floor Shop no 26 14.32 10.35 148.212 yes 3 9188.22 1855.35 0.87 53 1.35 492.95 12"x12" 1 1 492.95 231.687 150 231.6865 child water system
First Floor Shop no 26 A 12.74 18.93 241.1682 yes 5 10268 2507.7 0.87 53 1.7 556.13 15"X15" 1 1 556.13 261.381 300 261.3811 child water system
7 First Floor Shop no 27 25.11 18.93 475.3323 yes 10 19787.96 4448.05 0.87 53 3.44 1072.91 15"X15" 2 2 536.455 504.268 180 252.13385 child water system
8 First Floor Shop no 28 18.56 14.33 265.9648 yes 6 11616.83 2833.88 0.87 53 2.06 630.28 12"X12" 2 2 315.14 296.232 180 148.1158 child water system
9 First Floor Shop no 29 18.56 15.09 280.0704 yes 6 12001.78 2833.88 0.87 53 2.09 650.53 12"X12" 2 2 325.265 305.749 300 152.87455 child water system
10 First Floor Shop no 30 25.49 18.55 472.8395 yes 10 23279.02 23359.3 0.87 53 5.36 1256.57 12"X12" 3 3 418.85667 590.588 150 196.8626333 child water system
11 First Floor Shop no 31 12.36 18.55 229.278 yes 5 12461.93 2507.7 0.87 53 1.96 671.55 12"X12" 2 2 335.775 315.629 300 157.81425 child water system
12 First Floor Shop no 32 43.89 11.53 506.0517 yes 10 34077.93 4448.05 0.87 53 4.67 1824.7 12"X12" 4 4 456.175 857.609 150 214.40225 child water system
13 First Floor Shop no 33 12.74 18.55 236.327 yes 5 14708.81 2507.7 0.87 53 2.16 789.76 12"X12" 2 2 394.88 371.187 150 185.5936 child water system
14 First Floor Shop no 34 16.6 14.71 244.186 yes 5 12050.94 2507.7 0.87 53 1.93 649.93 12"X12" 2 2 324.965 305.467 150 152.73355 child water system
15 First Floor Shop no 35 15.09 16.59 250.3431 yes 5 12262.31 2507.7 0.87 53 1.96 661.05 12"X12" 2 2 330.525 310.694 150 155.34675 child water system
38.17 12348.69 29 29 5824.85 58
1 Second Floor Office no 1 47.29 41.89 9 1980.9781 yes 40 101568.1 14233.31 0.87 53 15.36 5029.12 24"x24" 5 5 1005.824 2372.23 1200 474.445283 child water system
2 Second Floor Office no 2 47.33 42.31 9 2002.5323 yes 40 96177.6 14233.31 0.87 53 14.89 4762.21 24"x24" 5 5 952.442 2246.33 1200 449.2650943 child water system
3 Second Floor Office no 3 60.53 17.8 9 1077.434 yes 22 67313.78 8929.51 0.87 53 9.52 3333.03 24"x24" 4 4 833.2575 1572.18 660 393.0459906 child water system
4 Second Floor Office no 4 46.15 41.9 9 1933.685 yes 39 88254.96 13907.14 0.87 53 14.05 4369.92 24"x24" 4 4 1092.48 2061.28 1170 515.3207547 child water system
5 Second Floor Office no 5 46.15 41.9 9 1933.685 yes 39 94033.09 13907.14 0.87 3 14.55 4656.03 24"x24" 4 4 1164.0075 2196.24 1170 549.0601415 child water system
6 Second Floor Office no 6 43.93 19.8 9 869.814 yes 18 54353.69 7624.81 0.87 53 7.76 2691.31 24"x24" 3 3 897.10333 1269.49 540 423.1619497 child water system
76.13 24841.62 25 25 50
SLD and DLD
DUCTING BOQ
Ground Floor

Summary
Total Duct Area(M 2)
Gage 24 = 196.786 M2
Gage 22 = 10.308 M2
Gage 20 = 0.000 M2
Gage 18 = 0.000 M2
Checked = 207.094 M2
Total Insulation Area(M 2)
Area = 242.777 M2
Price = 35.000 Rupees Per M2
Total Price For
Insulation= 8497 Rupees
Total Price For Fabrication And Erection (*Amounts may be varies) Note:-1
Rupees Per M 2
Qty (M2) Amount Rs/- The waste can be Taken as 15%
Gage 24 = 120.000 196.786 23614.316 Note:-2
Gage 22 = 140.000 10.308 1443.178 Sizes of Duct (W or H) Gauge GI.Sheet Thickness
Gage 20 = 180.000 0.000 0.000 0 MM To 750 MM Gage 24 0.63 MM
Gage 18 = 300.000 0.000 0.000 751 MM To 1500 MM Gage 22 0.8 to 0.85 MM
Total Price 25057.495 1501 MM To 2250 MM Gage 20 1.0 MM
Total Weight of GI Sheets (KG) 2251 MM & Above Gage 18 1.2 MM
Gage 24 = 973.205 KG's
Gage 22 = 68.783 KG's Note:-3
Gage 20 = 0.000 KG's GI Sheet Gauge Thickness taken from internet.
Gage 18 = 0.000 KG's The values may changes from manufacturer to manufacturer
1041.988 KG's
Total Tone= 1.042 Tonnes
PROJECT BILL OF MATERIALS FOR DUCTING
Project Name: iiit bulding Prepared By: aquib Fields has to Enter
Project No: 123456 Insulation Thickness = 50.000 MM 0.033
DATE 30-Mar-22 TIME 10.03.15 AM
Total Area Gauge Wise in SQMT Total

TotalNo. of Friction Static


Width Height Length in Perimeter Sheet Total Duct Area Velocity Thermal
Sr.No Duct Type Width-1(MM) Hight-1(MM) Width-2 (MM) Hight-2(MM) 24 Gauge 22 Gauge 20 Gauge 18 Gauge Sheets Value Pressure
(Meters) (Meters) (Meters) (Meters) Gauge .Insulation

MAIN DUCT
1 reducers1 812 559 812 559 0.812 0.559 0.29 1250.000 0.058
2 reducers2 711 508 711 508 0.711 0.508 0.25 0.058
3 reducers3 305 254 305 254 0.305 0.254 0.25 0.058
4 reducers4 406 305 406 305 0.406 0.305 0.29 0.058
5 reducers5 254 254 254 254 0.254 0.254 0.30 0.058
6 reducers6 254 203 254 203 0.254 0.203 0.29 0.058
7 reducers7 457 356 457 356 0.457 0.356 0.25 0.058
8 reducers8 254 254 254 254 0.254 0.254 0.29 0.058
9 reducers9 305 305 305 305 0.305 0.305 0.25 0.058
10 reducers10 305 254 305 254 0.305 0.254 0.29 0.058
11 reducers11 356 305 356 305 0.356 0.305 0.30 0.058
12 reducers12 660 305 660 305 0.660 0.305 0.25 0.058
13 reducers13 254 254 254 254 0.254 0.254 0.25 0.058
14 reducers14 254 203 254 203 0.254 0.203 0.25 0.058
15 reducers15 356 356 356 356 0.356 0.356 0.29 0.058
16 reducers16 254 254 254 254 0.254 0.254 0.25 0.058
17 reducers17 610 305 610 305 0.610 0.305 0.30 0.058
18 reducers18 254 254 254 254 0.254 0.254 0.25 0.058
19 reducers19 559 457 559 457 0.559 0.457 0.30 0.058
20 reducers20 508 406 508 406 0.508 0.406 0.29 0.058
21 reducers21 457 355 457 355 0.457 0.355 0.29 0.058
22 reducers22 355 355 355 355 0.355 0.355 0.30 0.058
23 reducers23 254 305 254 305 0.254 0.305 0.29 0.058
24 reducers24 610 355 610 355 0.610 0.355 0.30 0.058
25 tee 1 431 305 431 305 0.431 0.305 0.19 0.058
26 tee 2 381 254 381 254 0.381 0.254 0.21 0.058
27 tee 3 685 356 685 356 0.685 0.356 0.21 0.058
28 tee 4 330 355 330 355 0.330 0.355 0.25 0.058
29 tee 5 330 254 330 254 0.330 0.254 0.19 0.058
30 tee 6 330 254 330 254 0.330 0.254 0.19 0.058
31 tee 7 432 305 432 305 0.432 0.305 0.25 0.058
32 tee 8 330 254 330 254 0.330 0.254 0.19 0.058
33 tee 9 330 254 330 254 0.330 0.254 0.19 0.058
34 tee 10 431 305 431 305 0.431 0.305 0.30 0.058
35 tee 11 330 203 330 203 0.330 0.203 0.19 0.058
36 tee 12 381 305 381 305 0.381 0.305 0.24 0.058
37 tee 13 381 305 381 305 0.381 0.305 0.24 0.058
38 tee 14 381 203 381 203 0.381 0.203 0.31 0.058
39 tee 15 584 457 584 457 0.584 0.457 0.34 0.058
40 tee 16 330 355 330 355 0.330 0.355 0.25 0.058
41 tee 17 330 355 330 355 0.330 0.355 0.25 0.058
42 tee 18 330 203 330 203 0.330 0.203 0.31 0.058
43 tee 19 431 305 431 305 0.431 0.305 0.34 0.058
44 tee 20 330 254 330 254 0.330 0.254 0.21 0.058
45 tee 21 381 254 381 254 0.381 0.254 0.21 0.058
46 tee 22 381 254 381 254 0.381 0.254 0.21 0.058
47 elbows 1 813 559 813 559 0.813 0.559 1.09 0.058
48 elbows 2 355 559 355 559 0.355 0.559 0.54 0.058
49 elbows 3 305 305 305 305 0.305 0.305 0.58 0.058
50 elbows 4 305 254 305 254 0.305 0.254 0.47 0.058
51 elbows 5 610 357 610 357 0.610 0.357 1.14 0.058
52 elbows 6 254 254 254 254 0.254 0.254 0.78 0.058
53 elbows 7 254 254 254 254 0.254 0.254 0.78 0.058
54 elbows 8 254 254 254 254 0.254 0.254 0.78 0.058
55 elbows 9 254 254 254 254 0.254 0.254 0.78 0.058
56 elbows 10 254 254 254 254 0.254 0.254 0.78 0.058
57 elbows 11 355 305 355 305 0.355 0.305 0.54 0.058
58 elbows 12 457 356 457 357 0.457 0.357 0.54 0.058
59 elbows 13 711 711 711 711 0.711 0.711 1.37 0.058
60 elbows 14 711 711 711 711 0.711 0.711 1.99 0.058
61 elbows 15 711 711 711 711 0.711 0.711 1.99 0.058
62 elbows 16 711 711 711 711 0.711 0.711 1.99 0.058
63 elbows 17 254 254 254 254 0.254 0.254 0.78 0.058
64 elbows 18 660 711 660 711 0.660 0.711 1.27 0.058
65 elbows 19 610 559 610 559 0.610 0.559 1.07 0.058
66 elbows 20 610 457 610 457 0.610 0.457 0.98 0.058
67 elbows 21 254 303 254 303 0.254 0.303 0.49 0.058
68 elbows 22 254 254 254 254 0.254 0.254 0.48 0.058
69 elbows 23 254 254 254 254 0.254 0.254 0.48 0.058
70 elbows 24 254 203 254 203 0.254 0.203 0.50 0.058
71 elbows 25 356 356 356 356 0.356 0.356 0.36 0.058
72 elbows 26 305 254 305 254 0.305 0.254 0.42 0.058

Project Name: iiit bulding Prepared By: aquib Fields has to Enter
Project No: 123456 Insulation Thickness = 50.000 MM
DATE 30-Mar-22 TIME 10.03.15 AM
Total Area Gauge Wise in SQMT
Width Height Length in Perimeter Sheet TotalNo. of Sheets Total Duct Area Velocity Friction Value Static Pressure
Sr.No Duct Type Width-1(MM) Hight-1(MM) Width-2 (MM) Hight-2(MM) 24 Gauge 22 Gauge 20 Gauge 18 Gauge
(Meters) (Meters) (Meters) (Meters) Gauge

MAIN DUCT
1 Damper 1 813 559 813 559 0.813 0.559 0.00 1250.000 0.058
2 Damper 2 356 305 356 305 0.356 0.305 0.00 0.058
3 Damper 3 610 356 610 356 0.610 0.356 0.00 0.058
4 Damper 4 356 303 356 303 0.356 0.303 0.00 0.058
5 Damper 5 356 303 356 303 0.356 0.303 0.00 0.058
6 Damper 6 711 711 711 711 0.711 0.711 0.00 0.058
7 Damper 7 303 303 303 303 0.303 0.303 0.00 0.058
8 Damper 8 508 457 508 457 0.508 0.457 0.00 0.058
9 Damper 9 457 406 457 406 0.457 0.406 0.00 0.058
10 Damper 10 303 254 303 254 0.303 0.254 0.00 0.058
11 Damper 11 356 457 357 457 0.357 0.457 0.00 0.058
12 Damper 12 457 355 457 355 0.457 0.355 0.00 0.058
13 Damper 13 559 457 559 457 0.559 0.457 0.00 0.058
14 Damper 14 303 355 303 355 0.303 0.355 0.00 0.058
15 ALL FDS 0.15 0.058
16 FC 813 559 813 559 0.813 0.559 1.10 0.058
Summary
Total Duct Area(M2)
Gage 24 = 162.086 M2
Gage 22 = 12.096 M2
Gage 20 = 0.000 M2
Gage 18 = 0.000 M2
Checked = 174.182 M2
Total Insulation Area(M2)
Area = 174.182 M2
Price = 35.000 Rupees Per M2
Total Price For
Insulation= 6096 Rupees
Total Price For Fabrication And Erection (*Amounts may be varies) Note:-1
Rupees Per M2 Qty (M2) Amount Rs/- The waste can be Taken as 15%
Gage 24 = 120.000 162.086 19450.263 Note:-2
Gage 22 = 140.000 12.096 1693.474 Sizes of Duct (W or H) Gauge GI.Sheet Thickness
Gage 20 = 180.000 0.000 0.000 0 MM To 750 MM Gage 24 0.63 MM
Gage 18 = 300.000 0.000 0.000 751 MM To 1500 MM Gage 22 0.8 to 0.85 MM
Total Price 21143.737 1501 MM To 2250 MM Gage 20 1.0 MM
Total Weight of GI Sheets (KG) 2251 MM & Above Gage 18 1.2 MM
Gage 24 = 801.594 KG's
Gage 22 = 80.712 KG's Note:-3
Gage 20 = 0.000 KG's GI Sheet Gauge Thickness taken from internet.
Gage 18 = 0.000 KG's The values may changes from manufacturer to manufacturer
882.306 KG's
Total Tone= 0.882 Tonnes
First Floor
PROJECT BILL OF MATERIALS FOR DUCTING
Project Name: iiit bulding Prepared By: aquib Fields has to Enter
Project No: 123456 Insulation Thickness = 50.000 MM 0.033
DATE 30-Mar-22 TIME 10.03.15 AM
Total Area Gauge Wise in SQMT Total

TotalNo. of Friction Static


Width Height Length in Perimeter Sheet Total Duct Area Velocity Thermal
Sr.No Duct Type Width-1(MM) Hight-1(MM) Width-2 (MM) Hight-2(MM) 24 Gauge 22 Gauge 20 Gauge 18 Gauge Sheets Value Pressure
(Meters) (Meters) (Meters) (Meters) Gauge .Insulation

MAIN DUCT
1 1std 1 254 254 254 254 0.254 0.254 0.50 1.016 24 0.510 0.000 0.000 0.000 0.177 0.510 1250.000 0.058 0.001 0.610
2 sad2 254 254 254 254 0.254 0.254 2.32 1.016 24 2.357 0.000 0.000 0.000 0.818 2.357 0.058 0.004 2.821
3 sad3 254 254 254 254 0.254 0.254 1.18 1.016 24 1.199 0.000 0.000 0.000 0.416 1.199 0.058 0.002 1.435
4 sad4 254 254 254 254 0.254 0.254 0.30 1.016 24 0.305 0.000 0.000 0.000 0.106 0.305 0.058 0.001 0.365
5 sad5 254 254 254 254 0.254 0.254 2.45 1.016 24 2.489 0.000 0.000 0.000 0.864 2.489 0.058 0.005 2.979
6 sad6 254 254 254 254 0.254 0.254 1.26 1.016 24 1.280 0.000 0.000 0.000 0.445 1.280 0.058 0.002 1.532
7 sad7 254 254 254 254 0.254 0.254 3.07 1.016 24 3.119 0.000 0.000 0.000 1.083 3.119 0.058 0.006 3.733
8 sad8 254 254 254 254 0.254 0.254 2.18 1.016 24 2.211 0.000 0.000 0.000 0.768 2.211 0.058 0.004 2.646
9 sad9 254 254 254 254 0.254 0.254 4.43 1.016 24 4.501 0.000 0.000 0.000 1.563 4.501 0.058 0.008 5.387
10 sad10 254 254 254 254 0.254 0.254 0.89 1.016 24 0.065 0.000 0.000 0.000 0.022 0.065 0.058 0.002 1.082
11 sad11 254 254 254 254 0.254 0.254 2.77 1.016 24 2.814 0.000 0.000 0.000 0.977 2.814 0.058 0.005 3.368
12 sad12 254 254 254 254 0.254 0.254 1.80 1.016 24 1.826 0.000 0.000 0.000 0.634 1.826 0.058 0.003 2.185
13 sad13 254 254 254 254 0.254 0.254 2.10 1.016 24 2.130 0.000 0.000 0.000 0.739 2.130 0.058 0.004 2.549
14 sad14 254 254 254 254 0.254 0.254 1.96 1.016 24 1.991 0.000 0.000 0.000 0.691 1.991 0.058 0.004 2.383
15 sad15 254 254 254 254 0.254 0.254 1.07 1.016 24 1.087 0.000 0.000 0.000 0.377 1.087 0.058 0.002 1.301
16 sad16 254 254 254 254 0.254 0.254 1.12 1.016 24 1.138 0.000 0.000 0.000 0.395 1.138 0.058 0.002 1.362
17 sad17 254 254 254 254 0.254 0.254 1.36 1.016 24 0.065 0.000 0.000 0.000 0.022 0.065 0.058 0.003 1.654
18 sad18 254 254 254 254 0.254 0.254 1.11 1.016 24 1.128 0.000 0.000 0.000 0.392 1.128 0.058 0.002 1.350
19 sad19 254 254 254 254 0.254 0.254 1.73 1.016 24 1.755 0.000 0.000 0.000 0.609 1.755 0.058 0.003 2.100
20 sad20 254 254 254 254 0.254 0.254 0.62 1.016 24 0.628 0.000 0.000 0.000 0.218 0.628 0.058 0.001 0.751
21 sad21 254 254 254 254 0.254 0.254 2.25 1.016 24 2.284 0.000 0.000 0.000 0.793 2.284 0.058 0.004 2.734
22 sad22 254 254 254 254 0.254 0.254 0.55 1.016 24 0.556 0.000 0.000 0.000 0.193 0.556 0.058 0.001 0.665
23 sad23 305 305 305 305 0.305 0.305 1.40 1.220 24 1.708 0.000 0.000 0.000 0.593 1.708 0.058 0.003 1.988
24 sad24 305 305 305 305 0.305 0.305 1.13 1.220 24 0.093 0.000 0.000 0.000 0.032 0.093 0.058 0.002 1.598
25 sad25 305 305 305 305 0.305 0.305 0.76 1.220 24 0.926 0.000 0.000 0.000 0.322 0.926 0.058 0.001 1.078
26 sad26 305 305 305 305 0.305 0.305 2.36 1.220 24 2.879 0.000 0.000 0.000 1.000 2.879 0.058 0.004 3.351
27 sad27 305 305 305 305 0.305 0.305 0.81 1.220 24 0.988 0.000 0.000 0.000 0.343 0.988 0.058 0.002 1.150
28 sad28 305 305 305 305 0.305 0.305 3.46 1.220 24 4.221 0.000 0.000 0.000 1.466 4.221 0.058 0.007 4.913
29 sad29 305 305 305 305 0.305 0.305 2.90 1.220 24 3.538 0.000 0.000 0.000 1.228 3.538 0.058 0.006 4.118
30 sad30 305 305 305 305 0.305 0.305 4.82 1.220 24 5.880 0.000 0.000 0.000 2.042 5.880 0.058 0.009 6.844
31 sad31 356 356 356 356 0.356 0.356 2.52 1.424 24 3.586 0.000 0.000 0.000 1.245 3.586 0.058 0.005 4.089
32 sad32 305 254 305 254 0.305 0.254 1.98 1.118 24 2.214 0.000 0.000 0.000 0.769 2.214 0.058 0.004 2.610
33 sad33 305 254 305 254 0.305 0.254 0.62 1.118 24 0.693 0.000 0.000 0.000 0.241 0.693 0.058 0.001 0.817
34 sad34 305 254 305 254 0.305 0.254 1.56 1.118 24 1.744 0.000 0.000 0.000 0.606 1.744 0.058 0.003 2.056
35 sad35 356 305 355 305 0.356 0.305 1.86 1.322 24 0.109 0.000 0.000 0.000 0.038 0.109 0.058 0.004 2.831
36 sad36 356 305 355 305 0.356 0.305 2.37 1.322 24 3.134 0.000 0.000 0.000 1.088 3.134 0.058 0.005 3.609
37 sad37 356 356 356 356 0.356 0.356 2.51 1.424 24 3.574 0.000 0.000 0.000 1.241 3.574 0.058 0.005 4.076
38 sad38 457 305 457 305 0.457 0.305 2.56 1.524 24 3.901 0.000 0.000 0.000 1.355 3.901 0.058 0.005 4.413
39 sad39 457 305 457 305 0.457 0.305 1.11 1.524 24 1.692 0.000 0.000 0.000 0.587 1.692 0.058 0.002 1.806
40 0.000 0.000 0.000 24 0.000 0.000 0.000 0.000 0.000 0.000 0.058 0.000 0.000

Summary
Total Duct Area(M 2)
Gage 24 = 76.317 M2
Gage 22 = 0.000 M2
Gage 20 = 0.000 M2
Gage 18 = 0.000 M2
Checked = 76.317 M2
Total Insulation Area(M 2)
Area = 101.266 M2
Price = 35.000 Rupees Per M2
Total Price For
Insulation= 3544 Rupees
Total Price For Fabrication And Erection (*Amounts may be varies) Note:-1
Rupees Per M2 Qty (M2) Amount Rs/- The waste can be Taken as 15%
Gage 24 = 120.000 76.317 9158.031 Note:-2
Gage 22 = 140.000 0.000 0.000 Sizes of Duct (W or H) Gauge GI.Sheet Thickness
Gage 20 = 180.000 0.000 0.000 0 MM To 750 MM Gage 24 0.63 MM
Gage 18 = 300.000 0.000 0.000 751 MM To 1500 MM Gage 22 0.8 to 0.85 MM
Total Price 9158.031 1501 MM To 2250 MM Gage 20 1.0 MM
Total Weight of GI Sheets (KG) 2251 MM & Above Gage 18 1.2 MM
Gage 24 = 377.425 KG's
Gage 22 = 0.000 KG's Note:-3
Gage 20 = 0.000 KG's GI Sheet Gauge Thickness taken from internet.
Gage 18 = 0.000 KG's The values may changes from manufacturer to manufacturer
377.425 KG's
Total Tone= 0.377 Tonnes
Summary
Total Duct Area(M 2)
Gage 24 = 137.758 M2
Gage 22 = 41.202 M2
Gage 20 = 0.000 M2
Gage 18 = 0.000 M2 c
Checked = 178.960 M2
Total Insulation Area(M 2)
2
Area = 223.687 M
Price = 35.000 Rupees Per M2
Total Price For
Insulation= 7829 Rupees
Total Price For Fabrication And Erection (*Amounts may be varies) Note:-1
Rupees Per M2 Qty (M2) Amount Rs/- The waste can be Taken as 15%
Gage 24 = 120.000 137.758 16530.924 Note:-2
Gage 22 = 140.000 41.202 5768.336 Sizes of Duct (W or H) Gauge GI.Sheet Thickness
Gage 20 = 180.000 0.000 0.000 0 MM To 750 MM Gage 24 0.63 MM
Gage 18 = 300.000 0.000 0.000 751 MM To 1500 MM Gage 22 0.8 to 0.85 MM
Total Price 22299.260 1501 MM To 2250 MM Gage 20 1.0 MM
Total Weight of GI Sheets (KG) 2251 MM & Above Gage 18 1.2 MM
Gage 24 = 681.281 KG's
Gage 22 = 274.923 KG's Note:-3
Gage 20 = 0.000 KG's GI Sheet Gauge Thickness taken from internet.
Gage 18 = 0.000 KG's The values may changes from manufacturer to manufacturer
956.204 KG's
Total Tone= 0.956 Tonnes
Second Floor

Summary
Total Duct Area(M 2)
Gage 24 = 170.565 M2
Gage 22 = 160.600 M2
Gage 20 = 56.085 M2
Gage 18 = 0.000 M2
Checked = 387.250 M2
Total Insulation Area(M 2)
Area = 419.146 M2
Price = 35.000 Rupees Per M2
Total Price For
Insulation= 14670 Rupees
Total Price For Fabrication And Erection (*Amounts may be varies) Note:-1
Rupees Per M 2
Qty (M2) Amount Rs/- The waste can be Taken as 15%
Gage 24 = 120.000 170.565 20467.835 Note:-2
Gage 22 = 140.000 160.600 22483.983 Sizes of Duct (W or H) Gauge GI.Sheet Thickness
Gage 20 = 180.000 56.085 10095.322 0 MM To 750 MM Gage 24 0.63 MM
Gage 18 = 300.000 0.000 0.000 751 MM To 1500 MM Gage 22 0.8 to 0.85 MM
Total Price 53047.139 1501 MM To 2250 MM Gage 20 1.0 MM
Total Weight of GI Sheets (KG) 2251 MM & Above Gage 18 1.2 MM
Gage 24 = 843.531 KG's
Gage 22 = 1071.603 KG's Note:-3
Gage 20 = 440.268 KG's GI Sheet Gauge Thickness taken from internet.
Gage 18 = 0.000 KG's The values may changes from manufacturer to manufacturer
2355.402 KG's
Total Tone= 2.355 Tonnes
PROJECT BILL OF MATERIALS FOR DUCTING
Project Name: iiit bulding Prepared By: aquib Fields has to Enter
Project No: 123456 Insulation Thickness = 50.000 MM 0.033
DATE 30-Mar-22 TIME 10.03.15 AM
Total Area Gauge Wise in SQMT Total

TotalNo. of Friction Static


Width Height Length in Perimeter Sheet Total Duct Area Velocity Thermal
Sr.No Duct Type Width-1(MM) Hight-1(MM) Width-2 (MM) Hight-2(MM) 24 Gauge 22 Gauge 20 Gauge 18 Gauge Sheets Value Pressure
(Meters) (Meters) (Meters) (Meters) Gauge .Insulation

MAIN DUCT
1 reducers1 864 762 854 762 0.859 0.762 0.30 0.058
2 reducers2 711 559 711 559 0.711 0.559 0.30 0.058
3 reducers3 356 365 356 356 0.356 0.361 0.35 0.058
4 reducers4 711 610 711 610 0.711 0.610 0.30 0.058
5 reducers5 559 457 559 457 0.559 0.457 0.30 0.058
6 reducers6 406 356 406 356 0.406 0.356 0.30 0.058
7 reducers7 559 457 559 457 0.559 0.457 0.30 0.058
8 reducers8 356 356 356 356 0.356 0.356 0.30 0.058
9 reducers9 356 356 356 356 0.356 0.356 0.29 0.058
10 reducers10 610 559 610 559 0.610 0.559 0.30 0.058
11 reducers11 508 457 508 457 0.508 0.457 0.30 0.058
12 reducers12 762 660 762 660 0.762 0.660 0.30 0.058
13 reducers13 457 356 457 356 0.457 0.356 0.30 0.058
14 reducers14 457 356 457 356 0.457 0.356 0.30 0.058
15 tee1 432 356 432 356 0.432 0.356 0.01 0.058
16 tee2 432 356 432 356 0.432 0.356 0.08 0.058
17 tee3 432 356 432 356 0.432 0.356 0.09 0.058
18 tee4 432 356 432 356 0.432 0.356 0.08 0.058
19 tee5 432 356 432 356 0.432 0.356 0.08 0.058
20 tee6 432 356 432 356 0.432 0.356 0.08 0.058
21 tee7 483 356 483 356 0.483 0.356 0.10 0.058
22 tee8 483 356 483 356 0.483 0.356 0.09 0.058
23 tee9 483 356 483 356 0.483 0.356 0.09 0.058
24 tee10 483 356 483 356 0.483 0.356 0.09 0.058
25 tee11 483 356 483 356 0.483 0.356 0.09 0.058
26 tee12 762 711 762 711 0.762 0.711 0.14 0.058
27 tee13 431 356 431 356 0.431 0.356 0.09 0.058
28 tee14 533 356 533 356 0.533 0.356 0.09 0.058
29 tee15 483 356 483 356 0.483 0.356 0.09 0.058
30 elbows 1 1066 1270 1066 1270 1.066 1.270 1.03 0.058
31 elbows 2 1117 965 1117 965 1.117 0.965 1.72 0.058
32 elbows 3 610 508 610 508 0.610 0.508 0.94 0.058
33 elbows 4 356 356 356 356 0.356 0.356 0.54 0.058
34 elbows 5 356 356 356 356 0.356 0.356 0.54 0.058
35 elbows 6 610 508 610 508 0.610 0.508 0.94 0.058
36 elbows 7 406 356 406 356 0.406 0.356 0.62 0.058
37 elbows 8 559 457 559 457 0.559 0.457 0.86 0.058
38 elbows 9 1016 762 1016 762 1.016 0.762 0.98 0.058
39 elbows 10 610 559 510 559 0.560 0.559 0.40 0.058

PROJECT BILL OF MATERIALS FOR DUCTING


Project Name: iiit bulding Prepared By: aquib Fields has to Enter
Project No: 123456 Insulation Thickness = 50.000 MM 0.033
DATE 30-Mar-22 TIME 10.03.15 AM
Total Area Gauge Wise in SQMT Total
Width Height Length in Perimeter Sheet TotalNo. of Sheets Total Duct Area Velocity Friction Value Static Pressure Thermal
Sr.No Duct Type Width-1(MM) Hight-1(MM) Width-2 (MM) Hight-2(MM) 24 Gauge 22 Gauge 20 Gauge 18 Gauge
(Meters) (Meters) (Meters) (Meters) Gauge .Insulation

MAIN DUCT
1 Dampers1 1066 1270 1066 1270 1.066 1.270 0.00 0.000 1250.000 0.058
2 Dampers2 610 559 610 559 0.610 0.559 0.00 0.000 0.058
3 Dampers3 813 610 813 610 0.813 0.610 0.00 0.000 0.058
4 Dampers4 762 711 762 711 0.762 0.711 0.00 0.000 0.058
5 Dampers5 559 457 559 457 0.559 0.457 0.00 0.000 0.058
6 Dampers6 1016 762 1016 762 1.016 0.762 0.00 0.000 0.058
7 Dampers7 813 559 813 559 0.813 0.559 0.00 0.000 0.058
8 Dampers8 762 660 762 660 0.762 0.660 0.00 0.000 0.058
Summary
Total Duct Area(M 2)
Gage 24 = 151.154 M2
Gage 22 = 82.530 M2
Gage 20 = 42.308 M2
Gage 18 = 0.000 M2
Checked = 275.992 M2
Total Insulation Area(M 2)
Area = 275.992 M2
Price = 35.000 Rupees Per M2
Total Price For
Insulation= 9660 Rupees
Total Price For Fabrication And Erection (*Amounts may be varies) Note:-1
Rupees Per M2 Qty (M2) Amount Rs/- The waste can be Taken as 15%
Gage 24 = 120.000 151.154 18138.489 Note:-2
Gage 22 = 140.000 82.530 11554.159 Sizes of Duct (W or H) Gauge GI.Sheet Thickness
Gage 20 = 180.000 42.308 7615.417 0 MM To 750 MM Gage 24 0.63 MM
Gage 18 = 300.000 0.000 0.000 751 MM To 1500 MM Gage 22 0.8 to 0.85 MM
Total Price 37308.065 1501 MM To 2250 MM Gage 20 1.0 MM
Total Weight of GI Sheets (KG) 2251 MM & Above Gage 18 1.2 MM
Gage 24 = 747.532 KG's
Gage 22 = 550.679 KG's Note:-3
Gage 20 = 332.117 KG's GI Sheet Gauge Thickness taken from internet.
Gage 18 = 0.000 KG's The values may changes from manufacturer to manufacturer
1630.329 KG's
Total Tone= 1.630 Tonnes
PIPING THEORY
Water piping system:
 Once through & recirculating:
Water piping systems discussed are divided into once through and recirculating system. In once through
system, water passes through the equipment only once and is discharged. In a recirculating system water is not
discharged, but flows in repeating circuit from the heat exchanger to refrigeration equipment and back to the heat
exchanger.
Open & closed system:
Recirculating system can be classified as open or close system. an open system is the one in which the water
flows into the reservoir open to atmosphere; cooling towers, air washers and collecting tanks are examples of
reservoir open to atmosphere. A closed system is the one in which the flow of water is not exposed to atmosphere
at any point of flow. This system usually contains an expansion tank that is open to atmosphere but the water
area exposed is insignificant.

Water piping design:


 There is a friction loss in any pipe through which water is flowing. This loss depends on the following factors:
1. Water velocity
2. Pipe diameter
3. Interior surface roughness
4. Pipe length

 The quantity of water required is determined from the air-conditioning load and the water velocity by the pre-
determined recommendations. These two factors are used to determine pipe size and friction rate.

Types of pipes:
1. Mild steel pipes (ERW-Electro resistive welding pipes)
Code name: IS-1239 (Black color painted pipes)
Class A: Thickness up to 2.56mm, with a yellow color band.
Class B: Thickness up to 4.5mm, with a blue color band.
Class C: Thickness 4.5 to 12.56 mm, with a red color band.

2. Carbon steel pipes.


Code name: IS-1239 / ASTM 10, 10.3
SCH - 20: Less thick
SCH - 40,SCH - 80: Best suited for chilled water pipeline(3.5mm – 7.5mm thick)
SCH - 100, SCH – 120, SCH-160: High Thickness (12.5mm Thickness above)

3. Stainless Steel Pipes (SS).


Type – 304, 316.
Thickness – 5 mm min.
Physical View:
 Seam pipes.
 Seam less pipes.
 Spiral pipes.

Pipe Fittings:
 Flanges.
 Reducers.
 Elbows.
 Dead end/ Dummy flange/Blind flange.
 T – Pipe fitting.
 Nipples.
Valves used in piping:
 Gate valve/Butterfly valve.
 Globe valve.
 Ball valve.
 Non – return valve:
I. Swing check valve.
II. Lift check valve.
 Motorized control valve:
I. 2 – Way Motorized control valve.
II. 3 – Way Motorized control valve.
 Strainer:
I. Y – Strainer.
II. T – Strainer.
III. Pot type Strainer.
 Balancing valve.
 Dynamic motorized valve.
 Btu meter.
 Flexible bellow.

NOTE: 1) For closed circuit system 2.4 USGPM / 1TR is taken.

2) For open circuit system 3 USGPM / 1 TR is taken.


Description about Valves
1. Butterfly Valves

A butterfly valve is a valve which can be used for isolating or


regulating flow. The closing mechanism takes the form of a disk.
Operation is similar to that of a ball valve, which allows for quick shut
off. Butterfly valves are generally favored because they are lower in cost
to other valve designs as well as being lighter in weight, meaning less
support is required. The disc is positioned in the center of the pipe,
passing through the disc is a rod connected to an actuator on the outside
of the valve. Rotating the actuator turns the disc either parallel or
perpendicular to the flow. Unlike a ball valve, the disc is always present
within the flow; therefore a pressure drop is always induced in the flow,
regardless of valve position.

2. Gate Valves

A gate valve, also known as a sluice valve, is a valve that opens by lifting a
round or rectangular gate/wedge out of the path of the fluid. A gate valve,
also known as a sluice valve, is a valve that opens by lifting a round or
rectangular gate/wedge out of the path of the fluid. The distinct feature of
a gate valve is the sealing surfaces between the gate and seats are planar,
so gate valves are often used when a straight-line flow of fluid and
minimum restriction is desired. The gate faces can form a wedge shape or
they can be parallel. Gate valves are primarily used to permit or prevent
the flow of liquids, but typical gate valves shouldn't be used for regulating
flow, unless they are specifically designed for that purpose.

3. Globe Valves
A globe valve, different from ball valve, is a type of valve used for
regulating flow in a pipeline, consisting of a movable disk-type element
and a stationary ring seat in a generally spherical body. Globe valves are
named for their spherical body shape with the two halves of
the body being separated by an internal baffle. This has an opening that
forms a seat onto which a movable plug can be screwed in to close (or
shut) the valve. The plug is also called a disc or disk. In globe valves, the
plug is connected to a stem which is operated by screw action using a
hand wheel in manual valves. Typically, automated globe valves use
smooth stems rather than threaded and are opened and closed by
an actuator assembly.
4. Balancing Valves
A cooling or heating water distribution system is in balance when the flow in the whole system
(through the component terminal lines, distributing lines and main distributing lines)
corresponds to the flow rates that were specified for the design of the system. If the correct
balancing of the system is not established, this will result in unequal distribution of the flow so
that there will be a surplus effect in some of the terminals, whereas the effect will be inadequate
in others. The result of this will be that the wanted heating/chilling will not be ensured in all
parts of the installation. In practice it is not possible to make a correctly balanced system by
manipulation of the piping or alteration of the pipe dimensions only. Only a correct set
of balancing valves can ensure the correct distribution of the flow in the system.
5. 2-Way motorized Valve/3-Way Motorized Valve

A check valve, clack valve, non-return valve or one-


way valve is a valve that normally
allows fluid (liquid or gas) to flow through it in only
one direction. Check valves are two-port valves,
meaning they have two openings in the body, one for
6. Non Return Valve fluid to enter and the other for fluid to leave. There
are various types of check valves used in a wide
variety of applications. Check valves are often part
of common household items. Although they are
available in a wide range of sizes and costs, check
valves generally are very small, simple, or
inexpensive. Check valves work automatically and
most are not controlled by a person or any external
control; accordingly, most do not have any valve
handle or stem. The bodies (external shells) of most
check valves are made of plastic or metal. An
important concept in check valves is the
cracking pressure which is the minimum upstream
7. Flexible Bellows pressure at which the valve will operate. Typically
the check valve is designed for and can therefore be
specified for a specific cracking pressure.

For a cylinder with a constant diameter the reinforcement angle is constant as


well and is 54.7º. This also known as the magic angle or neutral angle. The
neutral angle is the angle where a wound structure is in equilibrium. For a
cylinder this is 54.7º, but for a more complex shape like a bellow which has a
varying radius over the length of the product, this neutral angle is different for
each radius. In other words, for complex shapes there is not one magic angle
but the fibers follow a geodesic path with angles varying with the change in
radius. To obtain a reinforcement structure with iso-tensoidal loading the
geometry of the complex shape must follow an iso-tensoid meridian profile.
Typically the check valve is designed for and can therefore be specified for a
8. Strainers
specific cracking pressure.

Stay flow Y strainers mechanically remove solids from flowing steam, gases or liquid
piping systems with the use of a perforated or wire mesh straining screen, and are
used to protect equipment. They get their names from their configuration, which
includes a branch angled off the flow path. “Y” strainers are most often used for steam
and gases, but are occasionally used for liquids. They have less debris holding capacity
and higher pressure drops than basket strainers, but they can be used in
either horizontal or vertical pipe runs where flow is downwards. They can also be fitted
with a blow-off connection at the end of the branch end that includes a valve, which
allows for cleaning. The valve is opened without shutting off the flow or disassembling
the strainer, as the flow through the pipe will flush out the solids in the screen.
GPM Calculations for 100TR WATER COOLED CHILLER
Calculation for Chilled Water Piping (Closed Piping System)

Primary Pump :
Section Flow Velocity Pipe size diameter Friction loss
Suction side TR x2.4 7fpm 4inch 4 inches of water
100 x2.4=240gpm 101.6mm gauge/100ft
Discharge side TR x2.4 6.5fpm 3.5 inch 10 inches of water
100 x2.4= 240gpm 88.9fpm gauge/100ft

(Open Piping System) Secondary Pump:


Section Flow Velocity Pipe size diameter Friction loss
Suction side TR x3.0 7.5fpm 4inch 6 inches of water
100 x3.0=300 gpm 101.6 mm gauge/100ft
Discharge side TR x3.0 7.5f 3.5inch 15 inches of water
100 x3= 300gpm 88.9 fpm gauge/100ft

Chilled water Supply Piping (CHWS):


Secondary Pump:
𝑮𝑷𝑴 𝑿 𝑻𝑫𝑯 𝑿 𝑺𝒑.𝒈𝒓𝒂𝒗𝒊𝒕𝒚
Secondary Pump Horse power =
𝟑𝟗𝟔𝟎 𝑿 𝜼

Where,

GPM = 240

Total dynamic Head loss = Total Suction head loss + Total Discharge Head loss

= 9.91+8.61

= 18.53 Feet’s

Specific Gravity of Secondary Refrigerant (water) = 1,

𝜼= Pump Efficiency = 80% = 0.80


Therefore,
𝟐𝟒𝟎𝑿𝟏𝟖𝟓𝟐 𝑿 𝟏
Secondary pump Horse power = = 140.5HP≈105.33KW
𝟑𝟗𝟔𝟎 𝑿 𝟎.𝟖𝟎

_________________________________________________________

Primary Pump:
𝑮𝑷𝑴 𝑿 𝑻𝑫𝑯 𝑿 𝑺𝒑.𝒈𝒓𝒂𝒗𝒊𝒕𝒚
PrimaryPump Horse power =
𝟑𝟗𝟔𝟎 𝑿 𝜼

Where,

GPM = 240

Total dynamic Head loss = Total Suction head loss + Total Discharge Head loss

= 9.79+21.59

= 30.38 Feets

Specific Gravity of Secondary Refrigerant (water) = 1,

𝜼 = Pump Efficiency = 80% = 0.80


Therefore,
𝟐𝟒𝟎𝑿𝟑𝟎𝟑𝟖 𝑿 𝟏
Primary pump Horse power = = 230.5HP≈172.78KW
𝟑𝟗𝟔𝟎 𝑿 𝟎.𝟖𝟎
Piping BOQ
PIPING BOQ
GAUGES AND ACCESSORIES
AHU PUMP CHILLER COOLING TOWER Total Qty Remarks
PRESURE GAUGES 2 12*6 12*3 0 126
TEMPRETURE GAUGES 2 0 12*3 0 54
AIR VENTS 2 0 7 1 17
BALL VALVES 0 0 0 0 0
FLOW SWITCH 0 0 1*3 0 3
DIELECTRIC UNION 0 0 0 0 0
VICTOLIC JOINTS 0 0 1*3 0 3

PIPE AND VALVES


PIPE SIZE in inches\mm
1" 2" 2.5" 3" 4" 5" 6" 7" 8" 9" 10" QUANTITY
ITEM DISCRIPTION
25 50 65 80 100 125 ## ## ## ## ##
PIPE LENGTH(Feets) 0 0 0 0 100 0 0 0 0 0 100
BUTTER FLY/GATE VALVE 0 2 0 0 2 1 2 0 0 0 0 7
STRAINER VALVE 0 2 0 0 2 0 0 0 0 0 0 4
FLEXIBLE BELLOWS 0 0 0 0 2 0 0 0 0 0 0 2
PRESSURE GAUGE 0 2 0 0 2 0 0 0 0 0 0 4
TEMPERATURE GAUGE 0 2 0 0 0 1 1 0 0 0 0 4
GLOBE/PICV VALVE 0 1 0 0 0 0 0 0 0 0 0 1
DYNAMIC BLANCING VALVE 0 3 0 0 0 1 0 0 0 0 0 4
FLOW SWITCH 0 0 0 0 0 0 0 0 0 0 0 0
NON RETURN VALVE 0 0 0 0 0 0 0 0 0 0 0 0
3 WAY or 2 WAY MOTORISED VALVE 0 0 0 0 0 0 3 0 0 0 0 3
TOTAL 129
PIPING LAYOUTS SLD & DLD
Final BOQ

NAME OF THE WORK : PROVISION OF HVAC SYSTEM FOR CORPORATE OFFICE


CA No. DESIPL/D/02 OF 2014-15. Date: 12-05-2015. RAR NO. FINAL RAR
AGENCY :XYZ PVT. LTD.,
AS PER
AS PER BOQ AS PER SITE % Of
SOTERS
Claimed
S.NO DESCRIPTION OF WORKS UNIT QTY RATE AMOUNT Qty AMOUNT Qty AMOUNT
SCREW TYPE CHILLING MACHINES:
Supply, installation testing and commissioning of water cooled Screw Chilling
machine complete with semihermatically sealed compressors, multi circuit chiller,
shall and tube condenser, microprocessor based control panel, including oil
separators pressure relief devices, filter drier moisture indicators, refrigerant
1
economisers and complete operating charge of both refrigerant & compressor oil
control safeties and diagnostics, display, refrigerant piping, mounting baseframe
etc. complete as per the specifications and the drawings of 154 TR actual
Cooling capacity.
Operation Parameters:
Chiller:
Water Temerature IN -54F
Water Temerature IN -44F
Fouling Factor - 0.0005 FPS
Condenser:
Water Temerature IN -90F
Water Temerature IN -97.5F
Fouling Factor - 0.001 FPS Nos 2

Supply, installation, testing and commissioning of end suction


split casing type watter pump sets factory mounted on a common
base with electric motor for recirculation of water for the central
2 air-conditioning system.All pumps shall be aligned. The pump
motor shall be suitable for 415+10% V, 50cycles, 3phase power
supply. The quoted rates shall be inclusive of insulation and
clading. Pump performance charaterstics shall be as followings as
per drawings and specifications.
a Chilled water Primary Pumps 1
System:
Water flow Rate: 368US GPM at 36 Feet Head.
Head : 36 Feet Nos 3

b Chilled water secondary Pumps with VFDs


System:
Water flow Rate: 368 US GPM at 44 m Head. Nos 3
Head : 44 Feet
c Hot water Pumps for Winter Heating System:
Water flow Rate: 250 US GPM at 24m Head. Nos
d Condenser water Pumps for central air-conditioning
system w/o insulation
Water flow Rate: 720 US GPM AT 16.68 Feet head
Head : 16.68feet Nos 2

Hot Water Generators:


Supply, Installation, testing and commissioning of electricles Hot
water generator equipped with sufficient no.of flanges and electric
immersion heaters. The pressure Vessel shall be constructed as
per ASME standards and insulated on all sides with 2layers of
50mm thick fibrerglass with 28 guage Aluminium cladding as per
specification. The hot water generator shall be equipped with all
automatic and safety controls such as manual reset, high
3 temperature water outlet, step controller and recycling relay,on/off
switch type thermostat, pilot light,low water cut off and
othercontrols as per manufacturers recommednditions. All basic
controls and terminals shall be located in an integral control
cabinet factory wired abd tested. The hot water generator shall be
suitable for415+10% volts/50cycles, 3phase power supply. The
entire hot water generator shall be factory assembled and tested
requiring only connection to services of 250 KW
water in - 110 Deg
Water in - 120 Deg No

Cooling Towers
Supply, Installation, Testing and commissioning of FRP induced
draft Type cooling towers. Each cooling tower shall be complete
with casing, distribution system, filling louvers, ladder,propellar
fans,motors and shall be suitable for 415 V/mP/50HZ power Nos
supply, isolator panel with suitble MCB at each cooling
tower.There shall be 1No fan each one with 10HP motor. These
coling towers shall be complete as per the drawings and
specifications.
a 307 TR
Air Handling Units:
Supply, installation, testing and commissioning of sheer metal
sectionalised construction draw thrh type in Double skin
construction. Each Air Handling Units shall be with filter section
with filter section with prefilters, fhilled water cooling coil of copper
tube & AI.Fins construction, sgirrel cage induction motor,
5
centrifugal fan,spray type humidifier for RH balance pump. belt
drive and vibration isolators, coil size shall be selected for a
max.face velocity of 500FPM and static shall be 50mm. Motor
shall be suitable for 415V/50HZ AC supply,Air moving capacities
shall be as as follows as [er drawings and specifiacations.
a 2126 cfm with 4row cooling coil Nos 1
b 2085cfm with 4row cooling coil Nos 1
c 7750 cfm with 4row cooling coil Nos 1
d 5236 cfm with 4row cooling coil Nos 1

Fan Coil Units :


Supply, Installation, testing and commissioning of horizontal hide
way type fan coil unit complete with fan, fan motor, cooling coil,
6 filters, 3 way motarised with snap acting thermostat and ball valve
set etc. and complete as per specifications and and drawings of
below capacities.
a) 7 TR (2000 cfm ) No.
b) 6 TR (1600 cfm ) No.
c) 3.5 TR( No.
D) 3 TR( No. 14
Exhaust fan sections for basement:
Pressurisation Fan sections:
Supply, Installation, testing and commissioning of DIDW
7 centrifugal fan section with motor, drives set mounting frame, GI
Sheet casing of 16 Guage complete as per specifications and
drawings of below capacities for staricase pressurisation.
a) 22000 cfm Nos 1
Ducted Inline Type Fans :
Supply, Installation, testing and commissioning of ducted inline
8 type exhaust fans complete with motor, fan, exhaust Louvers as
per drawings and specifications of following sizes:
a) 2,000 cfm with 4row cooling coil Nos
b) 1,600 cfm with 4row cooling coil Nos

Main A/C Panel


Installation, testing and commissioning of Main A/C Panel (MCC),
9 cubicle compartmentalised floor mounted type made of 2 mm
thick steel sheet duly painted complete as per the specifications
and drawing and as detailed below:
1No. 1600 Amps ACB MDO type incomer with KWH meter, phase
indicating lamps with control fuse & toggle switch, voltmeter and
selector switch, ammeter with CTs and selector switch
1 Set 2000 Amps triple pole with neutral al. Bus Bars duly sleeved
3 Nos outgoing feeders for Chilling Machines Each with 630 A TPN
MCCB and on / off indication lamps (One no.spare)
3 Nos 63 Amps TPN MCCB outgoing for Condensor water pumps
with star delta Starter.
3 Nos 63 Amps TPN MCCB outgoing for chilled water primary
pumps with star delta Starter.
3 Nos 63 Amps TPN MCCB outgoing for chilled water secondary
pumps with star delta Starter
2 Nos 63 Amps TPN MCCB outgoing for hot water pumps with star
delta starter.
3 No. 32 Amps TPN MCCB outgoing for the cooling tower (10 HP )
No 1
with star delta starter for cooling towers (One no spare )
Control panel in Air Handling Unit Rooms
Supply, Installation, testing and commissioning of the following
cubicle type openable front, sheet steel wait mounted controlk
panels sleeve tyupe al . Nus bar including anchoring into the wall,
These panels shall be comlete in all respects as per the drawings
and the specifications. The panel shall include the following
accessories.

MCCB as per rating given below.


Terminal block for power distribution.
Single Phase Preventor.
Phase indicating lights and indicating lights for ON / TRIP status
Digital type Ammeter and suitable size CT and slector switche.
Time delay relay for automatic restart of AHUs motors.
Auto / Manual stop selector switch shall be provided in each AHU
panel. The same should provide potential free contact for position
montioring to BMS system.
All starters shall have suitable potential free contacts
Wiring for microswitch for stopping the fan when fire dampers
closes.
The number of AHU panel shall be as detailed below:
63 Amps TPN MCCB with 1 No 7.5 HP DOL Starter for AHU fan
motor and & 16 Amps. DP MCB with 1# 1 HP DOL Starter for Sets
pump.

63 Amps TPN MCCB with 1No.7.5 HP Star Delta Starter for AHU
fanmotor and & 16 Amps. DP MCB with 1 # 1 HP DOL Starter for Sets
pmps.
63 Amps TPN MCCB with 1 No.12.5 HP Star Delta Starter for AHU
fan motor and & 16 Amps. DP MCB with 1 # 1 HP DOL Starter for Sets
Pump.
63 amps TPN MCCB with 1 NO. 15 Hp star Delta Starter for AHU
fan motor and & 16 Amps. DP MCB with 1 # 1 HP DOL Starter for Sets
Pump.
63 Amps TPN MCCB with 1 No. 20 Hp Star Delta Starter for AHU
fan motor and & 16 Amps. DP MCB with 1 # 1 HP DOL Starter for Sets
Pump.

Control Panle for ventilatin and pressurisation fans :


Supply, Installatin, Testing and commissioning of the following
cubicle type openable front, sheet steel wall mounted control
panels sleeve tyupe Al. bus bar including anchoring into the wall.
These pabels shall be complete in all respects as per the drawings
and the specficatins. The panels shall include the following
accessories :
MCCb as per rating given below.
Terminal block for power distribution.
Single Phase Preventor.
Digital type Ammeter and suitable size CT and slector switche.
Digital type Ammeter and suitable size CT and slector switche.
Time delay relay for automatic restart of AHUs motors.
Auto / Manual stop selector switch shall be provided in each AHU
panel.
All starters shall have suitable potential free contacts
The number of EI. Panels shall be as detailed below:
32 Amps TPN MCCB with 1 No. 5.0 HP / 3.0 HP DOL Starter Sets

Condenser Water Piping :


Supply , Installatin , Testing and commissioning of "C" class mild
steel condenser water piping with all necessary fittings like bends,
tees, reducers, flanges supports etc complete as per drawings and
specifications of below sizes :

250 mm dia Feets


200 mm dia Feets
175 mm dia Feets
150 mm dia Feets 1035
125 mm dia Feets
100 mm dia Feets 155
50 mm dia Feets 100
25 mm dia Feets 75
Condenser Circuit Valves:
Supply, Installatin, Testing and commissioning of following type of
valves as per drawings and specifications for the condenser water
circuit complete with all fittings etc.
Butterfly Valves
250 mm dia Nos
200 mm dia Nos
175 mm dia Nos
150 mm dia Nos 2
125 mm dia Nos
100 mm dia Nos 5
50 mm dia Nos 4
Balancing Valve
200 mm dia Nos
125 mm dia Nos
Check Valve
150 mm dia Nos
200 mm dia Nos 2
Y-Strainer
200 mm dia Nos 4
d) Y-Strainers
150 mm dia Nos 3
80 mm dia Nos
65 mm dia Nos
50 mm dia Nos
e) Pot Strainer
200 mm dia No
Flexible Pipe connection to be used at pump
f)
suction/discharge and chilling machines
125 mm dia Nos
100 mm dia Nos 5

g) Water Flow Switch Nos 3

2-way Motorised Valves:


Supply, installation, testing and commissioning of following Globe
type UL/CE Approved 2-way motorised valves for AHUs with
17 status feedback for the chilled water and hot water circuit with
actuators, linkage, control wiring and all fittings and insulation
and 28 Guage Al.cladding as per drawings and specifications.
a) 100 mm dia. Pipe size Nos
b) 80 mm dia. Pipe size Nos
c) 65 mm dia. Pipe size Nos
d) 50 mm dia. Pipe size Nos
AHUs Thermostats:
Supply, installation testing and commissioning of proportional
18 type cooling and heating thermostats for the various Air Handling
Nos 12
Units complete with required control wiring/installation kit etc. as
per drawings and specifications.

Supply, installation, testing and commissioning of following


19 Thermameters and pressure guage as per drawings and
specifications for the Chilled/hot water circuit complete with
syphon and fittings
a) Pressure guage Nos 45

b) Temperature guage Nos 25

Expansion Tank:
Supply, installation, testing and commissioning of 1000 Ltrs
capacity expansion tank fabricated from 3mm MS sheet and
having 19 mm thick nitrile rubber foam insulation covered with 28
20 No 1
Gas Aluminium sheet with man hole cover, drain, overflow, quick
fill, water supply connections, valves and complete in all respects
as per drawings and specification 1000mm X 1000mm X 1000mm
Drain Piping:
Supply, installation, testing and commissioning of "B" class GI
21 drain piping complete with fitting etc & nitrile foam insulation with
sealing tapes & 28 G Aluminium cladding complete as per
drawings & specifications of below sizes.
a) 100 mm dia Meters
b) 50 mm dia Meters
c) 40 mm dia Meters
d) 32 mm dia Meters
e) 25 mm dia Meters
Supply, installation, testing and commissioning of Air Vents 15
22 Meters
mm dia

Supply, installation, testing and commissioning of 1" dia Ball


23 Nos
valves for drain with fittings etc.

Rectangular Ductwork:
Supply, installation, testing commissioning of rectangular sheet
metal ductwork complete with supports,
24 dampers/splitters/vanes/fasteners/nuts/washers and all
ancilliary items as per specification and drawings of the following
guages / thickness: (To be fabricated manually and installed at
site)
a) 24 Gauge Sqmt 895
b) 22 Guage Sqmt 305
c) 20 Guage Sqmt 101
d) 18 Guage Sqmt -

Nitrile Rubbe Foam Insulation :


Supply, installation, testing and commissioning of elastomeric
25 nitrile rubber insulation on ducts complete as per the drawings SM NR
and specifications of following sizes.
a) 9 mm thickness

Supply, installation, testing and commissioning of 25 mm thick &


32 kg/m3 density fiberglass insulation boards fixed on GI frame &
26 covered with 26 guage perforated Aluminium sheet with nuts, SM 1233.457
bolts and complete as per drawings and specifications for the
accoustic lining of a/c ducts.

underdeck Insulation:
Supply, installation, testing and commissioning of 25 mm thick &
27 48 kg/m3 density fiberglass insulation boards fixed on GI frame
Sqmt NR
for underdeck insulation with all accessories and complete as per
drawings and specifications.

Grilles/Diffusers/Louvers/VCDs/FDs :
Supply, installation, testing and commissioning of Supply air
28 grilles with dampers in extruded Aluminium construction and Sqft 13
powder coated finish as per specifications and drawings.6 x 6

Supply, installation, testing and commissioning of Supply air


29 Diffusers with dampers in extruded Aluminium construction and Sqmt 72
powder coated finish as per specifications and drawings.9X9

Supply, installation, testing and commissioning of Supply air


30 Diffusers with dampers in extruded Aluminium construction and Sqmt 6
powder coated finish as per specifications and drawings.12X12
d) Y-Strainers
150 mm dia Nos 3
80 mm dia Nos
65 mm dia Nos
50 mm dia Nos
e) Pot Strainer
200 mm dia No
Flexible Pipe connection to be used at pump
f)
suction/discharge and chilling machines
125 mm dia Nos
100 mm dia Nos 5

g) Water Flow Switch Nos 3

2-way Motorised Valves:


Supply, installation, testing and commissioning of following Globe
type UL/CE Approved 2-way motorised valves for AHUs with
17 status feedback for the chilled water and hot water circuit with
actuators, linkage, control wiring and all fittings and insulation
and 28 Guage Al.cladding as per drawings and specifications.
a) 100 mm dia. Pipe size Nos
b) 80 mm dia. Pipe size Nos
c) 65 mm dia. Pipe size Nos
d) 50 mm dia. Pipe size Nos
AHUs Thermostats:
Supply, installation testing and commissioning of proportional
18 type cooling and heating thermostats for the various Air Handling
Nos 12
Units complete with required control wiring/installation kit etc. as
per drawings and specifications.

Supply, installation, testing and commissioning of following


19 Thermameters and pressure guage as per drawings and
specifications for the Chilled/hot water circuit complete with
syphon and fittings
a) Pressure guage Nos 45

b) Temperature guage Nos 25

Expansion Tank:
Supply, installation, testing and commissioning of 1000 Ltrs
capacity expansion tank fabricated from 3mm MS sheet and
having 19 mm thick nitrile rubber foam insulation covered with 28
20 No 1
Gas Aluminium sheet with man hole cover, drain, overflow, quick
fill, water supply connections, valves and complete in all respects
as per drawings and specification 1000mm X 1000mm X 1000mm
Drain Piping:
Supply, installation, testing and commissioning of "B" class GI
21 drain piping complete with fitting etc & nitrile foam insulation with
sealing tapes & 28 G Aluminium cladding complete as per
drawings & specifications of below sizes.
a) 100 mm dia Meters
b) 50 mm dia Meters
c) 40 mm dia Meters
d) 32 mm dia Meters
e) 25 mm dia Meters
Supply, installation, testing and commissioning of Air Vents 15
22 Meters
mm dia

Supply, installation, testing and commissioning of 1" dia Ball


23 Nos
valves for drain with fittings etc.

Rectangular Ductwork:
Supply, installation, testing commissioning of rectangular sheet
metal ductwork complete with supports,
24 dampers/splitters/vanes/fasteners/nuts/washers and all
ancilliary items as per specification and drawings of the following
guages / thickness: (To be fabricated manually and installed at
site)
a) 24 Gauge Sqmt 895
b) 22 Guage Sqmt 305
c) 20 Guage Sqmt 101
d) 18 Guage Sqmt -

Nitrile Rubbe Foam Insulation :


Supply, installation, testing and commissioning of elastomeric
25 nitrile rubber insulation on ducts complete as per the drawings SM NR
and specifications of following sizes.
a) 9 mm thickness

Supply, installation, testing and commissioning of 25 mm thick &


32 kg/m3 density fiberglass insulation boards fixed on GI frame &
26 covered with 26 guage perforated Aluminium sheet with nuts, SM 1233.457
bolts and complete as per drawings and specifications for the
accoustic lining of a/c ducts.

underdeck Insulation:
Supply, installation, testing and commissioning of 25 mm thick &
27 48 kg/m3 density fiberglass insulation boards fixed on GI frame
Sqmt NR
for underdeck insulation with all accessories and complete as per
drawings and specifications.

Grilles/Diffusers/Louvers/VCDs/FDs :
Supply, installation, testing and commissioning of Supply air
28 grilles with dampers in extruded Aluminium construction and Sqft 13
powder coated finish as per specifications and drawings.6 x 6

Supply, installation, testing and commissioning of Supply air


29 Diffusers with dampers in extruded Aluminium construction and Sqmt 72
powder coated finish as per specifications and drawings.9X9

Supply, installation, testing and commissioning of Supply air


30 Diffusers with dampers in extruded Aluminium construction and Sqmt 6
powder coated finish as per specifications and drawings.12X12
CONCLUSION
Estimating a conceptual HVAC design can prove to be challenging. There are many methods estimators have
adopted over the years to help accurately complete a system with limited information. HVAC equipment is one
of the most important components in the system since it tends to have the highest overall cost. Making sure an
estimator has quantified all of these pieces is important since the other components such as piping are impacted
by these quantities. Since the equipment affects the affects the quantity of piping, the equipment should be the
first item that an estimator focuses on. After the equipment that will be used is established, an estimator can
accurately quantify the meters of the pipe needed using the methods disused in this paper. Knowing the type of
building and how it will be used is very helpful to the estimate since the influences the amount of duct that will
be required. Estimators with past Experience as well as using the techniques and methods discussed, can help
provide accuracy when trying to estimate quantities for a conceptual HVAC design.

You might also like