Professional Documents
Culture Documents
Operation Manual 3500 60 and 61 Temperat
Operation Manual 3500 60 and 61 Temperat
#
! "! #
3& 4 % 5 3& 4 % $ )$ #$ )$ # 5
36 -5 7 / " 5. 8 &5 6 ) 56 &' 1 56 5 6/ &
6 ) 5 6/ &# ' 5- ) 3'' ' 5 9 " 5 9 "8 &5 9 : #4 5
9 : #3 5 )/ & " ) 3 ; &$ /5 /" <05 = / ∅5
= / $ ' 5 &$ . " ) 5 &$ 8 /5 & >5 6 5
5 4 % 5 6 5 % & ) 5 > 3.5 : 5
-73 5 1 ' 5 1/' 5 #64>& >5 # &+ * ")/5 # 8 &5 # > 5# '
6 ) 5 # " ' 5 # 8 &5 <3 5 < 5>
) 3"" '' ! 7 / +* / 1 $
" 5 " 013 ?@
013
# $ ? !
?
9 : ?
4 *** ) )/ & /
! "!
! # $ ! "!
%&'' ( ) # * ( ( !
+, ! - . //0' 1
, " '& % ' " " '/'
, " '& % # " " " # '/'
4 ' & '% ' ) " ) $ " % &+
6 * )' % & ' ' " $ ) 1/'
%&'' ( ) # * ! 2 3!
+, ! - . 0' 1
, " '% ' ) $ &+ . %) ' %* % ' ) $ )
' % $ "
, " '% ' ) $ ' ' %/ $ $ " '
$ " ) /
%&'' ( ) ! 4 $ ) $ ( !
+, ! - .5 &50' 1
4 ' & '% & & ) $ &+ $ ' &
& " '% %/ ) & &
& " '% ' )' % *
, " '% ' )6 3&A ' 66- 1 " 6' /1 % *
& " ' "" ) '% ' ) * + " & & '
%&'' 6 7 8 , * +, ! - %'9%.0' 1
6 ) ' $ '$ * $ * $ + & '" &
8' ' % & " "* )
! "! #
, ! 8 )
. ' ' " $ " '5 *$ ' ' % $ - 0 5 *$
& % $ " & $ " % ' % $ " % ' ' 5 ' /
' ' % $ "' ' % $ " & ' 5% 5& 5
'' & ) &/ $ ' & % " & '$ " ' ' % $ '
% / & % " 5' 5 & * 7 / " 88.
' ' ' % $ "' ' % $ " & $ " % ' % $ " % '
'
Contact Information .................................................................................................ii
Figures............................................................................................... viii
Tables .................................................................................................. ix
2. General Information.................................................................... 3
2.1 Triple Modular Redundant (TMR) Description........................................................... 4
2.2 Available Data .......................................................................................................... 4
2.2.1 Statuses................................................................................................................ 4
2.2.2 Proportional Values............................................................................................... 6
2.3 LED Descriptions...................................................................................................... 7
3. Configuration Information.......................................................... 8
3.1 Hardware Considerations ......................................................................................... 8
3.2 Monitor Options ........................................................................................................ 8
3.3 Channel Options..................................................................................................... 10
3.3.1 Temperature Channel Configuration Considerations........................................... 10
3.3.2 Group Summary ................................................................................................. 11
3.3.3 Range Setup....................................................................................................... 12
3.3.4 Temperature Channel Configuration Options ...................................................... 12
3.4 Available Setpoints ................................................................................................. 19
3.5 Software Switches .................................................................................................. 23
3.5.1 Module Switches................................................................................................. 23
3.5.2 Channel Switches ............................................................................................... 25
5. Maintenance .............................................................................. 47
5.1 Verifying a 3500 Rack - Temperature Monitor .........................................................47
5.1.1 Choosing a Maintenance Interval ........................................................................47
5.1.2 Required Test Equipment....................................................................................48
5.1.3 Typical Verification Setup ....................................................................................48
5.1.4 Using the Rack Configuration Software ...............................................................49
5.1.5 Verifying RTD Temperature Channels.................................................................51
5.1.6 Verifying Thermocouple Temperature Channels..................................................57
5.1.7 Verify Recorder Outputs (3500/61) ......................................................................66
5.1.8 If a Channel Fails a Verification Test ...................................................................67
5.2 Performing Firmware Upgrades...............................................................................68
6. Troubleshooting........................................................................ 70
6.1 Self-test...................................................................................................................70
6.2 LED Indication of Monitor Status .............................................................................71
6.3 System Event List Messages ..................................................................................73
6.4 Alarm Event List Messages .................................................................................... 86
6.5 Advanced Diagnostics ............................................................................................ 87
8. Specifications ............................................................................. 1
! "! #
Figures
Figure 2-1 Front and Rear View............................................................................................3
Figure 2-2 LED’s...................................................................................................................7
Figure 3-3 Transducer Orientation ......................................................................................17
Figure 4-1 RTD/TC Temperature I/O Module (3500/60, without recorders, internal
termination) .................................................................................................................27
Figure 4-2 RTD/TC Temperature I/O Module (3500/61, with recorders, Internal Termination)
....................................................................................................................................28
Figure 4-3 Isolated TC Temperature I/O Module (3500/60, without recorders, internal
termination) .................................................................................................................29
Figure 4-4 Isolated TC Temperature I/O Module (3500/61, with recorders, internal
termination) .................................................................................................................30
Figure 4-5 Barrier Temperature I/O Module (3500/60, without recorders) ...........................31
Figure 4-6 Barrier Temperature I/O Module (3500/61, with recorders) ................................32
Figure 4-7 Removing Terminal Blocks from an Internal Termination I/O module.................33
Figure 4-8 Connecting field wiring to an Internal Termination I/O module ...........................33
Figure 4-9 RTD/TC Temperature I/O Module (3500/60, without recorders, external
termination) .................................................................................................................34
Figure 4-10 RTD/TC Temperature I/O Module (3500/60, with recorders, external
termination) .................................................................................................................36
Figure 4-11 Isolated TC Temperature I/O Module (3500/60, without recorders, external
termination) .................................................................................................................37
Figure 4-12 Isolated TC Temperature I/O Module (3500/61, with recorders, external
termination) .................................................................................................................38
Figure 4-13 RTD/TC Temperature External Termination Block (terminal strip connectors) .39
Figure 4-14 RTD/TC Temperature External Termination Block (Euro style connectors).....40
Figure 4-15 Isolated TC Temperature External Termination Block (terminal strip
connectors) .................................................................................................................41
Figure 4-16 Isolated TC Temperature External Termination Block (Euro style connectors) 42
Figure 4-17 Recorder External Termination Block (terminal strip connectors)....................43
Figure 4-18 Recorder External Termination Block (Euro style connectors) ........................44
Figure 4-19 Transducer Signal to ET Block Cable, part number 134544-XXXX-XX ............45
Figure 4- 20 3500 Six-Channel Recorder Output to ET Block Cable, part number 134543-
XXXX-XX ....................................................................................................................46
Figure 5-1 Typical Verification Setup ..................................................................................48
Figure 5-2 Connect test equipment to input terminals .........................................................49
Figure 5-3 RTD Temperature Test Setup............................................................................52
Figure 5-4 Thermocouple Temperature Test Setup ............................................................59
Figure 5-5 Test equipment connection to verify recorder outputs.......................................66
Figure 5-6 Connection of multimeter ...................................................................................66
Tables
Table 2-1 Module Statuses................................................................................................... 6
Table 3-2 Full Scale Ranges by Thermocouple Type ......................................................... 14
Table 3-3 Full Scale Ranges by RTD Sensor Type ............................................................ 15
Table 3-4 Worst Case Minimum Alarm Time Delay ............................................................ 18
Table 3-5 Setpoints for Differential Temperature Channel Type ......................................... 21
Table 3-6 Setpoints for Temperature Channel Type ........................................................... 22
Table 3-7 Module Software Switches ................................................................................. 24
Table 3-8 Channel Software Switches................................................................................ 25
Table 4-1 I/O modules and supported transducers............................................................. 26
Table 4-2 Available versions of Temperature I/O modules ................................................. 26
Table 5-1 RTD Transducer OK Limits ................................................................................ 57
Table 5-2 Thermocouple Transducer OK Limit ................................................................... 65
Table 6-1 LED Indication of Monitor Status ........................................................................ 71
Table 6-2 Sample System Event ........................................................................................ 73
Table 6-3 System Event Class Value Descriptions............................................................. 73
Table 6-4 Alarm Event Message ........................................................................................ 87
Table 8-1 Maximum Thermocouple Wire Length by Gauge.................................................. 2
Table 8-2 CJC Error by I/O Module and Backplane type ...................................................... 2
:
# 4 !
#
<' / ' & $ " % ' '$ )" ) 4% '$ )" ) '
5% & * $ $ & "' & / 7 / "
. 4 )
. & "' & " & ' $ ' '& " ) *$ : ' "
& ' & &$ ) ' 6 ) & ' " / ' '$ " ) % $ "*
" $ * / # "" ) 5 ' $ % * ) & ' $
" )
Application Alert
• 6 " '&$ ) ' & & & / $ & & " 3 " '
& " ' $ * "' ( & $ & & " ' &" ) 1
'' & ' ' & " ) " "' " ) '5 & " &
' &'5 " ' '
• ' ' ) " "* $ ' ) " )' ' &$ '
< ' ! % $ " ) ) "& & "
• # ' "' & & "' & & /& " & )' %
• 0' : & " )" /* $ $ " / '' $ B
"' / $ && %' & &$ ) ' /' % &
% 8 )
. ' " $ " ' $ & % " & $ " % ' %
$ " % ' ' ' / ' ' % "' ' % " & ' 5
% 5& 5 '' & ) &/ $ ' & % " & '$ " ' '
% $ ' %0 "1 '' *'5 0 "1 '
% " *'5 / & * 7 / " ' ' '
% "' ' % " & $ " % ' % $ " % ' '
! "! #
! ! " & , 4 %
. 3
#$ ! ! # ' ' : &$ " ') "%
' & ' 4 && ' % $ '' &
" & ' #6 $ & ' #. " ' ' $ ' ' "
. ( ! # ! + (#1 8
C$ ' " # & %) 5 ! ! ' "& ' " )4
" ' ' ' " "( & &$ $ ) ' % $ C$ ' "
$'& %) 5 * / ' % ) / " ' &&
" "' ) % '
#$ % ' % ) && ' $ # / " C $ $' )5 $
' & " '% $ $ " ' & " %
$ " #* " ' ' ) % $ / '" % $
D / " " & %
% $' )
#$ ' & " / % ) ' % " ' E. ' E ) C $ $' / %
)5 $ ' % &$ " $ ) & "
* $ &$ $ 4% $ % " " %% ' % $ % $ $
" ' $ ) / ' &% " 5 $ " * "" / $
1/' - ' . %) & ' ) /' ). ' "B
. ' $ &+ . % ) 1 %*
9 # & '5 $ # A ' $ " "
'" & ' &$ ' & $ &$ #$ % &$
'" & ' & & " ' # '
.. - 8
#$ # '
& '' " ' $
. & ', * / " 56' /4 % & " 5 " $ $ '
' %* $ &+ 4 % & " #$ # ' '
$ " " &$ ' ' '
.. ) !
#$ " ' $ % * )' ' ' #$ ' ' & " '& ' $
' ' ' " *$ $ /& % "
! ! " & , 4 %
.. ( ! ) !
OK
This indicates if the module is functioning correctly. A not OK status is returned under any
of the following conditions:
• Module Hardware Failure
• Node Voltage Failure
• Configuration Failure
• Transducer Failure
• Slot ID Failure
• Channel not OK
If the Module OK status goes not OK, then the system OK Relay on the Rack Interface I/O
Module will be driven not OK.
Alert/Alarm 1
This indicates whether the module has entered Alert/Alarm 1. A module will enter the
Alert/Alarm 1 state when the process proportional value provided by the module exceeds its
configured Alert/Alarm 1 setpoint.
Danger/Alarm 2
This indicates whether the module has entered Danger/Alarm 2. A module will enter the
Danger/Alarm 2 state when the process proportional value provided by the module exceeds
its configured Danger/Alarm 2 setpoint.
Bypass
This indicates when the module has bypassed alarming the proportional value of a channel.
When a channel bypass status is set, this module bypass status will also be set.
Configuration Fault
This indicates if the monitor configuration is valid.
.. . ) !
OK
This indicates whether or not the associated module channel has detected a fault. A not
OK status is returned under any of the following conditions:
• Transducer Failure
• Channel Specific Hardware Failure
Alert/Alarm 1
This indicates whether the associated module channel has entered Alert/Alarm 1. A
channel will enter the Alert/Alarm 1 state when any proportional value provided by the
channel exceeds its configured Alert/Alarm 1 setpoint.
Danger/Alarm 2
This indicates whether the associated module channel has entered Danger/Alarm 2. A
channel will enter the Danger/Alarm 2 state when any proportional value provided by the
channel exceeds its configured Danger/Alarm 2 setpoint.
Bypass
This indicates that the channel has bypassed alarming for one or more of its proportional
values. A channel bypass status may result from the following conditions:
• Temperature Monitor has never been configured
• Temperature Monitor is in configuration mode
, 4 % ! ! " &
• Temperature Channel has an invalid configuration
• Temperature Monitor is in power up self-test
• Fatal error found during self-test
• Alarming is bypassed via a software switch
• Rack Alarm Inhibit is enabled.
Off
This indicates whether the channel has been turned off. The monitor channels may be
turned off (inactivated) using the Rack Configuration Software.
Module OK X X
Module Alert/Alarm 1 X X
Module Danger/Alarm 2 X X
Module Bypass X
Channel OK X X X
Channel Alert/Alarm 1 X X X
Channel Danger/Alarm 2 X X X
Channel Bypass X X X
Channel Off X X
Table 4-1 Module Statuses
... , : !
' & '' ' ' ' " $ &$
#$ # ' & '' " '
!
! ! " & , 4 %
.% ;8 8
#$ 8-6' $ % % $ # "& $ )
' ' % $ " ' '$ * $ % * )%) % 1 & ! %
1. OK: Indicates that the Temperature Monitor and the Temperature I/O Module are
operating correctly.
2. TX/RX: Flashes at the rate that messages are received and transmitted
3. BYPASS: Indicates that some of the monitor functions are temporarily suppressed.
. %) 4 % ! ! " &
% !
#$ ! ! # ' $ "& %)
/ #$ ' ' & '' $ '1 & 5 .$
'1 & 53 1 '1 & 5 "1 % * 1* &$ '
1 & % $ #
# & %) $ # 5 ' $'' & ) $ $
& %) % " $ ' $ &+ . % ) 1 %* '
' "" * " $ & %) $ " #$ )
1/' &+ . % ) "0 ', " @ '$ *'
$ * ' " $ &+ . % ) 1 %*
% 4 $
#$ ' ' $ &+ "% 5& )% % )$ 1
' ' "% * ' ' 1 ' ' "% % & " 5
$ $ # ' 6 4 % & $ &+ 4 % &
" 1 ' $ )$ & "F ) ' 'G #$ ! !
# & ' " / % $ ) ' '
* 5 % $ &+ 4 % & " "6 ) 4
' " % & 664>5 #64> #6> 5 % $ $ %
' ' & ' $' / & / & %)
%. ( <
#$ ' ' & " '& ' $ ' $ #
& %) '& ' " " '& '' ' & %) & '" '
?
! ! " & . %) 4 %
Reference Information
@
. %) 4 % ! ! " &
Isolated TC Temperature I/O Module (External Termination)
This I/O module is explained in sections 4.3.3 and 4.3.4.
Barrier Temperature I/O Module
This I/O module is explained in section 4.2.
Channel Type
Two channel types are available on the 3500/60-/61 Temperature Monitor
Temperature channel type
This channel type offers a simple configuration where only basic temperature
measurements are required.
Differential Temperature channel type
This channel type has additional options for composite temperature measurements.
Line Noise Rejection
This field allows selection of 50Hz or 60 Hz line noise rejection. Depending on the system
power source being used, this option should be selected to match with the line frequency.
If the incorrect option is set, the line noise from the system power source may couple into
the input signals.
Group Summary (Differential Temperature Only)
Select this button to bring up a read only summary showing how all the composite and
differential proportional values are configured.
Recorder Setup (3500/61 Only)
This button allows each recorder to be configured for any channel and proportional value.
Range Setup (Differential Temperature Only)
This button shows all of the channels range and clamp values. Optionally it can display this
information for all the channels that make up the composite proportional value for a
particular channel.
Copy
Use this button to copy one channels complete configuration to any or all of the other
channels.
%% <
#$ ' ' & " '& '' ' $ . %) . '" ' " $ &+
. %) 1 %* '& ' '' & "* $ $ # .$ /
%% ! !
. '" $ % * ) ' % & %) ) # .$ 2
! ! " & . %) 4 %
• #$ % '& ' * "" " $ '" & /
• 0 ' % ' $ & ' $
&$ $ ' % $ " &
• 1 ' / / ' &$ ' $ &
• C$ % '& ) ' " % "5 "( ' $ ' ' '' & "* $
$ &$
% % . 3 ! )!
#$ ' ' & " '& ' $ " / '& $ ) ' $ ) ' /
View Mode
Show all
Lists all configured differential and composite proportional values.
Composite only
List only configured composite proportional values
Differential only
List only configured differential proportional values
Enabled only
. %) 4 % ! ! " &
List all calculated proportional values that are configured to be active.
%%% # ) !
View Mode
Show All
displays and allows modification of all the full scale and clamp values for every enabled
proportional value.
Only Channel(s) in Grouping for [Channel #]
displays and allows modification of all the full scale and clamp values for all the channels
that are a part of the composite proportional value for the chosen channel.
%%9 ! ! <
#$ ' ' & " '& ' $ ' $ # .$
& %) '&
! ! " & . %) 4 %
%%9 #
#$ ' % "' & % $ "& ' *$ &$ &$ /
& %) )
Channel
The number of the channel being configured (1 through 6).
Slot
The location of the monitor in the 3500 rack (2 through 15).
Rack Type
The type of Rack Interface Module installed in the rack (Standard or TMR).
%%9. ; - +, : ! 1
The Enable field contains the units, full-scale range, and clamp value for the enabled
Temperature proportional value. Direct is always enabled, composite and differential can
be enabled by configuring for a channel type of “Differential Temperature and checking the
enable boxes next to the desired proportional value.
Range Options
The Direct full-scale ranges are listed below in the following tables
. %) 4 % ! ! " &
°C °F
100 ohm Platinum -50 to 2001 -122 to 2001 -50 to 700° C1
(0.00392)
-50 to 1001 -122 to 200 (-122 to 1292° F) 1
-200 to 200 -100 to 100
-100 to 100 0 to 200 -200 to 700° C
0 to 100 0 to 300 (-328 to 1292° F)
0 to 150 0 to 400
0 to 200 0 to 500
0 to 250 0 to 1000
0 to 500 Custom*
Custom*
100 ohm Platinum -50 to 2001 -122 to 2001 -50 to 850° C1
(0.00385)
-50 to 1001 -122 to 200 (-122 to 1562° F) 1
-200 to 200 -100 to 100
-100 to 100 0 to 200 -200 to 850° C
0 to 100 0 to 300 (-328 to 1562° F)
0 to 150 0 to 400
0 to 200 0 to 500
0 to 250 0 to 1000
0 to 500 0 to 1500
0 to 750 Custom*
Custom*
10 ohm Copper -50 to 1001 -122 to 1001 -50 to 260° C1
-100 to 100 -100 to 100 (-122 to 500° F) 1
0 to 100 0 to 200
0 to 150 0 to 300 -100 to 260° C
0 to 200 0 to 400 (-148 to 500° F)
0 to 250 0 to 500
Custom* Custom*
120 ohm Nickel 0 to 100 0 to 200 -80 to 260° C
0 to 150 0 to 300 (-112 to 500° F)
0 to 200 0 to 400
0 to 250 0 to 500
Custom* Custom*
See section 4 I/O Module Descriptions for a list of which transducers are supported on each I/O module.
Not all transducers are supported on every I/O module.
1 - With external barriers
%%9% <= (
' $ = " ) " $ * $ &$ =' ' ' %% & "
*$ $ &$ ) ' = " $ ' =' #$ ' ' '
%% & ' $ ' % $ &+ = / $ &+ 4 % & "
Latching
If a channel is configured for Latching OK, once the channel has gone not OK the status
stays not OK until a reset is issued. Reset a latched not OK by using one of the following
methods:
• Pushing the reset switch on the front of the Rack Interface Module
• Closing the reset contact on the back of the Rack Interface Module
• Selecting the Rack Reset command in the Rack Configuration or Operator Display
Software
• Issuing the reset command through the Communication Gateway Module.
• Issuing the reset command through the Display Interface Module.
Nonlatching
The channel OK status will return to an OK state once the not OK condition is removed.
%%99 (# + (# ! 1
C$ & %) " ' % # ) "" ' 1
' & # " " " # 6 '&
Comparison
The enabled proportional value of the TMR monitor group that is used to determine how far
apart the values of the three monitors can be from each other before an entry is added to
the System Event List.
% Comparison
!
! ! " & . %) 4 %
The highest allowed percent difference between the middle value of the three monitors in a
TMR group and the individual values of each monitor.
%%9& ! )
0' $ ' ' & *$ &$ '" & * ' "% $ ) &$ 3
&$ & ' ' " ' & - < '
%%9/
1 & -: , & 4' % $ : '& & "
* $ " $ '" & 7 ' ' " ' & $
% )/ $ & % * $ H " ' C$ ' & ) : '5
$ * % '& ) ' °.% ' #6' 1 %
%
%%9 ! <
#$ ' ' $ & % $ '" & $ &$ #$ ) %
) ' ? " ) ' % )$ ' ' "% $ "
$ " " % $ &$ #$ ' % " ' % % ' ' /
" / % '" % ' ) % $ % * )%) 2
0°
90°
90°
left
right
Driver end
180°
! '
#* '
#$ '
9 ! '
9 '
1: ? '
Table 5-4 Worst Case Minimum Alarm Time Delay
%%9 (
Latching
Once an alarm is active it will remain active even after the proportional value drops below
the configured setpoint level. The channel will remain in alarm until reset by using one of
the following methods:
• Pressing the reset switch on the front of the Rack Interface Module
• Closing the reset contact on the Rack Interface I/O Module
?
! ! " & . %) 4 %
• Selecting the Rack Reset command in the Rack Configuration or Operator Display
Software
• Issuing the reset command through the Communication Gateway or Display
Interface Module.
Nonlatching
When an alarm is active, it will go inactive as soon as the proportional value drops below
the configured setpoint level.
%9 - )
#$ ' ' & ' &% ' $ ' '% $ # &$ 3
' ' $ * $ $ % '& ) $ " ' *$
&& ' #$ ) 1/' *' * 3 3 ' '
' " " ' ' &$ #
#$ &$ * " 3 3 "& % $ &$
:& "' ' ' ' #$ ) 1/' ' *'
* 6 ) 3 ' ' ' " " '
' % &$ # &$ #$ &$ * " 6 ) 3
"& % $ &$ :& "' ' ' '
Note
@
. %) 4 % ! ! " &
0' $ % * ) '& $ &+ . %) 1 %* "( ' 3 3
"6 ) 3 ' '
1 Over Temperature
Alert/Alarm 1
2 Under Temperature
Alert/Alarm 1
4 Under Composite
Alert/Alarm 1
5 Over Differential
Alert/Alarm 1
6 Under Differential
Alert/Alarm 1
7 Over Danger/Alarm 2
8 Under Danger/Alarm 2
9 Over Danger/Alarm 2
10 Under Danger/Alarm 2
Table 5-5 Setpoints for Differential Temperature Channel Type
1 Over Alert/Alarm 1
2 Under Alert/Alarm 1
3 Over Danger/Alarm 2
4 Under Danger/Alarm 2
. %) 4 % ! ! " &
Table 5-6 Setpoints for Temperature Channel Type
%& ) $ )$
#$ # ' ' * " ' %* '* &$ ' " %
&$ ' %* '* &$ ' #$ ' '* &$ ' / / / ''5 $ 5
+ " &$ % & ' 1 $ ' '* &$ ' $ ) $
)$ '& " $ 2 $ '& % $ &+
. %) 1 %*
%& ( ! )$
Configuration Mode
This switch allows the monitor to be configured. To configure the monitor, enable ( ) this
switch and set the key switch on the front of the Rack Interface Module in the PROGRAM
position. When downloading a configuration from the Rack Configuration Software, this
switch will automatically be enabled and disabled by the Rack Configuration Software. If
the connection to the rack is lost during the configuration process, use this switch to remove
the module from Configuration Mode.
. %) 4 % ! ! " &
Monitor Alarm Bypass
When this switch is enabled, the monitor does not perform alarming functions. All
proportional values are still provided.
1 Configuration Mode
1 Alert Bypass
2 Danger Bypass
4 Bypass
9 >< ( ! 8
#$ # 4 " & ' "& " '') '% $
'' & " & ' #6 $ & #. '" & ' #$ '
') ' $ ' $ # % "" ') & '' )
#$ ! # " ' $ ' ' $ ! * $
$ "" % " ) 3 & " % &$ &$ 4
" ' A "% &$ # 4 ' $ 4 " $ "
$ &+ &+5 $
7 +$ " &+ & % ) #$ ! "! # ' '
$ % * )4 " / '2
Thermocouple 3-wire RTD 4-wire RTD
RTD/TC Temperature I/O Module X X X
Isolated TC Temperature I/O Module X
Barrier Temperature I/O Module X X
#$ ' ' & " '& ' $ & & '% $ ' " '5 ' ' *$ &$ & ' ' 5
" '$ *' $ ' % $ & ' #$ 9 "C )6 ) &+ )
'$ *' $ * & & '" & ' " & " ' $
4 " $ -: # 7 &+
9 >< ( !
4 # 4
" ' A / * &$ '" & "
& " $ 4 " " & / #$ ' ' & " &' $ 4 #
4 " ' " '$ *' $ * & & $ * ' $ - 1/ & &
!
! ! " & 4 " 6 '& '
3. Connect the wire from the transducers associated with Channel 1, 2, and 3 to the I/O
module.
4. Connect the wire from the transducers associated with Channel 4, 5, and 6 to the I/O
module.
5. Connect each channel of output recorders to the I/O module.
?
! ! " & 4 " 6 '& '
9 % ! >< ( ! +%&''>/'? $ ! ?
1
#$ ' 4 " && ' $ & ' #$ ' $'4 " $
$ '/' ) " ' " &$ &$ ' #$ ' 4
" & ' "* $) " " $ & '
Figure 6-3 Isolated TC Temperature I/O Module (3500/60, without recorders, internal
termination)
6. Connect the wire from the transducers associated with Channel 1, 2, and 3 to the I/O
module.
7. Connect the wire from the transducers associated with Channel 4, 5, and 6 to the I/O
module.
@
4 " 6 '& ' ! ! " &
9 9 ! >< ( ! +%&''>/ ? $ ?
1
#$ ' 4 " && ' $ & ' #$ ' $'4 " $
$ '/' ) " ' " &$ &$ ' #$ ' 4
1. Connect the wire from the transducers associated with Channel 1, 2, and 3 to the I/O
module.
2. Connect the wire from the transducers associated with Channel 4, 5, and 6 to the I/O
module.
3. Connect each channel of output recorders to the I/O module.
! ! " & 4 " 6 '& '
9. ! >< ( !
#$ ' 4 " " ' ' : &$ ' % '& /' % ') & " )%
$ #. " * #6 '" & ' 3 - $ ) " ' A "%
'/' ' $ ' 4 7 4 " ' " '& /' % $
& & % '& /' % & ' % $ &+ 4 ' "
& % '/' A ' *$ ' )4 7 4
" '
9. ! >< ( ! +%&''>/'? $ ! 1
9.% 7 ;! )
# &+ % ' ' 5 ' $ '& *' &$ ) $
&+ $ ' 5) $ &+ % / " 6 $ &+
/ '* ' & ' $'& " ' " ) $ * ' & &
Figure 6-7 Removing Terminal Blocks from an Internal Termination I/O module
9 % ;@ >< ( !
-: # 4 " ' / ' %/ $ * ) $ 4 " '
&+ / ' ) & " & & ' $ ') ' "% $
' ' $ 4 " - &$ % $ ' 4 " ' A ' :
&+ ' & -: # 7 &+' " & ' &
-: # . '
1. Connect the I/O module to the External Termination Block using cable 134544-XXXX-
XX.
4 " 6 '& ' ! ! " &
1. Connect the I/O module to the External Termination Block using cable 134544-XXXX-
XX.
2. Connect the I/O module to the Recorder External Termination Block using cable
134543-XXXX -XX.
!
! ! " & 4 " 6 '& '
Figure 6-11 Isolated TC Temperature I/O Module (3500/60, without recorders, external
termination)
1. Connect the I/O module to the External Termination Block using cable 134544-XXX-XX.
4 " 6 '& ' ! ! " &
Figure 6-12 Isolated TC Temperature I/O Module (3500/61, with recorders, external
termination)
1. Connect the I/O module to the External Termination Block using cable 134544-XXXX-
XX.
2. Connect the I/O module to the Recorder External Termination Block using cable
134543-XXXX-XX.
?
! ! " & 4 " 6 '& '
9 9 ;@ *
#$ $ / ' % -: # 7 &+' ' " * $ # 4
" $ #6 #.5 #. 4' "5 " & " -: # 7 &+'
- &$ / & '* $ $ ' - '/ & & '% %
' : " %% -: # 7 &+'
99 # 8> ! ;@ *+
1
@
4 " 6 '& ' ! ! " &
9 9 . # 8> ! ;@ * +;!
1
Figure 6-14 RTD/TC Temperature External Termination Block (Euro style connectors)
1. Connect the wire from the transducers associated with Channel 1, 2, 3, 4, 5, and 6 to the
External Termination Block.
2. Connect the Transducer I/O module to the Transducer’s External Termination Block
using cable 134544-XXXX-XX.
3. Channel 1, Channel 2, and Channel 3
4. Channel 4, Channel 5, and Channel 6
! ! " & 4 " 6 '& '
99% ! ;@ *+
1
1. Connect the wire form the transducers associated with Channel 1,2,3,4,5 and 6 to the
External Termination Block.
2. Connect the Transducer I/O module to the Transducer’s External Termination Block
using cable 134544-XXXX-XX.
3. Channel 1, Channel 2, and Channel 3
4. Channel 4, Channel 5, and Channel 6
4 " 6 '& ' ! ! " &
999 ! ;@ * +;!
1
99& # ;@ *+ 1
99/ # ;@ * +;! 1
9 & ;@ -
!
! ! " & &
& (
#$ "'
"& ' '" % " '& " $
% " ) &+ & ' ' ' % ' ) " &$ ' %/ $
$ / )& & / " ' $ )& & / '$ "
& "* $ '
C$ % " /5 $ ' " / "% $ &+ *$
* ' " $ &+ % $ &+ 4 ' " &
@ !! % $ & "
#$ ' ' & '$ *' $ * %/ $ % &$ ' #
' & "$ * ) " % * ' &
& : %&'' # *0 ! (
#$ ) 1/' ' $ )$ &' ' $ A '
& #$ % & ' % &$ '5 $ * 5 ' % "
) ' 3 &$ & 5* & " $ / ' $
& " ' $'' & %/ $ % & &$ ' $
4 ' / & '' / %/ $ ' " && &/ % &$
' $ &
& (
0' $ % * ) &$ &$ ' & 2
& ! ! " &
1 * $ % / " $ '$ $ % / % $
% * )& " ' /2
#$ " &$ ' & '' % " ' & &
#$ &+ ' ) $ '$ ' &$ ' :
5 $ )$ $ " /5 & ' ' $
& % : ) !
#$ % * )%) '$ *' $ / & ' ' % %/ ) #
#$ ' A ' ' " ' $ '" & ' ) " $
& ' ' " ' $ % $ &+
# '" & ' & & & " &+ / % * /' 6 " )
$ * ) % $ 4 " %/ 5& & $ ' A
$ ' ) % $ % * ) $ "'2
Figure 7-2 Connect test equipment to input terminals
& 9 2 # * ! ) $
#$ & $ ' % $ ' ' ' ' $ &+ . % )
1 %* "' / % $ &+ " ' & )
' $ &+ # % $ ' & " ' $'' & / '
% * $ $ % * )% ' % $ &+ . % ) 1 %*
0 "5 6 * "5 "1 & %) % '
- ""' &$ ' " '
7/ '' &$ ' " '
6' / $ < %& '&
#$ &+ . % ) "# ' 0 ', " @ : '
$ * % $ ' '
@
& ! ! " &
Note
It is important to save the original rack configuration before doing any
maintenance and/or troubleshooting procedures. It may be necessary
during these procedures to change some configuration settings that
must be restored to their original values at the conclusion of the
procedures. At that time the original configuration should be
downloaded to the rack.
& & : # 8 !
#$ % * )' & ' " '& $ * ' '5 %/ &$ '5 " ' =
' % &$ ' & % ) " ' #6 # #$ ' "
' ' % " / / ) $ ') " ' )
$ $ & & ' ' " $ < %& '& $ '
&
CAUTION
High voltage present. Contact could cause
shock, burns, or death.
Application Alert
Application Alert
& &.
1 $ ') * $ " & " '' # ' $ ' /
/ ) $ % $ ' A " ' ) $ ' ' $
< %& '& $ ' & 4 ' / & '' / ' $ '
' $ & %) " " ) ' " # ' ' "( ' $ '
') 2
9. Exceed over Alert/Alarm 1 and Danger/Alarm 2 setpoints,
! ! " & &
10. Drop below under Alert/Alarm 1 and Danger/Alarm 2 setpoints,
11. Produce a non-alarm condition.
3"( ' $ ) & ' & ' &$ $ $ ') ( ' :& "'
$ 3 3 ' C % ' & "' % $
" / : ' " %/ $ $ ) $ "& % 6 &
&$ ) ' & % ) / * " $ $ . < 9 "
"& '
! '' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $ $
) $ "& % 6 & '/ * " $ $ . <
9 "' "& '
3"( ' $ ) & '
& ' &$ $ $ ') ( ' :& "'
$ 6 3 ) ' C % ' & "' % $
" / : ' " %/ $ $ ) $ "& % 6 &
&$ ) ' & % / * " " $ $ . < 9 "
"& '
? '' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $ $
) $ "& % 6 & ' " " $ $ . < 9 "
"& '
@ 3"( ' $ ) & ' & ' &$ $ $ ') "' *
$ 3 ' ' 4% $ &$ ) ' & % ) "5
' $ $ ) $ "& % 6 & &$ ) '& ) "
$ $ . < 9 "& ' "& % ' '' $
-1-# '* &$ $ &+ 4 % & " 4 ' &$ ) '
Under Setpoints
& ! ! " &
' ' $ )$ @ ' $ 0 " 3 3 "0 "
6 ) 3 ' ' / "( ' ) $ ) & ' & "
* $ 0 " 3 ' '
4% / & %/ /& %) " 5 &$ &+ $ & % ) "
' ' 4% $ ' " ' / % ' / $
% $' ' 5) 1 & ? 4% .$ 9 ' < %& # '
6 '& & $ ' A " & & % "* ) $
&$ ' $ # 4 " < %/ $ $ = 8-6
& ' '' $ -1-# '* &$ $ &+ 4 % & " 4
' $ = 8-6
' ' $ )$ % & %) " &$ '
& &% : : ! A# 8 !
#$ ) &$ % ' ) $ ' ' ' ' $
# ') * $ ) & ' & # %/ $ &$
' / / ) $ % $ ' A " ' ) $ $
& & ' ' " $ < %& '& $ ' &
Note
Note
All other channels in the rack must be OK or bypassed for the OK relay
to be energized.
# ' = ' ' " #6 ' ) '' & " "( '
$ 0 = " * $ 8 * = #$ ' ' ' & *
& ' =& " " $ = / &$ ) ' " ) H #$
0 "8 * = ' "' / " $ < %& '& $ '
&
6 '& & % "* )% $ &$ ' $ #
4 "
. & ' A " ' %* ' " '& " 1 &
# ' -A "1 % * 1 #6 #
7/ '' $ & %) " &$ '
Adjust the decade box to a value in the middle of the OK Limits listed in 1 - With
external barriers selected.
Adjust the decade resistor to some value in the middle of the OK limits as listed in
1 - With external barriers selected.
!
! ! " & &
4% / & %/ /& %) " = 5' ' & ? 4% .$
9 ' < %& # '
' ' $ )$ % & %) " &$ '
! $ / '' '* &$ % & %) " &$ ' &+ ' )
' )
RTD Type Lower OK Limit Upper OK Limit
(Ohms) (Degrees) (Ohms) (Degrees)
& / : ! !
#$ % * )' & ' " '& $ * ' '5 %/ &$ '5 " ' =
' % &$ ' & % ) " ' #$ & # #$ '
" ' ' % " / / ) $ ') "
' ) $ $ & & ' ' " $ < %& '& $
' &
& / ;"! ) $ ) ! 0 ! !
Use the following test equipment and software setup for all the verification procedures (Test Alarms,
Verify Channels, and Test OK Limits).
CAUTION
High voltage present. Contact could cause
shock, burns, or death.
Do not touch exposed wires or terminals.
& ! ! " &
Application Alert
Application Alert
?
! ! " & &
@
& ! ! " &
$ &+ . % ) 1 %* $ ' & .$ ' < %&
% $ 0 ' " &$ ' $ 1 " .$
$ & &+ $ < %/
& /. 0 !
1 $ ') * $ &' ' & # ' $
' / $ % $ &' ' & " ' $
< %& '& $ ' & 4 ' / & '' / ' $ '
' $ & %) " " ) ' " 3"( ' $ ' ') 2
12. Exceed the over Alert/Alarm 1 and Danger/Alarm 2 Setpoints
13. Drop below any under Alert/Alarm 1 and Danger/Alarm 2 Setpoints
14. Produce a non-alarm condition
3"( ' $ &' ' & ' &$ $ $ ' ) ( ' :& "'
$ 3 3 ' C % ' & "' % $
" / : ' " %/ $ $ ) $ "&
&$ ) ' & % ) / * " $ $ . < 9 "
"& ' 3
! '' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $
$ ) $ "& '/ * " $ $ . < 9 "
' "& ' 3
3"( ' $ &' ' & ' &$ $ $ ' ) ( ' :& "'
$ 6 ) 3 ' C % ' & "' %
$ " / : ' " %/ $ $ ) $ "&
&$ ) ' & % / * " " $ $ . < 9 "
"& ' 3
!
! ! " & &
? '' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $
$ ) $ "& % 6 & ' " " $ $ .
< 9 "' "& ' 3
@ 3"( ' $ &' ' & ' &$ $ $ ' ) "' * $
$ 3 ' ' 4% $ &$ ) ' & % ) "5
' $ $ ) $ "& &$ ) ' & ) " $
$ . < 9 "& ' "& % ' '' $
-1-# '* &$ $ &+ 4 % & " 4 ' &$ )
'
Under Setpoints
3"( ' $ &' ' & ' &$ $ $ ' ) ( ' :& "'
$ 0 " 3 3 ' C % ' & "' %
$ " / : ' " %/ $ $ ) $ "&
&$ ) ' & % ) / * " $ $ . < 9 "
"& ' 3
'' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $
$ ) $ "& '/ * " $ $ . < 9 "
' "& ' 3
3"( ' $ &' ' & ' &$ $ $ ' ) ( ' :& "'
$ 0 " 6 ) 3 ' C % ' & "' %
$ " / : ' " %/ $ $ ) $ "&
&$ ) ' & % / * " " $ $ . < 9 "
"& ' 3
'' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $
$ ) $ "& % 6 & ' " " $ $ .
< 9 "' "& ' 3
3"( ' $ &' ' & ' &$ $ $ ' ) "' * $
$ 3 ' ' 4% $ &$ ) ' & % ) "5
' $ $ ) $ "& &$ ) ' & ) " $
$ . < 9 "& ' "& % ' '' $
-1-# '* &$ $ &+ 4 % & " 4 ' &$ )
'
4% / & %/ /& %) " 5 &$ &+ $ & % ) "
' ' 4% $ ' " ' / % ' / $
% $' ' 5) ? 4% .$ 9 ' < %& # '
! 6 '& & $ ' A " & & $ % "* ) $
&$ ' $ # 4 " < %/ $ $ =
8-6 & ' " $ = / )H ' '' $ -1-# '* &$
$ &+ 4 % & " 4 ' $ = 8-6
' ' $ )$ ! % & %) " &$ '
!
& ! ! " &
& /% : : ! 0 ! !
1 $ # ') * $ &' ' & # %/
&$ ' / $ % $ ' A " ' $
< %& '& $ ' &
Note
!
! ! " & &
& " $ $ . < 7 : #$ ' ' $ .K.
$ % $ $ " % $ '
#$ ' " $ & " " ' & /
/ $ °. ?° 9 4% " ' /5 ' ' $ )$
< %/ $ $ ) $"' / " $ . < 7 : '* $
± ° . ± @° 9 % $ : & " 4% $ & " '
& % ) "5 % < %/ & " '% $ ' ' %/
$ & "
$ & " ' ' " % $ %&
'$ ' "
$ %& '& &$ ) &+ $ < 6' /
6 & <
! 4% $ " )" ' ' &%& '5 &$ &+ $ $ ')
'& & 4% $ ' " ' ' &%& ' % ' /
$ % $' ' 5) ? 4% .$ 9 ' < %& # '
6 '& & $ ' A " & & $ % "* ) $
&$ ' $ # 4 " < %/ $ $ =
8-6 & ' " $ = / )H ' '' $ -1-# '* &$
$ &+ 4 % & " 4 ' $ = 8-6
? ' ' $ )$ % & %) " &$ '
Example 1:
Some values for Type-J have the following resistance values:
Verification value 1: T1= 0° C Voltage = 0.000 mV
Verification value 2: T1= 90° C Voltage = 4.725 mV
Verification value 3: T1= 150° C Voltage = 8.008 mV
Example 2:
Assume that the CJC temperature measured in step 5 is 29 °C, that the monitor is
configured for the type-J TC and the desired test verification value is 100 °C.
For the CJC temperature of 29 °C the Thermocouple Table indicates this corresponds to a
CJC voltage (Vcjc) of 1.484 mV.
!
& ! ! " &
From the same table, the test temperature of 100° C corresponds to a voltage (Vtable) of
5.268 mV.
& /9 <= 0 !
Note
All other channels in the rack must be OK or bypassed for the OK relay
to be energized.
!
! ! " & &
@ '' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $ $
= 8-6 & ' &+ " $ $ = / ) H ' < %/ $ $
.$ =1 $ .$ 1 '' & "' =
, " /" & ' $ &' ' & ) $
= 8-6 ( ' ) ' %% * < %/ $ $ .$ =1
$ .$ 1 '' & "' = " $ $ = / "& '
= < %/ $ $ 8 * = ) "' / " $ < %&
'& ' A '' ) $ $ )
3"( ' $ &' ' & ' $ "" % $ =
' ' ' " # #$ & # '" & =8
'' $ -1-# '* &$ $ &+ 4 % & " 4 < %/ $ $
= 8-6 & ' &+ " $ $ = / ) H ' < %/ $ $
.$ =1 $ .$ 1 '' & "' =
6 '& & $ ' A " & & % "* ) $
&$ '
$ # 4 " < %/ $ $ = 8-6
& ' " $ $ = / )H ' '' $ -1-# '* &$ $
&+ 4 % & " 4 ' $ = 8-6
4% / & %/ /& %) " = 5) ? 4% .$ 9 '
< %& # '
' ' $ )$ % & %) " &$ '
! $ / '' '* &$ % & %) " &$ ' &+ ' )
' )
Thermocouple Transducer OK Limit
Thermocouple Lower OK Limit Upper OK Limit
(millivolts) (Degrees) (millivolts) (Degrees)
Type-J -0.896 -18° C 42.922 +760° C
Type-K -0.701 -18° C 54.807 +1370° C
Type-E -5.237 -100° C 76.358 +1000° C
Type-T -4.865 -160° C 20.869 +400° C
!
& ! ! " &
& : # <! ! +%&''>/ 1
0' $ % * ) ' A " & " %/ $ & " '%
$ ! #
Figure 7-5 Test equipment connection to verify recorder outputs
13. Connect test equipment here
14. Temperature I/O module (Internal Termination)
15. Recorder External Termination Block (Euro Style Connectors)
16. Recorder External Termination Block (Terminal Strip connectors)
!!
! ! " & &
17. To the Terminal Marked: COM
18. To the Terminal Marked: REC
& 5 6 :
C$ $ " ) & )& & "' * /' ' " A / &
) ' " ) % - & ' & 6 '&$ ) -16 3 * /' * * '
' "* + ) " "& " & * +' % &
1. 1 $ & %) % $ " ' ) $ &+ . %)
1 %*
2. & $ " * $ ' % $ ' ' & $
) 1/' &+ 4 ' " &
@ !!
!
& ! ! " &
3. $ % / " 7 / " %
4. 6 * " $ & %) % $ ' " ' ) $ &+
. %) 1 %*
5. < %/ $ % $ '
&. , 6 $ 2
&& ' /
/ & '' / ) " $ ) % * $ ' '$ "
* $ $ ! ! # #$ % * ) ' & ' " '&
$ * ) " $ :' )% * ' ) $ . %) ' %* #$
* " & %) " ' ) $ &+ . % ) ' %*
% $ ) '% * ) " " #$ % * ) ' & ' " % $
:' )% * ' ' $ )$ 4% $ % * ' ' * $
& & 7 / " &$ & ' % & "
CAUTION
!?
! ! " & &
!@
# '$ ) ! ! " &
/ !-
#$ ' ' & " '& '$ * '$ * $ $ #
$ 4 " / ' ) $ % " " / $ ' % '5 $
8-6'5 1/' - 8' 5 " $ 3 - 8'
/ ) 0
Application Alert
# % $ # ' % '2
. & & ) $ &+ . %) 1 %* $
&+ % " "
1 & 2 % $ '& % $ &+ . %) 1 %*
1 & ) ; >( ! ) 0 % $ 0 '
'' $ ( ! ) 0 $ 1/' - ' '&
1 & $ ' $ & ' $ # " '' $ <=
#$ * % % ' % ' " $ 1/' - '
'& * "' / " #$ ' * & $ ' ' % $ ' % '
! C ' & "' % $ " % ' % '
'' $ ; #$ 1/' - ' '& * " "
& " $ ' ' % $ ' % '
? < %/ % $ '' " $ ' % ' 4% $ % " $ ' % '5
% 1 & ! 1/' - 8' '' ) ' % " '& % $
%
! ! " & # '$ )
/. ;8 ( ) !
#$ % * ) '$ *' $ * ' $ 8-6' " ) ' "& & '
/% ) ; (
#$ &+ 4 % & " * & " '/' " '% &$
#$ ' ' & " '& ' $ 1/' - 8' '' ) ' $ "
/ $ #
-: 2
0 Severe/Fatal Event
1 Potential Problem Event
2 Typical logged Event
3 Reserved
Table 8-3 System Event Class Value Descriptions
Event Date
Event Time
The date and time the event occurred, uses the time as configured in the Rack Interface
Module
Event Specific
Provides additional information. For example if the event affects a single channel the
channel number will be noted here.
Slot
Indicates the module that the event is associated with, 0-15. If half-height module are
installed events for the module in the lower slot will be logged as 0L to 15L.
# '$ ) ! ! " &
#$ % * ) 1/' - 8' '' ) ' / & " $ ' / $
# " ' " & " . & $ '
7 / " %% & $ ' /
4% + "* $ ' L && '5 $ * ' )
CAUTION
Events marked with an asterisk (*) indicate the
monitor will stop alarming if this event occurs.
All unexpected instances of these events
should be investigated immediately.
Device Is Communicating
Event Number: 33
Event Classification: Potential Problem
Action: Check to see if one of the following components is faulty:
• Monitor Module
• Rack backplane
*Neuron Failure
Event Number: 34
Event Classification: Severe / Fatal Event
Action: Replace the Monitor Module immediately.
! ! " & # '$ )
Fail Main Board +5V-A (Fail Main Board +5V - upper Power Supply)
Event Number: 100
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
Pass Main Board +5V-A (Pass Main Board +5V - upper Power Supply)
Event Number: 101
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
Fail Main Board +5V-B (Fail Main Board +5V - lower Power Supply)
Event Number: 102
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the lower slot
Pass Main Board +5V-B (Pass Main Board +5V - lower Power Supply)
Event Number: 103
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
# '$ ) ! ! " &
• Monitor Module
• Power Supply installed in the lower slot
*Fail Main Board +5V-AB (Fail Main Board +5V - upper and lower Power
Supplies)
Event Number: 104
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Monitor Module will stop alarming.
Pass Main Board +5V-AB (Pass Main Board +5V - upper and lower Power
Supplies)
Event Number: 105
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
*Fail Main Board +5VA-AB (Fail Main Board Analog +5V - upper and lower
Power Supplies)
Event Number: 122
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Pass Main Board +5VA-AB (Pass Main Board Analog +5V - upper and lower
Power Supplies)
Event Number: 123
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
!
! ! " & # '$ )
• Power Supply installed in the lower slot
*Fail Main Board -5V-AB (Fail Main Board -5V - upper and lower Power
Supplies)
Event Number: 128
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Pass Main Board -5V-AB (Pass Main Board -5V - upper and lower Power
Supplies)
Event Number: 129
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Fail Main Board +VA-A (Fail Main Board +VA - upper Power Supply)
Event Number: 130
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
Pass Main Board +VA-A (Pass Main Board +VA - upper Power Supply)
Event Number: 131
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
Fail Main Board +VA-B (Fail Main Board +VA - lower Power Supply)
Event Number: 132
Event Classification: Potential Problem
# '$ ) ! ! " &
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the lower slot
Pass Main Board +VA-B (Pass Main Board +VA - lower Power Supply)
Event Number: 133
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the lower slot
*Fail Main Board +VA-AB (Fail Main Board +VA - upper and lower Power
Supplies)
Event Number: 134
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• I/O Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Pass Main Board +VA-AB (Pass Main Board +VA - upper and lower Power
Supplies)
Event Number: 135
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• I/O Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Fail Main Board -VA-A (Fail Main Board -VA - upper Power Supply)
Event Number: 136
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
?
! ! " & # '$ )
• Power Supply installed in the upper slot
Pass Main Board -VA-A (Pass Main Board -VA - upper Power Supply)
Event Number: 137
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the upper slot
Fail Main Board -VA-B (Fail Main Board -VA - lower Power Supply)
Event Number: 138
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the lower slot
Pass Main Board -VA-B (Pass Main Board -VA - lower Power Supply)
Event Number: 139
Event Classification: Potential Problem
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• Power Supply installed in the lower slot
*Fail Main Board -VA-AB (Fail Main Board -VA - upper and lower Power
Supplies)
Event Number: 140
Event Classification: Severe/Fatal Event
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• I/O Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Pass Main Board -VA-AB (Pass Main Board -VA - upper and lower Power
Supplies)
Event Number: 141
Event Classification: Severe/Fatal Event
@
# '$ ) ! ! " &
Action: Problem may be caused by power fluctuations from the source. If power
source is known to be working properly check the following:
• Monitor Module
• I/O Module
• Power Supply installed in the upper slot
• Power Supply installed in the lower slot
Device Configured
Event Number: 300
Event Classification: Typical Logged Event
Action: No action required.
*Configuration Failure
Event Number: 301
Event Classification: Potential Problem or Severe/Fatal Event
Action: Download a new configuration to the Monitor Module. If the problem still
exists, replace the Monitor Module immediately.
*Module Reboot
Event Number: 320
Event Classification: Typical Logged Event
Action: Verify the Module reboot was intentionally caused. If not replace the Monitor
Module.
?
# '$ ) ! ! " &
Event Classification: Typical Logged Event
Action: No action required.
?
! ! " & # '$ )
Event Classification: Typical logged event
Event Specific: Ch x
Action: No action required.
*Enabled CJ Verification
Event Number: 430
Event Classification: Typical logged event
Action: No action required.
Alarming has been inhibited by this action.
Disabled CJ Verification
Event Number: 431
Event Classification: Typical logged event
Action: No action required.
?
# '$ ) ! ! " &
• Monitor Module
• Rack backplane
Setpoint Updated
Event Number: 511
Event Classification: Typical logged event
Action: No action required.
?
! ! " & # '$ )
* ADC Failure
Event Number: 562
Event Classification: Severe/Fatal Event
Action: Replace the Monitor Module immediately.
?
# '$ ) ! ! " &
Event Number: 564
Event Classification: Potential Problem
Action: The CJC sensor failed in the past and has now recovered. All thermocouple
measurements were in error and monitoring for channels using thermocouples was
disabled for a period of time. RTD measurements were unaffected. Check to see if one of
the following components is faulty:
• I/O module (If Internal Termination is used)
• ET module (If external Termination is used)
• Main Module
/9 ; (
#$ % * )3 - 8' '' ) ' " / $ #
Entered Alert / Alarm 1 A proportional value in the channel has entered Alert /
Alarm 1 and changed the channel Alert / Alarm 1
status.
Left Alert / Alarm 1 A proportional value in the channel has left Alert / Alarm
1 and changed the channel Alert / Alarm 1 status.
?!
! ! " & # '$ )
A proportional value in the channel has entered Danger
/ Alarm 2 and changed the channel Danger / Alarm 2
Entered Danger / Alarm 2 status.
/& 8
4% / : % ' ) $ 5/ & & %
$ ' % $ % #$ % * ) ' & ' & " " & % $
% * ) '& '
Note
Although the recommendations in this section provide the most probable solutions,
other faults may exist. When troubleshooting a temperature monitor, carefully review
all possible problems.
?
# '$ ) ! ! " &
One or more channels are Not OK on the Internal Barrier I/O Module
Details:
Transducer for a particular channel(s) shown as Not OK (Wiring Open)
One of the Following Events Occur After Installing a Module in the Rack
Events:
Transducer Not OK (Wiring Shorted)
Transducer Not OK (Wiring Open)
Action:
Check the backplane for a bent or otherwise damaged pin.
All of the recorder output signals are incorrect or are not available
Action:
Replace main module.
- or -
Check that the connectors are correctly installed into the I/O module and External
Termination Block (if available) and inspect to make sure that the cable and field wiring are
not damaged.
??
! ! " & " )4 %
<
% < < 0 -
% >< ! ;@ * -
, ! - %9&99 0 0
A Cable Length
0005 5 feet (1.5 metres)
0007 7 feet (2.1 metres)
0010 10 feet (3 metres)
0025 25 feet (7.5 metres)
0050 50 feet (15 metres)
0100 100 feet (30.5 metres)
B Assembly Instructions
01 Not Assembled
02 Assembled
%. # <! ! # ;@ * -
Part number 134543 - AXX - BXX
A Cable Length
0005 5 feet (1.5 metres)
0007 7 feet (2.1 metres)
0010 10 feet (3 metres)
0025 25 feet (7.5 metres)
0050 50 feet (15 metres)
0100 100 feet (30.5 metres)
B Assembly Instructions
00 Not Assembled
01 Assembled
@
! ! " & " )4 %
9 ) A %&''>/' ! (
163179-01 3500/60 Temperature Monitor (without recorders)
133819-01 RTD/TC Temperature I/O Module (3500/60, without recorders, internal
termination)
*133827-01 RTD/TC Temperature I/O Module (3500/60, without recorders, external
termination)
*133916-01 RTD/TC Temperature External Termination Block (Euro style connectors)
*133908-01 RTD/TC Temperature External Termination Block (terminal strip connectors)
136711-01 Barrier Temperature I/O Module (3500/60, without recorders)
133835-01 Isolated TC Temperature I/O Module (3500/60, without recorders, internal
termination)
*133843-01 Isolated TC Temperature I/O Module (3500/60, without recorders, external
termination)
*133932-01 Isolated TC Temperature External Termination Block (Euro style connectors)
*133924-01 Isolated TC Temperature External Termination Block (terminal strip
connectors)
134542-01 Operation and Maintenance Manual
& ) A %&''>/ ! (
163179-02 3500/61Temperature Monitor (with recorders)
133819-02 RTD/TC Temperature I/O Module (3500/61, with recorders, internal
termination)
*133827-02 RTD/TC Temperature I/O Module (3500/61, with recorders, external
termination)
*133916-01 RTD/TC Temperature External Termination Block (Euro style connectors)
*133908-01 RTD/TC Temperature External Termination Block (terminal strip connectors)
133835-02 Isolated TC Temperature I/O Module (3500/61, with recorders, internal
termination)
*133843-02 Isolated TC Temperature I/O Module (3500/61, with Recorders, external
termination)
*133932-01 Isolated TC Temperature External Termination Block (Euro style connectors)
*133924-01 Isolated TC Temperature External Termination Block (terminal strip
connectors)
136711-02 Barrier Temperature I/O Module (3500/61, with recorders)
*133900-01 Recorder External Termination Block (Euro style connectors)
*133892-01 Recorder External Termination Block (terminal strip connectors)
134542-01 Operation and Maintenance Manual
B
When ordering I/O modules with External Terminations, the External Termination
Blocks and Cables must be ordered separately.
External Termination Blocks cannot be used with Internal Termination I/O Modules.
@
5 )
INPUTS
Signal Accepts combination from 1 to 6 either resistance
temperature detectors (RTD) or thermocouple (TC)
Isolation 500 Volts (Isolated TC Temperature I/O Module only)
OUTPUTS
OK LED Indicates when the 3500/60-/61 is operating properly.
TX/RX LED Indicates when the 3500/60-/61 is communicating with
other modules in the 3500 rack.
Bypass LED Indicates when an alarming function has been disabled
either by the user or by a fault condition
RTD Current Source 925 ± 15 µA @ 25°C (single supply for each 4-wire RTD
dual supply for each 3-wire RTD)
4-20mA Recorder Output +4 to +20 mA analog signal proportional to a selected
proportional value for that channel. Monitor operation is
unaffected by short circuits on recorder outputs. 0 to +12
Vdc range across load. Max. Load resistance 600 Ω.
Proportional Values Up to 3 active per channel, Options are Direct,
Composite (Group Average) and Differential.
RESOLUTION
Sensor Input 20 bit, Averaged and filtered to 16 bit
Recorder Output 16 bit
ACCURACY
1 &% " M °. °9
RTD Input Total error = Sensor error + Monitor error.
Thermocouple Input Total error = Sensor error + Monitor error + CJC error.
Sensor Error (10 ohm Cu RTD) 3°C without barriers, 18.5°C with Barrier Temperature
I/O Module, external barriers depends on model
" )4 % ! ! " &
Sensor Error (other RTD’s) Negligible without barriers or Barrier Temperature I/O
Module, external barriers depends on model
Sensor Error (Thermocouple) Follow this table to keep sensor error below 1 deg C
TC 100 ft 500 ft 1000 ft
J 22 AWG 14 AWG 12 AWG
K 20 AWG 12 AWG 10 AWG
E 24 AWG 16 AWG 14 AWG
T 20 AWG 12 AWG 10 AWG
CJC Error Use this table to determine the accuracy of the CJC
sensor. The error of the CJC is caused by proximity to
heat sources. To minimize error the CJC should be
located in a well-ventilated area.
3500/05 RTD/TC RTD/TC Isolated TC Isolated TC Barrier
Backplane Temperature Temperature Temperature Temperature Temperature
type I/O Module I/O Module I/O Module I/O Module I/O Module
(Internal (External (Internal (External
Termination) Termination) Termination) Termination)
Bulkhead 3° C 3° C 2° C 1° C 3° C
Rack
Standard 3° C 1° C 2° C 1° C 3° C
Rack
ALARMS
Alarm Setpoints Alarm 1 and Alarm 2 levels (setpoints) can be set for the
proportional values measured by the Temperature
Monitor. All alarm setpoints are set using software
configuration. Alarms are adjustable and can be set
from 0 to 100% of full-scale for each proportional value.
Alarm time Delays Alarm delays can be programmed using software, and
can be set as follows
ENVIRONMENTAL LIMITS
Operating Temperature
Barrier Temperature I/O Module 0° C to 65° C (32° F to 149° F)
Other I/O Modules -30° C to 65° C (-22° F to 149° F)
Storage Temperature -40° C to 85° C (-40° F to 185° F)
Humidity 95% non-condensing
ELECTROMAGNETIC COMPATIBILITY
HAZARDOUS APPROVALS
CSA-NRTL/C
Barrier Temperature I/O Module Class I, Division 1, Groups A through D
Class II, Division 1, Groups E, F, G
Class III
Other I/O Modules Class I, Division 2, Groups A through D
CENELEC
Barrier Temperature I/O Module [EEx ia] IIC
Other I/O Modules No Rating
BARRIER PARAMETERS
PHYSICAL
Main Board
Dimensions 241.3 mm x 24.4 mm x 241.8 mm
(9.50 in x 0.96 in x 9.52 in)
Weight 0.82 kg (1.8 lbs)
I/O Modules
Barrier Temperature I/O Module 241.3 mm x 24.4 mm x 163.1 mm
(9.50 in x 0.96 in x 6.42 in)
Other I/O Modules 241.3 mm x 24.4 mm x 99.1 mm
(9.50 in x 0.96 in x 3.90 in)
Weight
Barrier Temperature I/O Module 0.46 kg (1.01 lbs)
Other I/O Modules 0.20 kg (0.44 lbs)