Download as pdf or txt
Download as pdf or txt
You are on page 1of 22

Energy Automation

7UT8 Transformer Differential


Protection:
- CT Requirements

© Siemens AG 2015. All rights reserved.


Content

§ Basics
§ Magnitude and angle errors of current transformers
§ Transients
§ Design
§ Summary of current transformers

© Siemens AG 2015. All rights reserved.


Page 2 30.06.2015 Energy Automation Division Energy Management
Basics
Types of current transformers

Resin-insulated Generator-current transformer


Indoor or outdoor For terminal box or main leads

Current transformers

insulator-type transformer

slip-over transformer

bushing-type current transformer


totally insulated

Cable-type current transformer

© Siemens AG 2015. All rights reserved.


Page 3 30.06.2015 Energy Automation Division Energy Management
Basics
Magnitude and angle errors

N
I‘p = Ip. 1
N2
Equivalent circuit:

Ip I‘p Rct e
Is Magnitude
error
N1 N2 I0 Is

L0 E U2 Rba

ideal Faulted part of current d


current transformer
Angle error
transformer

Note:
The secondary current is leading
(positive angle error) I0
© Siemens AG 2015. All rights reserved.
Page 4 30.06.2015 Energy Automation Division Energy Management
Basics
Defined errors at the P class

Definition:
5 P 20 30 VA
Rated burden
Rated accuracy limiting factor (ALFN old n)

core type P = protection

accuracy in % at ALFN · IN

at rated current at primary overcurrent


Accuracy
class Magnitude
Angle error Angle error Total error
error

% minute centigrade %
5P ±1 ±60 ±1,8 5
10P* ±3 ¾ ¾ 10

All values are valid for steady state conditions (symmetrical currents)

* fault angle is not specified in IEC 61869-2, therefore, the Class 10P for the differential protection is not recommended.
© Siemens AG 2015. All rights reserved.
Page 5 30.06.2015 Energy Automation Division Energy Management
Basics
Influence of the burden on the errors

Isecondary/In burden < 15 VA

Improvement
Under of the saturation
burden degree
10 burden = 15 VA
Fi = 10%

Note:
burden > 15 VA The burden is mainly
determined by the instrument
5
leads.

10P10, 15 VA Over
burden

0 5 10 15 Iprimary/In

© Siemens AG 2015. All rights reserved.


Page 6 30.06.2015 Energy Automation Division Energy Management
Basics
Definition of the rated currents

Primary rated current


Orientation on the rated current of the protective object
Normally the CT current selection is a little bit higher
Grading according standard: Decimal multiple of
10 – 12,5 – 15 – 20 – 25 – 30 – 40 – 50 – 60 – 75 A
(CT manufacturer delivers also a different grading)
Example: IN,G = 7330 A à selected rated CT current: 8000 A

Secondary rated current


Dominant current are 1 A and 5 A (according standard 2 A is permissible)
5 A: Advantage: less number of winding turns; Disadvantage: low permissible
burden ( ZN = SN,CT/(IN,CT)2 = 15 VA/25 A2 = 0,6 Ohm)
1A: Advantage: Higher permissible burden ( ZN = SN,CT/(IN,CT)2 = 15 VA/1 A2 = 15
Ohm); Disadvantage: higher number of winding turns (larger internal burden)

Preferred secondary rated current: 1A

© Siemens AG 2015. All rights reserved.


Page 7 30.06.2015 Energy Automation Division Energy Management
Basics
Equivalent circuit and Magnetizing characteristic

Ip I‘p Is RCt E = secondary e.m.f. (rms)


I0 (knee point voltage)
L0
TP E US RBC IP = primary current
Is = secondary current
ideal Faulted part of current
CT transformer I0 = Magnetizing current
RCt = sec. winding resistance
Example: CT 1500/1A, 5P20, 50VA, Rct = 3Ω
RBC= connected burden
US = sec. voltage (rms)
E TP = primary time constant
(e.g. network time)
constant)
Note:
Magnetizing characteristic is nonlinear

E = Is·(Rct + Rba)

I0
© Siemens AG 2015. All rights reserved.
Page 8 30.06.2015 Energy Automation Division Energy Management
Basics
Special features of class P CTs

Specified is for the total error at accuracy limit current


(5P20 à 5% at twenty time of rated current and rated burden)
No requirements on remanence
Closed ring core
Large CT time constant (seconds to minutes)

Problem:
Remanence § Current transformer is magnetized e.g. via
switching off of a transient current with a large
Hysterese
DC time constant. He remains in the resulting
Initial
remanence point.
magnetizing
curve
§ An new fault current can immediately lead to a
saturation. Reason: The process starts from the
remanence point (worst case: 80%)
§ The actual value of remanence is unknown (e.g.
the fault current can also start in the opposite
direction). This leads to a reduction of
remanence)

© Siemens AG 2015. All rights reserved.


Page 9 30.06.2015 Energy Automation Division Energy Management
Basics
Transient currents

Primary- and
I‘p [A]
secondary IS [A]
current

CT goes into
saturation

Magnetizing I0 [A]
current

© Siemens AG 2015. All rights reserved.


Page 10 30.06.2015 Energy Automation Division Energy Management
CT saturation
Critical at differential protection

Trip
45°

Block

© Siemens AG 2015. All rights reserved.


Page 11 30.06.2015 Energy Automation Division Energy Management
Current differential protection
Switching on of external loads can lead to problems 1/3

Generator differential protection trip on generator G1


In a industrial plant a transformer was switched on

69 kV Industrial infeed

30 km

12 MVA

6,9 kV

G1 G2

5,6 MVA G G
© Siemens AG 2015. All rights reserved.
Page 12 30.06.2015 Energy Automation Division Energy Management
Current differential protection
Switching on of external loads can lead to problems 2/3

Instantaneous values from the protection

DC component in the phase current is clear visible


© Siemens AG 2015. All rights reserved.
Page 13 30.06.2015 Energy Automation Division Energy Management
Current differential protection
Switching on of external loads can lead to problems 3/3

Different DC transient
transmission leads to a
small increased differential
current with a low
0,15 stabilizing current

0,18 Countermeasure:
Increasing of the
inclination of slope 1 from
0,15 to 0,25 (factory
setting)

© Siemens AG 2015. All rights reserved.


Page 14 30.06.2015 Energy Automation Division Energy Management
Current transformer dimensioning
Over dimensioning factor

To improve the transient performance of the CT the relay manufacturer specify a


transient dimensioning factor (Ktd).

Required actual accuracy limiting factor (ALF):

ALF = K td × K SSC

Required rated accuracy limiting factor (ALF’):

R BC + R Ct
ALF' = ALF
R BN + R Ct

© Siemens AG 2015. All rights reserved.


Page 15 30.06.2015 Energy Automation Division Energy Management
Transformer Differential CT calculation

Glossary of used abbreviations:


ALF' Operational Accuracy Limit Factor

ALF'

ALF Accuracy limit factor


Rct Secondary winding resistance at 75°C
Rb Ohmic rated burden
Rba Rated resistive burden
Rs (Rct + Rba)
Ipr Primary rated current of the transformer
Isr Secondary rated current of the transformer
IInt.max Maximum internal symmetric fault current
IExt.max Maximum external symmetric fault current
Ktd Transient rated dimensioning factor
KSSC Factor of the symmetric rated short-circuit current = Ipsc/Ipr
Ek Knee-point voltage
Vt Rated terminal voltage with 20-fold rated current and rated burden Rb
Vta Current terminal voltage with 20-fold rated current and current burden Rba
© Siemens AG 2015. All rights reserved.
Page 16 30.06.2015 Energy Automation Division Energy Management
Transformer Differential CT calculation

Recommendation:
As remanence leads to earlier saturation which, in general, is critical for the differential protection. For new
systems, Siemens recommends anti-remanence cores in the classes 5PR, PXR and TPY. In case of the high
direct-current components to be expected, Siemens recommends the class TPZ, so that an overfunction with
external faults is avoided. © Siemens AG 2015. All rights reserved.
Page 17 30.06.2015 Energy Automation Division Energy Management
Current transformer dimensioning
CT verification 1/5

1. Internal Fault 2. External Fault


31.5kA

l= 60m
110 kV, 50Hz A= 4mm2

7UT85

-T (T HV) -T1
1250/1A 200MVA
5P30 110/30 kV
5 VA 50 Hz
Rct = 18Ω uk = 14%

© Siemens AG 2015. All rights reserved.


Page 18 30.06.2015 Energy Automation Division Energy Management
Current transformer dimensioning
CT verification 2/5
SN 200000kVA
Transforme r rated current : I N ,Tr = = = 1050 A
3 ×U N 3 ×110kV
100% 100%
Maximum external symmetric fault current : I Ext .max = I N ,TR × = 1050 A × = 7498 A
uk 14%
31500 A
Factor of the internal symmetric rated short - circuit current : K ssc (int) = = 25.2
1250 A
7498 A
Factor of the external symmetric rated short - circuit current : K ssc (ext ) = = 6.0
1250 A

a.)IEC class 5P
31500 A
1. Internal fault : ALF' = 0.5 × = 12.6
1250 A
7498 A
2. External fault : ALF' = 2 × = 12 " but minimum 25"
1250 A
Result :
Operating accuracy limiting factor of ³ 25, for example : 5P30, R b = Sr /I sr ³ connected burden
R ba for example : Sr = 2.5 VA or 5 VA - > 5P30 5VA

Ktd = 2 for external fault (given from the relay manufacturer)

© Siemens AG 2015. All rights reserved.


Page 19 30.06.2015 Energy Automation Division Energy Management
Current transformer dimensioning
CT verification 3/5

S n 5 VA
Rb = 2
= = 5Ω
I sn 1A 2
2×ρ ×l
R ba = R Cable + R Relay = + 0.1 Ω
A
Ω mm 2
2 × 0.0175 × 60 m
= m + 0.1 Ω = 0.625 Ω
4 mm 2 ALF required = 25
ALF CT = 37.05
CT: 25 < 37.05
R Ct + R BN 18 Ω + 5 Ω
ALF = ALF N × = 30 × = 37.05 à CT Dimensioning is okay
R Ct + R BC 18 Ω + 0.625 Ω

Rb Ohmic rated burden


Rba Rated resistive burden
ALF' Operational Accuracy Limit Factor
ALF Accuracy limit factor
ρ Specific resistance of cupper

© Siemens AG 2015. All rights reserved.


Page 20 30.06.2015 Energy Automation Division Energy Management
Current transformer dimensioning
Avoiding of overfunction via remanence

Present practice:
Current applications live the risk of remanence (low probability assumed) and
trust the saturation detection in the relays

Additional over dimensioning of the P – core


1 1
K rem = ® worst case at class P : =5
1 - Kr 1 - 0,8
CT design is becomes larger and is more expensive

Current transformer with air gap and lower remanence


§ PR as class P , max. remanence factor 10%
(approx. factor 1,2 larger as P core)
§ TPY IEC 61869-2:2012, max. remanence factor 10%
(Cl. 1 at IN, error is specified at the transient overcurrent)
§ TPZ IEC 61869-2:2012, no remanence
(angle error 180‘ àtime constant 60 ms; Rated burden must be
connected on the CT) © Siemens AG 2015. All rights reserved.
Page 23 30.06.2015 Energy Automation Division Energy Management
Appendix

Thank you for your


attention!

© Siemens AG 2015. All rights reserved.


Page 24 30.06.2015 Energy Automation Division Energy Management

You might also like