Professional Documents
Culture Documents
Field Experience of Ssda - Ieee 2010
Field Experience of Ssda - Ieee 2010
This paper describes the IIE and CFE experiences Comisión Federal de Electricidad (CFE) has several
obtained during several years in the use of surge arresters thousand kilometers of 230 and 400 kV transmission lines
(externally gapped) on distribution and transmission lines that
(which are considered the main transmission voltages) built
run along different parts of the country. These lines usually had
many outage rates before being protected with surge arresters.
along the country: 27,147 km and 28,144 km, respectively as
per 2005, which are considered the main transmission
Index Terms— Lightning performance, ground flash density, voltages. All these lines have seriously been affected by
shielding angle, transmission line surge arrester, distribution line lightning and those whose performance has been very poor,
surge arrester, shielding failure, backflashover, footing were chosen under that criteria in order to be protected with
resistance. surge arresters even though the shielding angle and the tower
footing resistance may have been improved in several
I. INTRODUCTION structures, the evaluation will be considered before and after
L ightning is one of the main causes of problems on the arrester installation [1].
transmission lines, this will usually happen when a stroke
hits: the phase conductor, the groundwire or directly the One of the main commitments of the National
structure. If the first case occurs, the line may have a shielding Mexican utility (CFE) is to guarantee the continuity of the
failure. Meanwhile in the second or third cases, there may be a power supply through its owned transmission lines.
backflashover, which generally depends on a high footing Unfortunately, the service is frequently interrupted by
resistance value. These problems can be mitigated in several lightning caused failures, which are really very severe in
ways depending on the amount of investment the utility is several regions of the country, mainly in mountainous areas
decided to spend. For example, if the only concern is how to where many of the main transmission lines are located.
reduce the number of shielding failures, this can be done by
efficiently locating the groundwires in order to obtain an During 2005, the lightning caused failure represented
effective shielding angle. The backflashover problem can also 42 % of the total failures, meanwhile in 2006 represented 49
be solved partially by reducing the footing resistance at critical % for 230 kV transmission lines. The same performance was
towers by traditional or artificial methods. However, if the soil observed for 400 kV transmission lines, for 2005 and 2006,
conditions do not permit the installation of a good footing the lightning causes failures represented 38 % and 47 %,
resistance, line arresters are a good alternative. Recently, respectively.
worldwide utilities have started installing metal oxide arresters
on their transmission lines. Usually, transmission lines are protected by
groundwires, in order to avoid shielding failures. Most strokes
Each utility defines the way the arresters are installed are expected to terminate on the groundwires. Under certain
depending on the number of failures the line has, by applying conditions if the grounding resistance is high, there is a
probability of an insulation failure due to a backflashover. The
insulation failures may be reduced mainly in three ways:
C. Romualdo-Torres, Instituto de Investigaciones Eléctricas, Cuernavaca, reducing the tower footing resistance, locating properly the
Mor., Mexico. (e-mail: crt@iie.org.mx). groundwires or installing surge arresters.
F. Martínez-Fonseca, Comisión Federal de Electricidad, Mexico City,
Federal District. (e-mail: froylan.martinez@cfe.gob.mx).
The mounting schemes of surge arresters are of two B. Philosophy of surge arrester application
types: the arresters without any gap, which are connected
directly to the phase conductor line by means of a This section describes briefly the philosophy used for
disconnector, or the surge arrester externally with a series gap, the application of surge arrester in all transmission lines
which will operate by an air gap adjusted to flashover value studied in this paper. It is based on the following simple rules:
before the insulator string can be flashed over by lightning
surges. All these improvements will permit to have lighter a) Outage rate statistic of the prospect transmission line,
arresters than the present designs [2]. at least of the last five years or before in order to
obtain the typical lightning performance of the line.
A. Recent worldwide field experience with surge arrester b) Grounding resistance measurements along conflictive
installation line areas.
c) Ground flash density along the line.
Many utilities around the world have been worried d) Terrain topography through the transmission line
about the problems caused by lightning to transmission lines, route
and several solutions have been used such as the improvement e) Exposed towers over elevated mountainous areas
of the shielding angle and the footing resistance. However, with slopes and ravines, long spans and scarce
some obtained results are not sufficient in order to reduce the vegetation.
outages due to lightning, therefore the other cost effective
alternative is the installation of surge arresters in critical areas Surge arresters are commonly used as follows: they
combined in some cases with the improvements mentioned are only installed on critical sections of the line, or in regions
before. Many field experiences have been obtained with rocky soil where soil resistivity is very high, because it is
successfully with the installation of arresters in several considered cheaper to install arresters instead of improving the
countries such as: Brazil, Japan, as well as in Mexico. soil resistivity for decreasing the tower footing resistance. The
importance of the critical loads connected to the line where the
The Brazilian Ouro Preto - Mariana 138 kV line reliability must be high in spite of the costs It is also
transmission line which supplies energy to an industrial considered.
customer was reported to have 41 outages/100 km/year. The
considered solution was the installation of arresters in all three Since 1999, the IIE and CFE started a research
phases along all the structures. After this decision, failures in project installing surge arresters externally gapped in several
above line were reduced virtually to zero [3]. 230 kV transmission lines, with many successful results
decreasing drastically the lightning caused failures in those
For the last 25 years, externally gap surge arresters equipped lines with this kind of arrester.
have been used in Japan for 66 kV to 154 kV transmission
lines. However, new research and designs have been By 2004, the same arresters type, were installed in
developed for 275 kV transmission lines for further other 400 kV transmission lines, with the same successful
compactness, the improvement of the zinc oxide material, results as obtained in 230 kV level. The description of the
housing design as well as the optimum requirements for results obtained for distribution and transmission lines are
mechanical strength. shown in the following sections.
practically zero [5, 6]. 1993 and 1994 after installing surge arresters and the number
and type of surge arresters [5, 6].
Figure 1. Recloser operations at MZT 4040 distribution circuit, B. Installation of 230 kV arresters with external series gap
before and after the surge arrester installation [5, 6].
Since 2002, when the program for the installation of
III. APPLICATION OF SURGE ARRESTERS ON surge arresters on the MZD-93820-DGD transmission line
TRANSMISSION LINES started, at least 61 have been installed along the line at the
outer phase conductors of the line with selected critical
A. 115 kV transmission line equipped with external gapped regions of the line with the major lightning problems. This line
and gapless arresters has 220 km in length, a single circuit, with two groundwires
on a horizontal configuration. However, it has always had
The installation of surge arresters for 115 kV lines many problems due to lightning because it runs most of its
started in 1991 on a transmission line with a high outage rate length across ridges and high altitude mountains. Lightning
caused by lighting during thunderstorm periods. This line is storm seasons are very severe in these regions causing
running at the Southern Mexican Chiapas State, which is considerable damages to line insulation and as a consequence
described in three parts as follows: many line outages. Figure 2 shows the line performance
before and after the surge arrester installation [7]. Photograph
a) The first part of the line, coming from La Angostura number 1 of Appendix I shows the typical field installation for
hydroelectric power plant is a double circuit 141 this kind of arresters.
tower path identified as TL 73520. This line was
provided with 40 metal oxide arresters in 20 towers.
b) The second part is a single circuit line comprising
100 towers with 111 km line length, identified as TL
73530 which starts at tower number 141. This line
was provided with external series gap arresters [8] on
20 towers, most of them located on mountain ridges.
Outages reports showed them as highly exposed to
lightning damage. Arresters were installed at the
upper and bottom phases on 13 towers; the remaining
tower arresters were installed on the three phases.
c) The third part is a double circuit line which also
starts at tower number 141 with 226 towers with 159
km line length, identified as a double circuit TL Figure 2. Outages rates for MZD-93820-DGD transmission line [7].
73540/73560, both branches finally join at
Mapastepec substation. The full line is called La This line has had a permanent maintenance program
Angostura-Belizario Domínguez. TL 73560 was for improving the footing resistance at critical towers as well
provided with 60 arresters protecting upper and lower as the correction of the shielding angle for values near to a
phase conductors in 30 towers [5, 6]. zero angle or a negative value with the purpose of reducing the
shielding failure. The grounding resistance for this line where
Some parts of the line has long span lengths ranging arresters were installed was kept under 10 Ohms.
from about 900 to 1650 m, which is a factor that may
contribute to backflashover rates [9, 10]. Even though, the installation of surge arresters began
on this line in 2002, the maintenance program is still
Table 1 shows every circuit, the average outage rate continuing up to now. The arresters were only installed at the
before installing surge arresters, the average outage rate for
4
outer phases of the line selecting the structures located at the along ridges and high altitude mountains at the Central part of
critical sections of the line. the country. Lightning storm seasons are very severe causing
several insulation damages and as a consequence several line
Figure 2 shows, that this line had a very poor outages. Since 2005, at least 18 surge arresters have been
lightning performance from 1988 to 2000. However, with all installed on the line areas where major problems exist.
these corrections developed on the transmission line during
the line maintenance program and together with the Figure 4 shows, that this line had a very poor
installation of surge arresters, good results have been obtained lightning performance from 1997 to 2002. However, with
since 2001, with decreasing outages of the line virtually to footing resistance and shielding angle corrections developed
zero. on the transmission line during the permanent maintenance
program and together with the installation of surge arresters,
C. Installation of 400 kV arresters with external series gap good results have been obtained since 2005, with a decrease of
the outages of the line to a reasonable value.
Since 2004, the installation of surge arresters started
at the TUL-A3210-PRD transmission line. At least 13 surge The grounding resistance for this line where arresters
arresters were installed on critical areas of this line where were installed was kept under 10 Ohms.
major problems exist. It has 203 km in length. It is a single
circuit line with two groundwires on a horizontal
configuration. However, this line has had many problems due
to lightning, because runs most of its course along ridges and
high altitude mountains at the Eastern part of the country.
Lightning storm seasons are very severe over this area,
causing several insulation damages and as a consequence
several line outages occur. Figure 3 shows the lightning
performance of line before and after the surge arrester
installation [7]. Photograph number 2 of Appendix I shows the
typical field installation for this kind of arresters.
transmission lines in order to improve their lightning [4] L. P. Peter. Use of Line Surge Arresters to improve Lightning
performance. performance of a 275 kV line: A South African Pre-Engineering
Case Study. 28th International Conference on Lightning
Appendix I Protection. Kanazawa, Japan, 2006.
[5] F. De la Rosa F., R. Velazquez. Application of MOSA in T&D
Systems in Mexico. IEEE T&D Conference Procceedings, pp.
Typical installation of external gapped surge arresters 248-254, Los Angeles CA., Sept 15-20, 1996, ISBN 0-7803-
for 230 and 400 kV transmission lines 3522-8/96.
[6] G. Enriquez, R. Velazquez R., C. Romualdo. Mexican experience
with the application of transmission line arresters, paper C4-106,
CIGRE 2006.
[7] Lightning Field Performance of 230 and 400 kV Transmission
Lines with Surge Arresters, IIE, Internal project report 13153,
November 2006, (in Spanish).
[8] Furukawa S., Usuda O., Izosaki T., Irie T. Development and
Application of Lightning Arresters for Transmission Lines.
IEEE Trans. on PWR-D, Vol. 4, No. 4, pp. 2121-2129, October
1989.
[9] CIGRE WG 33-01, Guide to Procedures for Estimating the
Lightning Performance of Transmission Lines. CIGRE
Monograph No. 63, October 1991.
[10] Hileman A. R. Insulation. Coordination for Power Systems.
Marcel Dekker, Inc. ISBN 0-8247-9957-7, 1999.
VI. ACKNOWLEDGMENTS
Picture number 1. Typical installation of an external gapped arrester
for a 230 kV transmission line [7]. The authors are grateful to CFE engineers: José
Carlos Villicaña Coronado, Agustín Villavicencio Valadez,
Fernando Guadalupe González, Antonio Paniagua Silva,
Diego Durán Insunza, David Solís Corral, José Villanueva
Gutiérrez as well as Ernesto Escenaro Marín for all the
unvaluable information provided for this research.
VII. BIOGRAPHIES