PROJECT - CENTRE POINT HOTEL

PROJECT NO - L541
REVISION - R0
COOLING LOAD SUMMARY SHEET
CALCULATED SELECTED

LIGHTING
NO OF AREA TOTAL AREA FRESH AIR TON/ TOTAL DEHUMIDIFIED
S.NO. FLOOR APPLICATION/ROOMS OCCUPANCY LOAD DENSITY CFM TR/unit AHU/FCU NUMBER EQUIPMENT NAME CFM DIFF.
ROOM/FLOOR (sq.ft) (sq.ft) (CFM) SPACE TONNAFE AIR (CFM)
(W/sq.ft)

1 GF-HALL'!A1 1 1160 1160 140 1.5 770 16.1 16.14 4731


2 GF-PRE FUNCTION'!A1 1 550 550 17 1.5 161 3.3 3.35 1119
3 GF-bar'!A1 1 570 570 25 1.5 222 3.8 3.77 1023
4 GF-CLUB CABANA'!A1 1 845 845 50 1.5 426 8.0 8.02 2398
GROUND FLOOR
5 GF-BANQUET SALES'!A1 1 150 150 4 1.5 29 0.9 0.94 388
6 GF- MANAGER CABIN'!A1 1 96 96 3 1.5 21 0.6 0.57 214
7 GF-BACK OFF'!A1 1 65 65 3 1.5 19 0.6 0.63 263
8 GF-LOBBY & RECP.'!A1 1 2100 2100 80 1.5 526 13.5 13.46 4860
GF-LIFT LOBBY'!A1 1 330 330 10 1.25 70 2.0 2.04 805

9 1F- ROOM 01 02'!A1 2 332 664 3 1 35 1.3 2.54 711


10 1F- ROOM 03 04 05'!A1 3 290 870 3 1 32 0.9 2.62 474
11 1F- ROOM 06'!A1 1 530 530 5 1 57 1.6 1.63 892
12 1F- RM 7 8 9 10 11'!A1 5 225 1125 3 1.25 29 1.0 5.08 450
13 FIRST FLOOR 1F- ROOM 12'!A1 1 290 290 4 1 32 1.1 1.12 623
14 1F- ROOM 13'!A1 1 225 225 3 1.25 29 1.5 1.49 733
15 1F- RM 14 15 16 17'!A1 4 240 960 3 1.25 29 1.0 4.16 460
16 1F- OFFICE TYP.'!A1 3 160 480 3 1.25 30 1.5 4.52 724
1F-ADMIN STAFF'!A1 1 455 455 20 1 127 3.2 3.24 1159

1F- ROOM 01 02'!A1 2 332 664 3 1.25 35 2.1 4.26


1F- ROOM 03 04 05'!A1 3 290 870 3 1.25 32 1.5 4.62
1F- ROOM 06'!A1 1 530 530 5 1.25 57 3.1 3.05
SECOND FLOOR 1F- RM 7 8 9 10 11'!A1 5 225 1125 3 1.25 29 1.0 5.08
1F- ROOM 12'!A1 1 290 290 4 1.25 32 1.5 1.45
1F- ROOM 13'!A1 1 225 225 3 1.25 29 1.5 1.49
1F- RM 14 15 16 17'!A1 4 240 960 3 1.25 29 1.0 4.16

1F- ROOM 01 02'!A1 2 332 664 3 1.25 35 2.1 4.26


1F- ROOM 03 04 05'!A1 3 290 870 3 1.25 32 1.5 4.62
1F- ROOM 06'!A1 1 530 530 5 1.25 57 3.1 3.05
THIRD FLOOR 1F- RM 7 8 9 10 11'!A1 5 225 1125 3 1.25 29 1.0 5.08
1F- ROOM 12'!A1 1 290 290 4 1.25 32 1.5 1.45
1F- ROOM 13'!A1 1 225 225 3 1.25 29 1.5 1.49
1F- RM 14 15 16 17'!A1 4 240 960 3 1.25 29 1.0 4.16

1F- ROOM 01 02'!A1 2 332 664 3 1.25 35 2.1 4.26


1F- ROOM 03 04 05'!A1 3 290 870 3 1.25 32 1.5 4.62
1F- ROOM 06'!A1 1 530 530 5 1.25 57 3.1 3.05
FORTH FLOOR 1F- RM 7 8 9 10 11'!A1 5 225 1125 3 1.25 29 1.0 5.08
1F- ROOM 12'!A1 1 290 290 4 1.25 32 1.5 1.45
1F- ROOM 13'!A1 1 225 225 3 1.25 29 1.5 1.49
1F- RM 14 15 16 17'!A1 4 240 960 3 1.25 29 1.0 4.16

608677195.xlsxSUMMARY
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541

GF-HALL ZONE PEAK DATE 6-Sep

GROUND FLOOR AREA U TD DESIGN DB WB RH GR ENTH


EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70

WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4

WEST SOLAR 98 163 0.4 6,394 DIFFERENCE 28 20.5 72.3

TRANS 98 0.56 28 1,538 AREA 1160 SQFT HT = 13 FT


WALL 235 0.36 28 2,364 VOLUME 15105.06 SHYAM:

NORTH SOLAR 0 23 0.4 0 PEOPLE 140 Multipurpose


application
TRANS 0 0.56 28 0 LIGHTING 1740
WALL 640 0.36 28 6,447 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 69.6
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 700
WALL 0 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 179 0.36 23 1,483 SELECTED CFM 770 SHYAM:

FLOOR 1160 0.21 30 7,308 SHADING 0.40 Multipurpose


application
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 140 270 37,800 R.A. GAIN 0
LIGHTING 1740 3.4 1.25 7,395 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 1740 3.4 5,916 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 769.6 0.1 1.08 28 2,327 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 78,972 WEST 12 163
DUCT LOSSES, ETC. 7,897 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 86,870 NORTH-WEST 12 138
PEOPLE 140 195 27,300 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 770 0.68 0.1 72.3 3,784 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 31,084 CEILING 0.21
OTHER GAINS & SAFETY 3,108 FLOOR 0.21
ROOM LATENT HEAT 34,192
ROOM TOTAL HEAT 121,062 NOTE:-
OUTSIDE SEN HEAT 769.6 1.08 0.9 28 20,945 LIGHTING LOAD- 1.5 W/sq.ft
AIR LAT HEAT 769.6 0.68 0.9 72.3 34,053 EQUIP. LOAD- 1.5 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 176,060
OTHER GAINS & SAFETY 17,606
GRAND TOTAL HEAT 16.1 TR 193665.95 BTU/HR
S.H.F 0.72 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 166.95 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 4.08
D.H.A 4731.4566 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 4731 AREA /TON 71.88
Tons 16.1

608677195.xlsxGF-HALL
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541

GF-PRE FUNCTION ZONE PEAK DATE 5-Feb


GROUND FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70

WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4

WEST SOLAR 0 163 0.4 0 DIFFERENCE 28 20.5 72.3

TRANS 0 0.56 28 0 AREA 550 SQFT HT = 13 FT


WALL 0 0.36 28 0 VOLUME 7161.88 Author:
NORTH SOLAR 0 23 0.4 0 PEOPLE 17
PREFUNCTIO
TRANS 0 0.56 28 0 LIGHTING 825 application

WALL 426 0.36 28 4,298 VENTILATION 0


SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 33
TRANS 0 0.56 28 0 CFM/PERSON 7.5 CFM 127.5
WALL 0 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 0 0.36 23 0 SELECTED CFM 161 Author:

FLOOR 550 0.21 30 3,465 SHADING 0.40 PREFUNCT


application
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 17 270 4,590 R.A. GAIN 0
LIGHTING 825 3.4 1.25 3,506 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 688 3.4 2,338 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 160.5 0.1 1.08 28 485 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 18,682 WEST 12 163
DUCT LOSSES, ETC. 1,868 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 20,550 NORTH-WEST 12 138
PEOPLE 17 195 3,315 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 161 0.68 0.1 72.3 789 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 4,104 CEILING 0.21
OTHER GAINS & SAFETY 410 FLOOR 0.21
ROOM LATENT HEAT 4,514
ROOM TOTAL HEAT 25,065 NOTE:-
OUTSIDE SEN HEAT 160.5 1.08 0.9 28 4,368 LIGHTING LOAD- 1.5 W/sq.ft
AIR LAT HEAT 160.5 0.68 0.9 72.3 7,102 EQUIP. LOAD- 1.25 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 36,535
OTHER GAINS & SAFETY 3,653
GRAND TOTAL HEAT 3.3 TR 40188.32 BTU/HR
S.H.F 0.82 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 73.07 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.04
D.H.A 1119.3048 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 1119 AREA /TON 164.23
Tons 3.3
Author:

PREFUNCTION in hotel
application

Author:

PREFUNCTION in hotel
application
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS

GF-bar ZONE PEAK


GROUND FLOOR AREA U TD DESIGN DB
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F
TRANS 0 0.56 28 0 OUTSIDE 100

WALL 0 0.36 28 0 INSIDE 72

WEST SOLAR 0 163 0.4 0 DIFFERENCE 28

TRANS 0 0.56 28 0 AREA 570


WALL 0 0.36 28 0 VOLUME 7422
NORTH SOLAR 0 23 0.4 0 PEOPLE 25
TRANS 0 0.56 28 0 LIGHTING
WALL 0 0.36 28 0 VENTILATION
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06
TRANS 0 0.56 28 0 CFM/PERSON 7.5
WALL 0 0.36 28 0 PERSON/1000 SFT
PARTITION 0 0.36 23 0 SELECTED CFM 222
FLOOR 570 0.21 30 3,591 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 25 270 6,750 R.A. GAIN 0
LIGHTING 855 3.4 1.25 3,634 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 713 3.4 2,423 SOLAR: 8.0 AM
INFILTRATION 0 1.08 28 0 NORTH 23
O.A. BYPASS 221.7 0.1 1.08 28 670 SOUTH 12
EAST 163
SUB TOTAL 17,068 WEST 12
DUCT LOSSES, ETC. 1,707 NORTH-EAST 138
ROOM SENSIBLE HEAT 18,774 NORTH-WEST 12
PEOPLE 25 195 4,875 SOUTH-EAST 85
STEAM SOUTH-WEST 12
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56
O.A. BYPASS 222 0.68 0.1 72.3 1,090 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 5,965 CEILING 0.21
OTHER GAINS & SAFETY 596 FLOOR 0.21
ROOM LATENT HEAT 6,561
ROOM TOTAL HEAT 25,336 NOTE:-
OUTSIDE SEN HEAT 221.7 1.08 0.9 28 6,034 LIGHTING LOAD- 1.5
AIR LAT HEAT 221.7 0.68 0.9 72.3 9,810 EQUIP. LOAD- 1.25
RETURN AIR GAIN
GRAND SUB TOTAL 41,179
OTHER GAINS & SAFETY 4,118
GRAND TOTAL HEAT 3.8 TR 45297.32 BTU/HR
S.H.F 0.74 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 79.47 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 1.79
D.H.A 1022.5729 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 1023 AREA /TON 151.00
Tons 3.8
16.00 HRS JOB L541

DATE 6-Sep

WB RH GR ENTH
DEG F % BTU
82 47 137.3 45.70
61.5 55 65 27.4
20.5 72.3

SQFT HT = 13 FT
Shyam:

as per sitting arrangement


shown in layout
855
0
CFM 34.2
CFM 187.5
PEOPLE
Shyam:

Bar & louges in hotel


application

hru Glass:At 20° N Latitude


4:00PM 12:0PM
23
12 14
12
163
12
138
12
85
Glass
W/sq.ft
W/sq.ft
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS

GF-CLUB CABANA ZONE PEAK


GROUND FLOOR AREA U TD DESIGN DB
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F
TRANS 0 0.56 28 0 OUTSIDE 100

WALL 0 0.36 28 0 INSIDE 72

WEST SOLAR 0 163 0.4 0 DIFFERENCE 28

TRANS 0 0.56 28 0 AREA 845


WALL 0 0.36 28 0 VOLUME 11003
NORTH SOLAR 0 23 0.4 0 PEOPLE 50
TRANS 0 0.56 28 0 LIGHTING
WALL 0 0.36 28 0 VENTILATION
SOUTH SOLAR 305 12 0.4 1,466 CFM/SQFT 0.06
TRANS 305 0.56 28 4,788 CFM/PERSON 7.5
WALL 113 0.36 28 1,134 PERSON/1000 SFT
PARTITION 341 0.36 23 2,824 SELECTED CFM 426
FLOOR 845 0.21 30 5,324 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 50 270 13,500 R.A. GAIN 0
LIGHTING 1268 3.4 1.25 5,387 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 1268 3.4 4,310 SOLAR: 8.0 AM
INFILTRATION 0 1.08 28 0 NORTH 23
O.A. BYPASS 425.7 0.1 1.08 28 1,287 SOUTH 12
EAST 163
SUB TOTAL 40,020 WEST 12
DUCT LOSSES, ETC. 4,002 NORTH-EAST 138
ROOM SENSIBLE HEAT 44,022 NORTH-WEST 12
PEOPLE 50 195 9,750 SOUTH-EAST 85
STEAM SOUTH-WEST 12
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56
O.A. BYPASS 426 0.68 0.1 72.3 2,093 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 11,843 CEILING 0.21
OTHER GAINS & SAFETY 1,184 FLOOR 0.21
ROOM LATENT HEAT 13,027
ROOM TOTAL HEAT 57,049 NOTE:-
OUTSIDE SEN HEAT 425.7 1.08 0.9 28 11,586 LIGHTING LOAD- 1.5
AIR LAT HEAT 425.7 0.68 0.9 72.3 18,836 EQUIP. LOAD- 1.5
RETURN AIR GAIN
GRAND SUB TOTAL 87,471
OTHER GAINS & SAFETY 8,747
GRAND TOTAL HEAT 8.0 TR 96217.95 BTU/HR
S.H.F 0.77 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 113.87 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.84
D.H.A 2397.691 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 2398 AREA /TON 105.39
Tons 8.0
16.00 HRS JOB L541

DATE 6-Sep

WB RH GR ENTH
DEG F % BTU
82 47 137.3 45.70
61.5 55 65 27.4
20.5 72.3

SQFT HT = 13 FT Shyam:

as per sitting arrangement


shown in layout

1267.5
0
CFM 50.7
CFM 375 Shyam:

PEOPLE Bar & louges in hotel


application

hru Glass:At 20° N Latitude


4:00PM 12:0PM
23
12 14
12
163
12
138
12
85
Glass
W/sq.ft
W/sq.ft
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS
GF-BANQUET SALES ZONE PEAK
GROUND FLOOR AREA U TD DESIGN DB
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F
TRANS 0 0.56 28 0 OUTSIDE 100
WALL 0 0.36 28 0 INSIDE 72
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28
TRANS 0 0.56 28 0 AREA 150
WALL 0 0.36 28 0 VOLUME 1953
NORTH SOLAR 0 23 0.4 0 PEOPLE 4
TRANS 0 0.56 28 0 LIGHTING
WALL 0 0.36 28 0 VENTILATION
SOUTH SOLAR 109 12 0.4 523 CFM/SQFT 0.06
TRANS 109 0.56 28 1,710 CFM/PERSON 5
WALL 40 0.36 28 405 PERSON/1000 SFT
PARTITION 0 0.36 23 0 SELECTED CFM 29
FLOOR 150 0.21 30 945 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 4 270 1,080 R.A. GAIN 0
LIGHTING 225 3.4 1.25 956 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latit
EQUIPMENT 225 3.4 765 SOLAR: 8.0 AM
INFILTRATION 0 1.08 28 0 NORTH 23
O.A. BYPASS 29 0.1 1.08 28 88 SOUTH 12
EAST 163
SUB TOTAL 6,473 WEST 12
DUCT LOSSES, ETC. 647 NORTH-EAST 138
ROOM SENSIBLE HEAT 7,120 NORTH-WEST 12
PEOPLE 4 195 780 SOUTH-EAST 85
STEAM SOUTH-WEST 12
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56
O.A. BYPASS 29 0.68 0.1 72.3 143 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 923 CEILING 0.21
OTHER GAINS & SAFETY 92 FLOOR 0.21
ROOM LATENT HEAT 1,015
ROOM TOTAL HEAT 8,135 NOTE:-
OUTSIDE SEN HEAT 29 1.08 0.9 28 789 LIGHTING LOAD- 1.5
AIR LAT HEAT 29 0.68 0.9 72.3 1,283 EQUIP. LOAD- 1.5
RETURN AIR GAIN
GRAND SUB TOTAL 10,207
OTHER GAINS & SAFETY 1,021
GRAND TOTAL HEAT 0.9 TR 11227.74 BTU/HR
S.H.F 0.88 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 74.85 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.59
D.H.A 387.7865 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 388 AREA /TON 160.32
Tons 0.9
16.00 HRS JOB L541
DATE 6-Sep
WB RH GR ENTH
DEG F % BTU
82 47 137.3 45.70
61.5 55 65 27.4
20.5 72.3
SQFT HT = 13 FT
Shyam:

as per sitting arrangement


shown in layout
225
0
CFM 9
CFM 20
PEOPLE

hru Glass:At 20° N Latitude


4:00PM 12:0PM
23
12 14
12
163
12
138
12
85
Glass
W/sq.ft
W/sq.ft
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
GF- MANAGER CABIN ZONE PEAK DATE 6-Sep
GROUND FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28 20.5 72.3
TRANS 0 0.56 28 0 AREA 96 SQFT HT = 13 FT
WALL 98 0.36 28 989 VOLUME 1250
NORTH SOLAR 0 23 0.4 0 PEOPLE 3
Shyam:
TRANS 0 0.56 28 0 LIGHTING 144
as per sitting arrange
WALL 0 0.36 28 0 VENTILATION 0 shown in layout
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 5.76
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 15
WALL 0 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 0 0.36 23 0 SELECTED CFM 21
FLOOR 96 0.21 30 605 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 144 3.4 1.25 612 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 144 3.4 490 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 20.76 0.1 1.08 28 63 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 3,568 WEST 12 163
DUCT LOSSES, ETC. 357 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 3,925 NORTH-WEST 12 138
PEOPLE 3 195 585 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 21 0.68 0.1 72.3 102 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 687 CEILING 0.21
OTHER GAINS & SAFETY 69 FLOOR 0.21
ROOM LATENT HEAT 756
ROOM TOTAL HEAT 4,680 NOTE:-
OUTSIDE SEN HEAT 20.76 1.08 0.9 28 565 LIGHTING LOAD- 1.5 W/sq.ft
AIR LAT HEAT 20.76 0.68 0.9 72.3 919 EQUIP. LOAD- 1.5 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 6,164
OTHER GAINS & SAFETY 616
GRAND TOTAL HEAT 0.6 TR 6780.26 BTU/HR
S.H.F 0.84 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 70.63 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.23
D.H.A 213.75373 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 214 AREA /TON 169.90
Tons 0.6
Shyam:

as per sitting arrangement


shown in layout
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS
GF-BACK OFFICE ZONE PEAK
GROUND FLOOR AREA U TD DESIGN DB
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F
TRANS 0 0.56 28 0 OUTSIDE 100
WALL 0 0.36 28 0 INSIDE 72
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28
TRANS 0 0.56 28 0 AREA 65
WALL 64 0.36 28 645 VOLUME 846
NORTH SOLAR 0 23 0.4 0 PEOPLE 3
TRANS 0 0.56 28 0 LIGHTING
WALL 0 0.36 28 0 VENTILATION
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06
TRANS 0 0.56 28 0 CFM/PERSON 5
WALL 171 0.36 28 1,719 PERSON/1000 SFT
PARTITION 0 0.36 23 0 SELECTED CFM 19
FLOOR 65 0.21 30 410 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 98 3.4 1.25 414 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 98 3.4 332 SOLAR: 8.0 AM
INFILTRATION 0 1.08 28 0 NORTH 23
O.A. BYPASS 18.9 0.1 1.08 28 57 SOUTH 12
EAST 163
SUB TOTAL 4,386 WEST 12
DUCT LOSSES, ETC. 439 NORTH-EAST 138
ROOM SENSIBLE HEAT 4,825 NORTH-WEST 12
PEOPLE 3 195 585 SOUTH-EAST 85
STEAM SOUTH-WEST 12
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56
O.A. BYPASS 19 0.68 0.1 72.3 93 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 678 CEILING 0.21
OTHER GAINS & SAFETY 68 FLOOR 0.21
ROOM LATENT HEAT 746
ROOM TOTAL HEAT 5,571 NOTE:-
OUTSIDE SEN HEAT 18.9 1.08 0.9 28 514 LIGHTING LOAD- 1.5
AIR LAT HEAT 18.9 0.68 0.9 72.3 836 EQUIP. LOAD- 1.5
RETURN AIR GAIN
GRAND SUB TOTAL 6,922
OTHER GAINS & SAFETY 692
GRAND TOTAL HEAT 0.6 TR 7613.66 BTU/HR
S.H.F 0.87 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 117.13 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 4.04
D.H.A 262.80715 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 263 AREA /TON 102.45
Tons 0.6
16.00 HRS JOB L541
DATE 6-Sep
WB RH GR ENTH
DEG F % BTU
82 47 137.3 45.70
61.5 55 65 27.4
20.5 72.3 Shyam:
SQFT HT = 13 FT
as per sitting arrangement
shown in layout

97.5
0
CFM 3.9
CFM 15
PEOPLE

u Glass:At 20° N Latitude


4:00PM 12:0PM
23
12 14
12
163
12
138
12
85
Glass
W/sq.ft
W/sq.ft
CENTRE POINT HOTEL SUMMER SUMMARY 8.00 HRS
GF-LIFT LOBBY ZONE PEAK
GROUND FLOOR AREA U TD DESIGN DB
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F
TRANS 0 0.56 28 0 OUTSIDE 100
WALL 0 0.36 28 0 INSIDE 72
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28
TRANS 0 0.56 28 0 AREA 330
WALL 64 0.36 28 645 VOLUME 4297
SW SOLAR 0 12 0.4 0 PEOPLE 10
TRANS 0 0.56 28 0 LIGHTING
WALL 107 0.36 28 1,075 VENTILATION
SE SOLAR 0 85 0.4 0 CFM/SQFT 0.06
TRANS 0 0.56 28 0 CFM/PERSON 5
WALL 235 0.36 28 2,364 PERSON/1000 SFT
PARTITION 247 0.36 23 2,048 SELECTED CFM 70
FLOOR 330 0.21 30 2,079 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 10 270 2,700 R.A. GAIN 0
LIGHTING 413 3.4 1.25 1,753 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 165 3.4 561 SOLAR: 8.0 AM
INFILTRATION 0 1.08 28 0 NORTH 23
O.A. BYPASS 69.8 0.1 1.08 28 211 SOUTH 12
EAST 163
SUB TOTAL 13,435 WEST 12
DUCT LOSSES, ETC. 1,344 NORTH-EAST 138
ROOM SENSIBLE HEAT 14,779 NORTH-WEST 12
PEOPLE 10 195 1,950 SOUTH-EAST 85
STEAM SOUTH-WEST 12
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56
O.A. BYPASS 70 0.68 0.1 72.3 343 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 2,293 CEILING 0.21
OTHER GAINS & SAFETY 229 FLOOR 0.21
ROOM LATENT HEAT 2,522
ROOM TOTAL HEAT 17,301 NOTE:-
OUTSIDE SEN HEAT 69.8 1.08 0.9 28 1,900 LIGHTING LOAD- 1.25
AIR LAT HEAT 69.8 0.68 0.9 72.3 3,088 EQUIP. LOAD- 0.5
RETURN AIR GAIN
GRAND SUB TOTAL 22,289
OTHER GAINS & SAFETY 2,229
GRAND TOTAL HEAT 2.0 TR 24518.24 BTU/HR
S.H.F 0.85 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 74.30 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.44
D.H.A 804.93818 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 805 AREA /TON 161.51
Tons 2.0
8.00 HRS JOB L541
DATE 6-Sep
WB RH GR ENTH
DEG F % BTU
82 47 137.3 45.70
61.5 55 65 27.4
20.5 72.3
SQFT HT = 13 FT

412.5
0
CFM 19.8
CFM 50
PEOPLE

u Glass:At 20° N Latitude


4:00PM 12:0PM
23
12 14
12
163
12
138
12
85
Glass
W/sq.ft
W/sq.ft
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
GF-LOBBY & RECP. ZONE PEAK DATE 6-Sep
GROUND FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 101 163 0.4 6,585 DIFFERENCE 28 20.5 72.3
TRANS 101 0.56 28 1,584 AREA 2100 SQFT HT = 13 FT
WALL 415 0.36 28 4,183 VOLUME 27345
Shyam:
NORTH SOLAR 0 23 0.4 0 PEOPLE 80
as per sitting
TRANS 0 0.56 28 0 LIGHTING 3150 shown in layo
WALL 0 0.36 28 0 VENTILATION 0
SOUTH SOLAR 43 12 0.4 205 CFM/SQFT 0.06 CFM 126
TRANS 43 0.56 28 669 CFM/PERSON 5 CFM 400
WALL 68 0.36 28 688 PERSON/1000 SFT PEOPLE
PARTITION 1023 0.36 23 8,473 SELECTED CFM 526
FLOOR 2100 0.21 30 13,230 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 80 270 21,600 R.A. GAIN 0
LIGHTING 3150 3.4 1.25 13,388 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 2625 3.4 8,925 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 526 0.1 1.08 28 1,591 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 81,120 WEST 12 163
DUCT LOSSES, ETC. 8,112 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 89,232 NORTH-WEST 12 138
PEOPLE 80 195 15,600 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 526 0.68 0.1 72.3 2,586 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 18,186 CEILING 0.21
OTHER GAINS & SAFETY 1,819 FLOOR 0.21
ROOM LATENT HEAT 20,005
ROOM TOTAL HEAT 109,236 NOTE:-
OUTSIDE SEN HEAT 526 1.08 0.9 28 14,316 LIGHTING LOAD- 1.5 W/sq.ft
AIR LAT HEAT 526 0.68 0.9 72.3 23,274 EQUIP. LOAD- 1.25 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 146,826
OTHER GAINS & SAFETY 14,683
GRAND TOTAL HEAT 13.5 TR 161508.63 BTU/HR
S.H.F 0.82 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 76.91 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.31
D.H.A 4860.1061 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 4860 AREA /TON 156.03
Tons 13.5
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F- ROOM 01 02 ZONE PEAK DATE 6-Sep
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 35 163 0.4 2,282 DIFFERENCE 28 20.5 72.3
TRANS 35 0.56 28 549 AREA 332 SQFT HT = 12 FT
WALL 100 0.36 28 1,008 VOLUME 3984
NORTH SOLAR 0 23 0.4 0 PEOPLE 3
TRANS 0 0.56 28 0 LIGHTING 332
WALL 0 0.36 28 0 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 19.92
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 15
WALL 340 0.36 28 3,427 PERSON/1000 SFT PEOPLE
PARTITION 138 0.36 23 1,141 SELECTED CFM 35
FLOOR 0 0.21 30 0 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 332 3.4 1.25 1,411 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 332 3.4 1,129 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 34.92 0.1 1.08 28 106 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 11,862 WEST 12 163
DUCT LOSSES, ETC. 1,186 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 13,048 NORTH-WEST 12 138
PEOPLE 3 195 585 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 35 0.68 0.1 72.3 172 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 757 CEILING 0.21
OTHER GAINS & SAFETY 76 FLOOR 0.21
ROOM LATENT HEAT 832
ROOM TOTAL HEAT 13,881 NOTE:-
OUTSIDE SEN HEAT 0 1.08 0.9 28 0 LIGHTING LOAD- 1 W/sq.ft
AIR LAT HEAT 0 0.68 0.9 72.3 0 EQUIP. LOAD- 1 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 13,881
OTHER GAINS & SAFETY 1,388
GRAND TOTAL HEAT 1.3 TR 15268.67 BTU/HR
S.H.F 0.94 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 45.99 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.14
D.H.A 710.68932 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 711 AREA /TON 260.93
Tons 1.3
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F- ROOM 03 04 05 ZONE PEAK DATE 6-Sep
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 35 163 0.4 2,282 DIFFERENCE 28 20.5 72.3
TRANS 35 0.56 28 549 AREA 290 SQFT HT = 12 FT
WALL 80 0.36 28 806 VOLUME 3480
NORTH SOLAR 0 23 0.4 0 PEOPLE 3
TRANS 0 0.56 28 0 LIGHTING 290
WALL 0 0.36 28 0 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 17.4
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 15
WALL 0 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 138 0.36 23 1,141 SELECTED CFM 32
FLOOR 0 0.21 30 0 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 290 3.4 1.25 1,233 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 290 3.4 986 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 32.4 0.1 1.08 28 98 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 7,904 WEST 12 163
DUCT LOSSES, ETC. 790 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 8,695 NORTH-WEST 12 138
PEOPLE 3 195 585 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 32 0.68 0.1 72.3 159 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 744 CEILING 0.21
OTHER GAINS & SAFETY 74 FLOOR 0.21
ROOM LATENT HEAT 819
ROOM TOTAL HEAT 9,513 NOTE:-
OUTSIDE SEN HEAT 0 1.08 0.9 28 0 LIGHTING LOAD- 1 W/sq.ft
AIR LAT HEAT 0 0.68 0.9 72.3 0 EQUIP. LOAD- 1 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 9,513
OTHER GAINS & SAFETY 951
GRAND TOTAL HEAT 0.9 TR 10464.83 BTU/HR
S.H.F 0.91 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 36.09 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 1.63
D.H.A 473.57099 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 474 AREA /TON 332.54
Tons 0.9
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F- ROOM 06 ZONE PEAK DATE 6-Sep
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 35 163 0.4 2,282 DIFFERENCE 28 20.5 72.3
TRANS 35 0.56 28 549 AREA 530 SQFT HT = 12 FT
WALL 145 0.36 28 1,462 VOLUME 6360
NORTH SOLAR 0 23 0.4 0 PEOPLE 5
TRANS 0 0.56 28 0 LIGHTING 530
WALL 384 0.36 28 3,871 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 31.8
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 25
WALL 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 138 0.36 23 1,141 SELECTED CFM 57
FLOOR 0 0.21 30 0 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 5 270 1,350 R.A. GAIN 0
LIGHTING 530 3.4 1.25 2,253 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 530 3.4 1,802 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 56.8 0.1 1.08 28 172 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 14,880 WEST 12 163
DUCT LOSSES, ETC. 1,488 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 16,368 NORTH-WEST 12 138
PEOPLE 5 195 975 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 57 0.68 0.1 72.3 279 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 1,254 CEILING 0.21
OTHER GAINS & SAFETY 125 FLOOR 0.21
ROOM LATENT HEAT 1,380
ROOM TOTAL HEAT 17,748 NOTE:-
OUTSIDE SEN HEAT 0 1.08 0.9 28 0 LIGHTING LOAD- 1 W/sq.ft
AIR LAT HEAT 0 0.68 0.9 72.3 0 EQUIP. LOAD- 1 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 17,748
OTHER GAINS & SAFETY 1,775
GRAND TOTAL HEAT 1.6 TR 19522.49 BTU/HR
S.H.F 0.92 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 36.83 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 1.68
D.H.A 891.50542 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 892 AREA /TON 325.78
Tons 1.6
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F- RM 7 8 9 10 11 ZONE PEAK DATE 6-Sep
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28 20.5 72.3
TRANS 0 0.56 28 0 AREA 225 SQFT HT = 12 FT
WALL 0 0.36 28 0 VOLUME 2700
NORTH SOLAR 70 23 0.4 644 PEOPLE 3
TRANS 70 0.56 28 1,098 LIGHTING 281.25
WALL 35 0.36 28 353 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 13.5
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 15
WALL 0 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 138 0.36 23 1,141 SELECTED CFM 29
FLOOR 225 0.21 30 1,418 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 281 3.4 1.25 1,195 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 225 3.4 765 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 28.5 0.1 1.08 28 86 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 7,509 WEST 12 163
DUCT LOSSES, ETC. 751 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 8,260 NORTH-WEST 12 138
PEOPLE 3 195 585 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 29 0.68 0.1 72.3 140 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 725 CEILING 0.21
OTHER GAINS & SAFETY 73 FLOOR 0.21
ROOM LATENT HEAT 798
ROOM TOTAL HEAT 9,058 NOTE:-
OUTSIDE SEN HEAT 28.5 1.08 0.9 28 776 LIGHTING LOAD- 1.25 W/sq.ft
AIR LAT HEAT 28.5 0.68 0.9 72.3 1,261 EQUIP. LOAD- 1 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 11,094
OTHER GAINS & SAFETY 1,109
GRAND TOTAL HEAT 1.0 TR 12203.73 BTU/HR
S.H.F 0.91 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 54.24 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.00
D.H.A 449.88857 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 450 AREA /TON 221.24
Tons 1.0
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F- ROOM 12 ZONE PEAK DATE 6-Sep
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 228 0.36 28 2,301 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28 20.5 72.3
TRANS 0 0.56 28 0 AREA 290 SQFT HT = 12 FT
WALL 0 0.36 28 0 VOLUME 3480
NORTH SOLAR 35 23 0.4 322 PEOPLE 3
TRANS 35 0.56 28 549 LIGHTING 290
WALL 112 0.36 28 1,129 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 17.4
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 15
WALL 0 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 138 0.36 23 1,141 SELECTED CFM 32
FLOOR 290 0.21 30 1,827 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 290 3.4 1.25 1,233 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 290 3.4 986 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 32.4 0.1 1.08 28 98 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 10,395 WEST 12 163
DUCT LOSSES, ETC. 1,040 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 11,435 NORTH-WEST 12 138
PEOPLE 3 195 585 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 32 0.68 0.1 72.3 159 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 744 CEILING 0.21
OTHER GAINS & SAFETY 74 FLOOR 0.21
ROOM LATENT HEAT 819
ROOM TOTAL HEAT 12,253 NOTE:-
OUTSIDE SEN HEAT 0 1.08 0.9 28 0 LIGHTING LOAD- 1 W/sq.ft
AIR LAT HEAT 0 0.68 0.9 72.3 0 EQUIP. LOAD- 1 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 12,253
OTHER GAINS & SAFETY 1,225
GRAND TOTAL HEAT 1.1 TR 13478.58 BTU/HR
S.H.F 0.93 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 46.48 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.15
D.H.A 622.79612 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 623 AREA /TON 258.19
Tons 1.1
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F- ROOM 13 ZONE PEAK DATE 5-Feb
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 80 163 0.4 5,216 CRITERIA DEG F DEG F % BTU
TRANS 80 0.56 28 1,254 OUTSIDE 100 82 47 137.3 45.70
WALL 35 0.36 28 353 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 0 12 0.4 0 DIFFERENCE 28 20.5 72.3
TRANS 0 0.56 28 0 AREA 225 SQFT HT = 12 FT
WALL 0 0.36 28 0 VOLUME 2700
NORTH SOLAR 0 23 0.4 0 PEOPLE 3
TRANS 0 0.56 28 0 LIGHTING 281.25
WALL 0 0.36 28 0 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 13.5
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 15
WALL 0 0.36 28 0 PERSON/1000 SFT PEOPLE
PARTITION 138 0.36 23 1,141 SELECTED CFM 29
FLOOR 225 0.21 30 1,418 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 281 3.4 1.25 1,195 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 225 3.4 765 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 28.5 0.1 1.08 28 86 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 12,238 WEST 12 163
DUCT LOSSES, ETC. 1,224 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 13,462 NORTH-WEST 12 138
PEOPLE 3 195 585 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 29 0.68 0.1 72.3 140 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 725 CEILING 0.21
OTHER GAINS & SAFETY 73 FLOOR 0.21
ROOM LATENT HEAT 798
ROOM TOTAL HEAT 14,259 NOTE:-
OUTSIDE SEN HEAT 28.5 1.08 0.9 28 776 LIGHTING LOAD- 1.25 W/sq.ft
AIR LAT HEAT 28.5 0.68 0.9 72.3 1,261 EQUIP. LOAD- 1 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 16,296
OTHER GAINS & SAFETY 1,630
GRAND TOTAL HEAT 1.5 TR 17925.57 BTU/HR
S.H.F 0.94 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 79.67 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 3.26
D.H.A 733.20448 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 733 AREA /TON 150.62
Tons 1.5
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS
1F- RM 14 15 16 17 ZONE PEAK
1ST FLOOR AREA U TD DESIGN DB
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F
TRANS 0 0.56 28 0 OUTSIDE 100
WALL 0 0.36 28 0 INSIDE 72
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28
TRANS 0 0.56 28 0 AREA 240
WALL 0 0.36 28 0 VOLUME 2880
NORTH SOLAR 0 23 0.4 0 PEOPLE 3
TRANS 0 0.56 28 0 LIGHTING
WALL 0 0.36 28 0 VENTILATION
SOUTH SOLAR 70 12 0.4 336 CFM/SQFT 0.06
TRANS 70 0.56 28 1,098 CFM/PERSON 5
WALL 60 0.36 28 605 PERSON/1000 SFT
PARTITION 138 0.36 23 1,141 SELECTED CFM 29
FLOOR 240 0.21 30 1,512 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 3 270 810 R.A. GAIN 0
LIGHTING 300 3.4 1.25 1,275 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 240 3.4 816 SOLAR: 8.0 AM
INFILTRATION 0 1.08 28 0 NORTH 23
O.A. BYPASS 29.4 0.1 1.08 28 89 SOUTH 12
EAST 163
SUB TOTAL 7,681 WEST 12
DUCT LOSSES, ETC. 768 NORTH-EAST 138
ROOM SENSIBLE HEAT 8,449 NORTH-WEST 12
PEOPLE 3 195 585 SOUTH-EAST 85
STEAM SOUTH-WEST 12
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56
O.A. BYPASS 29 0.68 0.1 72.3 145 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 730 CEILING 0.21
OTHER GAINS & SAFETY 73 FLOOR 0.21
ROOM LATENT HEAT 802
ROOM TOTAL HEAT 9,252 NOTE:-
OUTSIDE SEN HEAT 29.4 1.08 0.9 28 800 LIGHTING LOAD- 1.25
AIR LAT HEAT 29.4 0.68 0.9 72.3 1,301 EQUIP. LOAD- 1
RETURN AIR GAIN
GRAND SUB TOTAL 11,353
OTHER GAINS & SAFETY 1,135
GRAND TOTAL HEAT 1.0 TR 12487.84 BTU/HR
S.H.F 0.91 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 52.03 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 1.92
D.H.A 460.18814 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 460 AREA /TON 230.62
Tons 1.0
16.00 HRS JOB L541
DATE 5-Feb
WB RH GR ENTH
DEG F % BTU
82 47 137.3 45.70
61.5 55 65 27.4
20.5 72.3
SQFT HT = 12 FT

300
0
CFM 14.4
CFM 15
PEOPLE

u Glass:At 20° N Latitude


4:00PM 12:0PM
23
12 14
12
163
12
138
12
85
Glass
W/sq.ft
W/sq.ft
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F- OFFICE TYP. ZONE PEAK DATE 5-Feb
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 0 0.36 28 0 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 59 163 0.4 3,849 DIFFERENCE 28 20.5 72.3
TRANS 59 0.56 28 926 AREA 160 SQFT HT = 12 FT
WALL 98 0.36 28 988 VOLUME 1920
NORTH SOLAR 0 23 0.4 0 PEOPLE 4
TRANS 0 0.56 28 0 LIGHTING 200
WALL 0 0.36 28 0 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 9.6
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 20
WALL 146 0.36 28 1,468 PERSON/1000 SFT PEOPLE
PARTITION 138 0.36 23 1,141 SELECTED CFM 30
FLOOR 160 0.21 30 1,008 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 4 270 1,080 R.A. GAIN 0
LIGHTING 200 3.4 1.25 850 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 200 3.4 680 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 29.6 0.1 1.08 28 90 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 12,079 WEST 12 163
DUCT LOSSES, ETC. 1,208 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 13,287 NORTH-WEST 12 138
PEOPLE 4 195 780 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 30 0.68 0.1 72.3 146 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 926 CEILING 0.21
OTHER GAINS & SAFETY 93 FLOOR 0.21
ROOM LATENT HEAT 1,018
ROOM TOTAL HEAT 14,305 NOTE:-
OUTSIDE SEN HEAT 29.6 1.08 0.9 28 806 LIGHTING LOAD- 1.25 W/sq.ft
AIR LAT HEAT 29.6 0.68 0.9 72.3 1,310 EQUIP. LOAD- 1.25 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 16,420
OTHER GAINS & SAFETY 1,642
GRAND TOTAL HEAT 1.5 TR 18062.49 BTU/HR
S.H.F 0.93 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 112.89 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 4.52
D.H.A 723.69509 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 724 AREA /TON 106.30
Tons 1.5
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS
1F-ADMIN STAFF ZONE PEAK
1ST FLOOR AREA U TD DESIGN DB
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F
TRANS 0 0.56 28 0 OUTSIDE 100
WALL 472 0.36 28 4,761 INSIDE 72
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28
TRANS 0 0.56 28 0 AREA 455
WALL 0 0.36 28 0 VOLUME 5460
NORTH SOLAR 0 23 0.4 0 PEOPLE 20
TRANS 0 0.56 28 0 LIGHTING
WALL 0 0.36 28 0 VENTILATION
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06
TRANS 0 0.56 28 0 CFM/PERSON 5
WALL 134 0.36 28 1,349 PERSON/1000 SFT
PARTITION 134 0.36 23 1,110 SELECTED CFM 127
FLOOR 455 0.21 30 2,867 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 20 270 5,400 R.A. GAIN 0
LIGHTING 455 3.4 1.25 1,934 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 455 3.4 1,547 SOLAR: 8.0 AM
INFILTRATION 0 1.08 28 0 NORTH 23
O.A. BYPASS 127.3 0.1 1.08 28 385 SOUTH 12
EAST 163
SUB TOTAL 19,352 WEST 12
DUCT LOSSES, ETC. 1,935 NORTH-EAST 138
ROOM SENSIBLE HEAT 21,287 NORTH-WEST 12
PEOPLE 20 195 3,900 SOUTH-EAST 85
STEAM SOUTH-WEST 12
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56
O.A. BYPASS 127 0.68 0.1 72.3 626 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 4,526 CEILING 0.21
OTHER GAINS & SAFETY 453 FLOOR 0.21
ROOM LATENT HEAT 4,978
ROOM TOTAL HEAT 26,265 NOTE:-
OUTSIDE SEN HEAT 127.3 1.08 0.9 28 3,465 LIGHTING LOAD- 1
AIR LAT HEAT 127.3 0.68 0.9 72.3 5,633 EQUIP. LOAD- 1
RETURN AIR GAIN
GRAND SUB TOTAL 35,363
OTHER GAINS & SAFETY 3,536
GRAND TOTAL HEAT 3.2 TR 38898.84 BTU/HR
S.H.F 0.81 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 85.49 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.55
D.H.A 1159.413 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 1159 AREA /TON 140.36
Tons 3.2
16.00 HRS JOB L541
DATE 5-Feb
WB RH GR ENTH
DEG F % BTU
82 47 137.3 45.70
61.5 55 65 27.4
20.5 72.3
SQFT HT = 12 FT

455
0
CFM 27.3
CFM 100
PEOPLE

u Glass:At 20° N Latitude


4:00PM 12:0PM
23
12 14
12
163
12
138
12
85
Glass
W/sq.ft
W/sq.ft
CENTRE POINT HOTEL SUMMER SUMMARY 16.00 HRS JOB L541
1F-A ZONE PEAK DATE 5-Feb
1ST FLOOR AREA U TD DESIGN DB WB RH GR ENTH
EAST SOLAR 0 12 0.4 0 CRITERIA DEG F DEG F % BTU
TRANS 0 0.56 28 0 OUTSIDE 100 82 47 137.3 45.70
WALL 472 0.36 28 4,761 INSIDE 72 61.5 55 65 27.4
WEST SOLAR 0 163 0.4 0 DIFFERENCE 28 20.5 72.3
TRANS 0 0.56 28 0 AREA 455 SQFT HT = 12 FT
WALL 0 0.36 28 0 VOLUME 5460
NORTH SOLAR 0 23 0.4 0 PEOPLE 20
TRANS 0 0.56 28 0 LIGHTING 455
WALL 0 0.36 28 0 VENTILATION 0
SOUTH SOLAR 0 12 0.4 0 CFM/SQFT 0.06 CFM 27.3
TRANS 0 0.56 28 0 CFM/PERSON 5 CFM 100
WALL 134 0.36 28 1,349 PERSON/1000 SFT PEOPLE
PARTITION 134 0.36 23 1,110 SELECTED CFM 127
FLOOR 455 0.21 30 2,867 SHADING 0.40
CEILING / ROOF 0 0.21 20 0 STORAGE -
PEOPLE 20 270 5,400 R.A. GAIN 0
LIGHTING 455 3.4 1.25 1,934 NOTES :
PARTITION-2 0 0.56 25 0 Solar Heat Gain Thru Glass:At 20° N Latitude
EQUIPMENT 455 3.4 1,547 SOLAR: 8.0 AM 4:00PM 12:0PM
INFILTRATION 0 1.08 28 0 NORTH 23 23
O.A. BYPASS 127.3 0.1 1.08 28 385 SOUTH 12 12 14
EAST 163 12
SUB TOTAL 19,352 WEST 12 163
DUCT LOSSES, ETC. 1,935 NORTH-EAST 138 12
ROOM SENSIBLE HEAT 21,287 NORTH-WEST 12 138
PEOPLE 20 195 3,900 SOUTH-EAST 85 12
STEAM SOUTH-WEST 12 85
INFILTRATION 0 0 72.3 0 TRANSMISSION: 0.56 Glass
O.A. BYPASS 127 0.68 0.1 72.3 626 INTERNAL WALL 0.36
EXTERNAL WALL 0.36
SUB TOTAL 4,526 CEILING 0.21
OTHER GAINS & SAFETY 453 FLOOR 0.21
ROOM LATENT HEAT 4,978
ROOM TOTAL HEAT 26,265 NOTE:-
OUTSIDE SEN HEAT 127.3 1.08 0.9 28 3,465 LIGHTING LOAD- 1 W/sq.ft
AIR LAT HEAT 127.3 0.68 0.9 72.3 5,633 EQUIP. LOAD- 1 W/sq.ft
RETURN AIR GAIN
GRAND SUB TOTAL 35,363
OTHER GAINS & SAFETY 3,536
GRAND TOTAL HEAT 3.2 TR 38898.84 BTU/HR
S.H.F 0.81 SPEC IFIC LOAD
A.D.P 52 BTU /SQ.FT. 85.49 DESIGNED BY: SHYAM
D.H.R 17 CFM /SQ.FT. 2.55
D.H.A 1159.413 D.H.A. /1000 BTU SEN.H. 54.47 CHECKED BY: GOUTHAM
TOTAL AIR 1159 AREA /TON 140.36
Tons 3.2