(RSC AND SHALL BE USED IN MAIN SERVICE ENTRANCE.

6.

5.

15 mm DIA. ELECTRICAL TRADE SIZE, CONDUITS SHALL BE RIGID STEEL CONDUITS

1.
LICENSED REGISTERED ELECTRICAL ENGINEER.
ELECTRICAL WORKS SHALL BE UNDER THE IMMEDIATE SUPERVISION OF A DULY

EDITION OF THE P.E.C. THE RULES AND REGULATIONS OF THE LOCAL ENFORCING

GENERAL NOTES:
7.

CONDUIT SHALL BE USED WHERE REQUIRED MINIMUM SIZE FOR ALL CONDUITS SHALL BE
3.

2.
VOLTS LINE TO NEUTRAL, 60 HZ.

WITH THESE PLANS AND SPECIFICATIONS, THE APPLICABLE PROVISIONS OF THE LATEST
AUTHORITY AND THE REQUIREMENTS OF THE LOCAL POWER COMPANIES,THE
ANY DISCREPANCY IN LOCATION AND RATINGS OF
CHANGES HALL BE MADE ACCORDINGLY.
WITH THE OWNER OR ANY OF HIS REPRESENTATIVES AND
EQUIPMENT AND APPARATUS SHALL

FIXTURES AND ALL NON-CURRENT CARRYING METAL PARTS SHALL BE PROPERLY


GROUNDED IN ACCORDANCE WITH THE PHILIPPINE ELECTRICAL CODE.

ALL SERVICE ENTRANCE EQUIPMENT, SWITCHES, PANELBOARDS, LIGHTING

THE CONTRACTOR SHALL VERIFY AND ORIENT THE ACTUAL LOCATION OF SERVICE
ENTRANCE FOR CONNECTION TO THE POWER SUPPLY.

THE ELECTRICAL WIRING INSTALLATION SHALL BE DONE IN EMT CONDUIT. FLEXIBLE

THE ELECTRICAL SERVICE VOLTAGE SHALL BE 1 PHASE, 2-WIRE + GROUND, 230

ALL ELECTRICAL INSTALLATION WORKS HEREIN SHALL BE DONE IN ACCORDANCE


2
230 V, SINGLE PHASE USE 2-60 mm AMP. MAIN CIRCUIT BREAKER
LINE TO LINE FROM +1-14MM DIA. THH WIRE GROUND
SERVICE ENTRANCE IN 50MM DIA. IMC
M
ELECTRIC
METER

____ A
C1 C10
8 LO. 20A 40A PWH
C2 C11
14 LO. 20A 30A LAU. CO
C3 C12
11 LO.

BE VERIFIED
20A 40A PWH
C4 C13
18 LO. 20A 40A PWH
C5 C14
10 CO. 20A 30A ACU

1800
1500
EARTH

3 TYPICAL 2-5 RISER DIAGRAM


E 6 NOT TO SCALE
SERVICE ENTRANCE DETAIL
3
LOCATION PLAN
NOT TO SCALE
E-01
NOT TO SCALE

LOAD SCHEDULE UNIT 01 PB1 LOAD SCHEDULE UNIT 02-03-04-05 PB2,3,4,5


CKT MULTIPLIER TOTAL CKT MULTIPLIER TOTAL
LOAD DESCRIPTION QTY WATTS PHASE WATTS VOLTS AMP CB WIRES LOAD DESCRIPTION QTY WATTS PHASE WATTS VOLTS AMP CB WIRES
NO. NO.
1 MAIN POLE 1 MAIN POLE
2 LIGHTING 6 100 2 600 230 2.61 15 2- 2.0 mm² THHN 2
15 mm Ø EMT PIPE 2 LIGHTING 6 100 2 600 230 2.61 15 2- 2.0 mm² THHN 2
15 mm Ø EMT PIPE
1- 2.0 mm² THHN 1- 2.0 mm² THHN
3 PIN LIGHT 8 100 2 800 230 3.48 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE
2 3 PIN LIGHT 8 100 2 800 230 3.48 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE
2
1- 2.0 mm² THHN 1- 2.0 mm² THHN
4 LIGHTING 5 100 2 500 230 2.17 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE 4 LIGHTING 5 100 2 500 230 2.17 20 1- 3.5
2- mm² THHN 15 mm Ø EMT PIPE
1- 2.0 mm² THHN 2.0 mm² THHN
5 LIGHT 3 100 2 300 230 1.30 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE 5 LIGHT 3 100 2 300 230 1.30 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE
1- 2.0 mm² THHN 1- 2.0 mm² THHN
6 PIN LIGHT 10 100 2 1000 230 4.35 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE 6 PIN LIGHT 10 100 2 1000 230 4.35 20 1- 3.5
2- mm² THHN 15 mm Ø EMT PIPE
1- 2.0 mm² THHN 2.0 mm² THHN
7 CONVENIENCE OUTLET 10 180 2 1080 230 4.69 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE 7 CONVENIENCE OUTLET 10 180 2 1080 230 4.69 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE
1- 2.0 mm² THHN 1- 2.0 mm² THHN
8 CONVENIENCE OUTLET 7 180 2 1260 230 5.48 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE 8 CONVENIENCE OUTLET 7 180 2 1260 230 5.48 20 1- 3.5
2- mm² THHN 15 mm Ø EMT PIPE
1- 2.0 mm² THHN 2.0 mm² THHN
9 CONVENIENCE OUTLET 6 180 2 1080 230 4.69 20 2- 3.5 mm² THHN 15 mm Ø EMT PIPE 9 CONVENIENCE OUTLET 6 180 2 1080 230 4.69 20 1- 2.0 mm²
2- 3.5 THHN 15 mm Ø EMT PIPE
1- 2.0 mm² THHN mm² THHN
10 REF 1 2 2000 230 8.69 20 2- 3.5 mm² THHN 10 REF 1 2 2000 230 8.69 20 2- 3.5 mm² THHN
2000 1- 2.0 mm² THHN 15 mm Ø EMT PIPE 2000 1- 2.0 mm² THHN 15 mm Ø EMT PIPE

TOTAL LOAD: 37.46 TOTAL LOAD: 37.46

12.020 VA x 80% D.F. + 25% (2200VA) SIZE OF FEEDER : 12.020 VA x 80% D.F. + 25% (2200VA) SIZE OF FEEDER :
I FL= I FL=
230 V USE : 2- 14 mm² THHN 230 V USE : 2- 14 mm² THHN
1-8.0 mm² THW (G ) / 25mm Ø IMT 1-8.0 mm² THW (G ) / 25mm Ø IMT
I FL= 37.46 Amperes / 60 AT MAIN MAIN : 60 AT, 2P, 230V, 60HZ I FL= 37.46 Amperes / 60 AT MAIN MAIN : 60 AT, 2P, 230V, 60HZ

ARCHITECT OWNER : PROJECT TITLE SHEET CONTENTS REVISIONS SHEET NO.


NO. DESCRIPTION DATE
"DRAWINGS AS INSTRUMENTS LOAD SCHEDULES
OF SERVICE REMAINS THE RISER DIAGRAM
PROPERTY OF THE
MR. JOFEL C. LAGUMBAY THREE STOREY APARTMENT BUILDING
IAPOA:
ARCHITECT, AND AS SUCH
MUCH NOT BE REPRODUCED
OR COPIED IN PART OR IN
SERVICE ENTRANCE DETAIL
E1
WHOLE WITHOUT
PTR NO : PLACE ISSUED : DATE ISSUED : PERMISSION.." (R.A. 9266) LOCATION : B4 L8 NARRA ST TAMARA LANE SUBDIVISION KAYBIGA CALOOCAN ELECTRICAL PLAN