COOLING/HEATING & DEHUMIDIFICATION LOAD ESTIMATE

SHEET : DATE:
PREPARED BY: DINKAR PROP NO: JOB NO:
NAME OF JOB: MEP SIMPLE LAYOUT
LOCATION: NEW ZEALAND Break Fast Area APPROVED: _____________________
SPACE USED FOR: HOUSE (GROUND FLOOR)

SIZE: 16 L in ft x 15 w in ft 240 Sq Ftx 12 Ht in ft 2,880.00 Cu Ft Load for winter


Local Time Local Time
Item Area or Quantity Sun Gain or Temp. Diff. Factor Btu/hr Estimate For Peak Load 4:00 PM
SunTime SunTime
SOLAR GAIN - GLASS Hours Of Operation 24 Daily Range 22
E Glass 8 Sq Ft x 11 x 0.26 23 CONDITION DB('F) WB('F) % RH DP GR/LB
S Glass 0 Sq Ft x 11 x 0.26 0 OutDoor Air 43 36 45 28 22
W Glass 0 Sq Ft x 164 x 0.26 0 Room Air 73 61 50 53.4 55
N Glass 8 Sq Ft x 15 x 0.26 31 Difference 30 xxx xxx xxx -33
NE Glass 0 Sq Ft x 11 x 0.26 0 OUTDOOR AIR
SE Glass 0 Sq Ft x 11 x 0.26 0 2 People x CFM / Person = 70
SW Glass 0 Sq Ft x 98.9 x 0.26 0 Ventilation Sq. Ft. x CFM / Sq. Ft. =
NW Glass 0 Sq Ft x 126.9 x 0.26 0 CFM Ventilation = 70
Swinging / Revolving Doors People x CFM / Person = 0
SOLAR & TRANS. GAIN - WALLS & ROOF Open Doors Doors X CFM/Door = 0
E wall 152 Sq Ft x 30 (18+12) x 0.36 1642 Infiltration Exhaust Fan = nos. x = 0
S wall 0 Sq Ft x 28 (16+12) x 0.36 0 Crack Feet x CFM/Ft = 0
W wall 0 Sq Ft x 24 (12+12) x 0.36 0 CFM Infiltration = 0
N wall 172 Sq Ft x 16 (4+12) x 0.36 991 CFM Outdoor Air Thro Apparatus = 69.84 CFMOA
NE wall 0 Sq Ft x 22 (10+12) x 0.36 0 APPARATUS DEWPOINT
SE wall 0 Sq Ft x 30 (18+12) x 0.36 0 ESHF Effective Sensible Heat Factor = ERSH / ERTH = 1
0 0
SW wall 0 Sq Ft x 26 (14+12) x 0.36 0 ADP Indicated ADP = 52 F Selected ADP = 52 F
NW wall 0 Sq Ft x 18 (6+12) x 0.36 0 DEHUMIDIFIED AIR QUANTITY
0
Roof-Sun 240 Sq Ft x 47 (35+12) x 0.2 2256 Temp Rise 0.85 x ( TRM 73 F - TADP 52 F ) = 17.85 F CFMD
Rf-Shaded 0 Sq Ft x x 0.45 0 Deh CFM 10537 /( 1.08 x 17.85 FTEMP RISE ) = 547 A

TRANS. GAIN - EXCEPT WALLS & ROOF


All Glass 16 Sq Ft x 30 x 0.8 384 Notes :
Partition 200 Sq Ft x 18 x 0.42 1512 L (ft) H (ft) Area(Sq ft) glass Area(Sq Effective Wall Area (Sq ft)
Ceiling 0 Sq Ft x 18 x 0.25 0 East Wall 16 10 160 8 152
Floor 0 Sq Ft x 18 x 0.25 0 South Wall 0 10 0 0 0
Infiltration 0 CFM x 30 x 1.08 0 West Wall 0 10 0 0 0
0
OA: 69.84 CFM x 30 Fx 0.15 BF x 1.08 339 North Wall 18 10 180 8 172
INTERNAL HEAT NE Wall 0 10 0 0 0
People 1 People x 245 245 SE Wall 0 10 0 0 0
Power 0 HP or KW x 3412 0 SW Wall 0 10 0 0 0
Light 500 Wattsx 1 xDiversityx 3.4 x 1 1700 NW Wall 0 10 0 0 0

Appliances 0 Watts x 1 xDivtyx 3.4 0 Partition 20 10 200


Add. HG x 0 Roof
Sub Total = 9123 Lighting Load Diversity = 100 %
Safety Factor 10 % 912 Equipment Load Diversity = 100 %
Room Sensible Heat = 10035
Heat Supply Duct % Fan H.P. % Sum
Gain = Leak. Loss= 5 502
Effective Room Sensible Heat = 10,537.00
LATENT HEAT
Infiltration 0 CFM x -33 Gr/lbx 0.68 0
OA: 70 CFM x -33 Gr/lb x 0.15 BF x 0.68 -235
People 1 People x 205 205
Steam lb/hr x 1050 0
Applian 0 Watts x 3.41 0
Add. HG Watts x 3.41 0
Vap Trans. Sq Ft x 0.01 x -33 Gr/lb x 0
Sub Total = -30
Safety Factor 10 % -3
Room Latent Heat = -33
Supply Duct Leak Loss 5 % -2
Effective Room Latent Heat = -35
Effective Room Total Heat = 10,502.00
OUTDOOR AIR HEAT
Sen 69.84 CFM x 30 xFx 0.85 x 1.08 1923
Lat 69.84 CFM x -33 xGr/lbx 0.85 x 0.68 -1332
Sub Total = 591
Pump H.P De.&P.lo
Return Duct % % ss% Sum
Heat Leak. Gain = 5 30
MEP LAYOUT
Grant Total Heat= 11,123.00 Btu/hr ( 0.926916667 TR )