Professional Documents
Culture Documents
Installation - MCD SV1801 en 0698 0203
Installation - MCD SV1801 en 0698 0203
Installation - MCD SV1801 en 0698 0203
ILLUSION
Split System
Concealed Type
MCD Series 50/60 Hz
General Information 2
System Appearance 4
Location and Preparation of Units 6
Units Installation 7
Connection of Refrigerant Tubing 9
Condensate Drain Piping 10
Electrical Installation 11
Wiring Diagram 12
Dimensional Data 15
Maintenance 18
MS-SVN004-EN 3
Blower
Motor
Outlet Collar
Evaporator Coil
Electric Heater
(Option)
Indoor unit
Outdoor Unit
4 MS-SVN004-EN
Motor
Blower
Outlet Collar
Evaporator Coil
Indoor Unit
Outdoor Unit
MS-SVN004-EN 5
Indoor Unit 2. Before cutting, check that no pipes 1. Tools Required for Installation
1. Select a convenient location that or studs are directly behind the (not supplied)
allows the air to reach every corner place to be cut. Avoid areas where - Level
of the room and where it is easy to electrical wiring or conduits are - Hole saw or saw
route the refrigerant tubing, wiring located. - Core bits
and drain to the outside. 3. Hang the unit on a solid and level - Hammer
2. The ceiling construction should be roof. Noise, vibration or leakage - Drill
strong enough to support the could occur on and unstable - Torque wrench
weight of the unit. foundation (Figure 3,4). - Adjustable wrench
3. The refrigerant tubing, drain piping For correct installation of duct - Standard screwdriver
and wiring conduit are connected work see (Figure 6). - Phillips head screwdriver
through the wall. 4. Support the unit solidly. - Knife or wire stripper
4. Refrigerant tubes between the 5. To have access to electrical - Tape measure
indoor and the outdoor units and terminals, remove the right side - 4 Anchor bolts for ceiling
drain pipes should be as short as junction box (Figure 2). mounting
possible (Figure 1). 6. Note that refrigerant tubing,
5. If a refrigerant charge adjustment is interconnecting wiring and drain 2. Refrigerant Piping and Insulation
necessary, follow the Installation hose should go through the wall. Material
Manual for the Outdoor Unit. Shape these items so that they will - See the Installation Manual
easily fit through the wall. included with the Outdoor Unit.
Outdoor Unit - The length of wiring will determine
See instructions for location and the wire size. See local codes and
preparation of the unit in the Installation refer to Section Electrical
Manual for the Outdoor Unit. Installation.
6 MS-SVN004-EN
CELING
RETURN PLENUM
DETAIL "X" WITH FILTER
I
A WALL
SUPPLY
DUCT B DRAIN PIPE
SLANT 1 : 50
H
F
E C
G
D
FILTER
FLEXIBLE CONNECTER
CHAMBER RETURN AIR GRILLE
FILTER
DRAIN PIPE
J K
CHAMBER
SUPPLY DUCT
A B C D E F G H I J K
DISTANCE (M.M.) Min.750 Min. 800 100 150 50 200 Min. 200 Min. 100 Min. 50 Min. 300 Min. 300
MS-SVN004-EN 7
8 MS-SVN004-EN
Proper installation prodecure is Flare Nut 2. Remove burrs at the end of the
recommended in the Installation copper tube with a tube reamer
Manual Package, usually provided (Figure 8).
together with the outdoor unit. It is 3. There are 2 ways to connect the
advisable to read bofore installing. Copper Tubing copper tube
Flare Tool - Use a coupling between the
The indoor unit refrigerant connections Figure 10 copper tube of Fan Coil Unit and
are located on the left hand side when the copper tube used for
facing the unit (Figure 7). A good flare should have the installation (Figure 13).
following characteristics:
• Inside surface is glossy and smooth.
• Edge is smooth. Copper Tube
• Tapered sides are of uniform of Fan Coil
length. Unit
Solder Coupling
Cautions Before Connecting
Tightly Copper Tube of
Figure 7 1. Be sure to apply a sealing cap or Condensing Unit
water-proof tape to prevent dust or Figure 13
water from getting into the tubes
Connecting the Units with before they are used.
Flaring Procedure. - Expand the copper tube by
2. Be sure to apply refrigerant using a swaging tool set as in
1. Cut the copper tube to the required lubricant to the matching surfaces
length with a tube cutter. It is Figure 14.
of the flare and union before
recommended to cut approx.
connecting them together. This is
20-30 cm. longer than the tubing
effective for reducing gas leaks Swaging Tool
length.
(Figure 11).
2. Remove burrs at the end of the
copper tube with a tube reamer
or file, as shown in Figure 8. Tube Holder
Copper Tube (Clamp)
Torch
CO
MM
Union Flare Nut ET
3
P.V.C. Tape
Insulation Tube
Figure 16
10 MS-SVN004-EN
MS-SVN004-EN 11
BLK
EXTRA–HI
HI BR
1
BLOWER MED BL
MOTOR
2
LOW RD
3
COM WH LOW MED HI
4
3 SPEED SWITCH
THERMOSTAT
L2 L1 C1 C2
POWER SUPPLY
200-240V/1PH/60Hz
NOTE : LEGEND : 220-240V/1PH/50Hz
1. Power wiring and grounding of equipment 200-240 VAC
must comply with local codes. FIELD WIRING CONTROL WIRING
2. Ensure that power supply agrees with TO CONDENSING
FACTORY WIRING
UNIT.
equipment nameplate.
3. Use only copper conductors.
12 MS-SVN004-EN
MS-SVN004-EN 13
HI BR
1
BLOWER MED BL
MOTOR
2
LOW RD
3
COM WH LOW MED HI
4
BLK HEAT
OFF
5 TO HEATING
RD
6
RD
TO COOLING h
0 1 COOL 3 SPEED
2 4 6 8 SWITCH
COOLING-HEATING THERMOSTAT
SWITCH
14 MS-SVN004-EN
HANGER HOLES - X6
SEE VIEW "A"
Ø16
111
32
127
63.5
VIEW "A"
A
B
284 C
252
SUCTION CONNECTION
LIQUID CONNECTION
166
210
234
254
40 174
DRAIN CONN. Ø22.5 MPT
All External Dimensions are in inch (mm.) Refrig. Line Conn. Size Number Of
Model
A B C Suction Liquid Fan(s) Motor(s)
Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the lenght of the air duct should be more than 3 meters.
MS-SVN004-EN 15
E
D
Ø20
HANGER HOLES - X6
SEE VIEW "A"
Ø16
32
111
VIEW "A"
127
63.5
A
B
C
625
490 SUCTION CONNECTION
165
LIQUID CONNECTION
254
300
266
40 174
DRAIN CONN. Ø22.5 MPT
Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the lenght of the air duct should be more than 3 meters.
16 MS-SVN004-EN
E
D
Ø20
HANGER HOLES - X6
SEE VIEW "A"
32
Ø16
111
VIEW "A"
139
75
A
B
759 C
615
SUCTION CONNECTION
352
394
354
408
All External Dimensions are in inch (mm.) Refrig. Line Conn. Size Number Of
Model
A B C D E Suction Liquid Fan(s) Motor(s)
Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the lenght of the air duct should be more than 3 meters.
MS-SVN004-EN 17
Figure 8
18 MS-SVN004-EN
MS-SVN004-EN 19