Installation - MCD SV1801 en 0698 0203

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 20

Installation Manual

ILLUSION
Split System
Concealed Type
MCD Series 50/60 Hz

Cooling Only/Cooling Heating Cooling Only/Cooling Heating


50 Hz Models 60 Hz Models
MCD 512 DB MCD 512 D1
MCD 518 DB MCD 518 D1
MCD 524 DB MCD 524 D1
MCD 530 DB MCD 530 D1
MCD 536 DB MCD 536 D1
MCD 048 DB MCD 048 D1
MCD 060 DB MCD 060 D1

February 2003 MS-SVN004-EN

L/O- 02091985TRA 1 18/3/03, 1:41 PM


General Information

Introduction Reception About this Manual


This Installation Manual is given as a On arrival, inspect the unit before Cautions appear at appropriate places
guide to good practice in the signing the delivery note. Specify any in this Installation Manual.
installation by the installer of MCD damage of the unit on the delivery Your personal safety and the
mini-split system. Installation note, and send a registered letter of proper operation of this machine
procedures should be performed in protest to the last carrier of the goods require that you follow them
the sequence that they appear in this within 72 hours of delivery. Notify the carefully.
manual. dealer at the same time. The Trane Company assumes no
liability for installations or servicing
For installing the unit to operate The unit should be totally inspected performed by unqualified personnel.
properly and reliably, it must be within 7 days of delivery. If any All phases of the installation of this air
installed in accordance with these concealed damage is discovered, conditioning system must conform to
instructions. Also, the services of a send a registered letter of protest to all national, provincial, state and local
qualified service technician should be the carrier within 7 days of delivery codes.
employed, through the maintenance and notify the dealer.
contract with a reputable service Warning
company. Warranty Warnings are provided at appropriate
Warranty is based on the general places in this manual to indicate to
Read these installation instructions terms and conditions by country. installers, operators and service
completely before installing the The warranty is void if the equipment personnel of potentially hazardous
air conditioning system. is modified or repaired without the situations which, if not avoided,
written approval of COULD result in death or serious
About the Unit The Trane Company, if the injury.
These MCD units are assembled, operating limits are exceeded or if
pressure tested, dehydrated, charged the control system or the electrical Caution
and run tested before shipment. wiring is modified. Cautions are provided at appropriate
The information contained in this places in this manual to indicate to
manual applies to MCD units are Damage due to inappropriate installers, operators, and service
designed to operate in cooling mode installation, lack of knowledge or personnel of potentially hazardous
only and in cooling or heating failure to comply with the situations which, if not avoided, MAY
modes. manufacturer’s instructions, is not result in minor or moderate injury or
covered by the warranty obligation. malfunction of the unit.
Important If the installation does not conform to
This document is customer property the rules described in Installation
and is to remain with unit. Please Manual, it may entail cancellation of
place in service information pack upon warranty and liabilities by
completion of work. The Trane Company.
These instructions do not cover all
variations in systems, nor do they
provide for every possible contingency
to be met in connection with
installation.
Should further information be
desired or should particular
problems arise which are not
covered sufficiently in this manual,
the matter should be referred to
your authorized Trane dealer.

© American Standard Inc.2000 MS-SVN004-EN

L/O- 02091985TRA 2 18/3/03, 1:41 PM


Contents

General Information 2
System Appearance 4
Location and Preparation of Units 6
Units Installation 7
Connection of Refrigerant Tubing 9
Condensate Drain Piping 10
Electrical Installation 11
Wiring Diagram 12
Dimensional Data 15
Maintenance 18

MS-SVN004-EN 3

L/O- 02091985TRA 3 18/3/03, 1:41 PM


System Appearance

MCD 512-536 DB/D1

Blower

Motor

Outlet Collar

Evaporator Coil

Electric Heater
(Option)

Condensate Drain Pan

Indoor unit

Outdoor Unit

4 MS-SVN004-EN

L/O- 02091985TRA 4 18/3/03, 1:41 PM


MCD 048-060 DB/D1

Motor
Blower

Outlet Collar

Evaporator Coil

Return Air Plenum


(Standard) Electric Heater
(Option)

Condensate Drain Pan

Indoor Unit

Outdoor Unit

MS-SVN004-EN 5

L/O- 02091985TRA 5 18/3/03, 1:41 PM


Location and Preparation of Units

Indoor Unit 2. Before cutting, check that no pipes 1. Tools Required for Installation
1. Select a convenient location that or studs are directly behind the (not supplied)
allows the air to reach every corner place to be cut. Avoid areas where - Level
of the room and where it is easy to electrical wiring or conduits are - Hole saw or saw
route the refrigerant tubing, wiring located. - Core bits
and drain to the outside. 3. Hang the unit on a solid and level - Hammer
2. The ceiling construction should be roof. Noise, vibration or leakage - Drill
strong enough to support the could occur on and unstable - Torque wrench
weight of the unit. foundation (Figure 3,4). - Adjustable wrench
3. The refrigerant tubing, drain piping For correct installation of duct - Standard screwdriver
and wiring conduit are connected work see (Figure 6). - Phillips head screwdriver
through the wall. 4. Support the unit solidly. - Knife or wire stripper
4. Refrigerant tubes between the 5. To have access to electrical - Tape measure
indoor and the outdoor units and terminals, remove the right side - 4 Anchor bolts for ceiling
drain pipes should be as short as junction box (Figure 2). mounting
possible (Figure 1). 6. Note that refrigerant tubing,
5. If a refrigerant charge adjustment is interconnecting wiring and drain 2. Refrigerant Piping and Insulation
necessary, follow the Installation hose should go through the wall. Material
Manual for the Outdoor Unit. Shape these items so that they will - See the Installation Manual
easily fit through the wall. included with the Outdoor Unit.
Outdoor Unit - The length of wiring will determine
See instructions for location and the wire size. See local codes and
preparation of the unit in the Installation refer to Section Electrical
Manual for the Outdoor Unit. Installation.

Installation Method: Figure 2 Caution


Indoor Unit Check local electrical codes and
After selecting the location to place regulations before buying any wire.
the unit, follow these steps: Also check for any specitic wiring
1. Make a hole in the wall to route instructions or limitations.
tubing and wiring through a locally
purchased PVC pipe. The hole 3. Additional Materials Required
should slope downwards slightly, Outdoor Unit for Installation
towards the outside (Figure 2). See the proper installation method - Saddles or clamps to secure
provided in the Installation Manual refrigerant tubing.
for the Outdoor Unit. - Insulated clamps or staples for
connecting wire. See local codes.
Installation Requirements - Ceiling mount: Use nuts and bolts
Important as required to mount the unit on the
- Read the Installation Manual ceiling. Use 4 (3/8) fasteners or
completely before installing and closest standard metric with nuts
operating the system. and lock washers. The length will
- Turn on the mains power at least vary with application.
five (5) hours before operating - Refrigerant oil and tape
Figure 1 (insulation).
the system.
- Putty or similar filler.
Installation Requirements
Following is a brief outline of where
and how to install the unit. Please read
over the entire set of instructions for
indoor and outdoor units and make
sure all accessory parts list are with
the unit before beginning.

6 MS-SVN004-EN

L/O- 02091985TRA 6 18/3/03, 1:41 PM


Unit Installation

CELING
RETURN PLENUM
DETAIL "X" WITH FILTER

I
A WALL
SUPPLY
DUCT B DRAIN PIPE
SLANT 1 : 50
H

F
E C
G
D

FILTER
FLEXIBLE CONNECTER
CHAMBER RETURN AIR GRILLE

FIGURE 3 (SIDE VIEW)

FILTER

DRAIN PIPE

J K
CHAMBER

SUPPLY DUCT

FIGURE 4 (TOP VIEW)

A B C D E F G H I J K

DISTANCE (M.M.) Min.750 Min. 800 100 150 50 200 Min. 200 Min. 100 Min. 50 Min. 300 Min. 300

NOTE: FOR DUCT LENGTH PLEASE SEE PAGE 15, 16 AND 17

MS-SVN004-EN 7

L/O- 02091985TRA 7 18/3/03, 1:41 PM


Units Installation

8 MS-SVN004-EN

L/O- 02091985TRA 8 18/3/03, 1:41 PM


Connection of Refrigerant Tubing

Proper installation prodecure is Flare Nut 2. Remove burrs at the end of the
recommended in the Installation copper tube with a tube reamer
Manual Package, usually provided (Figure 8).
together with the outdoor unit. It is 3. There are 2 ways to connect the
advisable to read bofore installing. Copper Tubing copper tube
Flare Tool - Use a coupling between the
The indoor unit refrigerant connections Figure 10 copper tube of Fan Coil Unit and
are located on the left hand side when the copper tube used for
facing the unit (Figure 7). A good flare should have the installation (Figure 13).
following characteristics:
• Inside surface is glossy and smooth.
• Edge is smooth. Copper Tube
• Tapered sides are of uniform of Fan Coil
length. Unit
Solder Coupling
Cautions Before Connecting
Tightly Copper Tube of
Figure 7 1. Be sure to apply a sealing cap or Condensing Unit
water-proof tape to prevent dust or Figure 13
water from getting into the tubes
Connecting the Units with before they are used.
Flaring Procedure. - Expand the copper tube by
2. Be sure to apply refrigerant using a swaging tool set as in
1. Cut the copper tube to the required lubricant to the matching surfaces
length with a tube cutter. It is Figure 14.
of the flare and union before
recommended to cut approx.
connecting them together. This is
20-30 cm. longer than the tubing
effective for reducing gas leaks Swaging Tool
length.
(Figure 11).
2. Remove burrs at the end of the
copper tube with a tube reamer
or file, as shown in Figure 8. Tube Holder
Copper Tube (Clamp)

Apply refrigerant lubricant here


Figure 11
Copper
Tubing Reamer 3. For proper connection, align the
union tube and flare tube straight Figure 14
Figure 8 with each other, then screw in the
flare nut lightly at first to obtain a 4. To braze the copper tube, before
When reaming, hold the tube end smooth match (Figure 12). brazing a copper tube to a solder
downward and be sure that no copper coupling or a copper tube to an
scraps fall into the tube (Figure 9). expanded tube, do not forget to
Deburring keep them tight as shown in
Figure 15.

Torch
CO
MM
Union Flare Nut ET
3

Figure 12 Copper Tube


Before After from Fan
4. Tighten the flare nuts, using the Coil Unit
Figure 9 appropriate wrench. Solder Rod
3. Remove the flare nut from the unit Connecting the Unit with Solder Coupling
and be sure to insert on the copper Brazing Prodecure Copper Tube from
tube. 1. Cut the copper tube to the required Condensing Unit
4. Make a flare at the end of the copper length with a tube cutter. It is
tube with a flare tool (Figure 10). recommended to cut approx. Figure 15
20-30 cm. longer than the tube length.
MS-SVN004-EN 9

L/O- 02091985TRA 9 18/3/03, 1:41 PM


Condensate Drain Piping

Condensate Drain Piping 4. When the drain hose is placed in


1. The drain hose should run straight the room, insulate the hose with
down the wall to a level where the foam polyethylene to avoid damage
run off will not stain the wall. to the ceiling or furniture.
2. These should have water traps. 5. After completing installation of
Avoid putting the end of the hose in refrigerant lines, wiring and drain
water. connections, bind the tubing,
3. To conveniently drain the system, wiring and drain piping (check if
the drain piping must slant local codes permit binding) into a
downward, with a slope of at least bundle by using tape at 100 or 200
1:50 to prevent leakage. mm (4" to 8") intervals. Make sure
the drain tube is at the bottom of
the bundle (Figure 16).

P.V.C. Tape

Insulation Tube

Suction Line Tube


Liquid Line Tube
P.V.C.
Water Condensated Conduit
Drain Tube
(P.V.C. Tube) Control Wiring
Power Wiring with
Ground Wiring

Figure 16

10 MS-SVN004-EN

L/O- 02091985TRA 10 18/3/03, 1:41 PM


Electrical Installation

Electrical Installation Indoor Unit


All wiring and grounding must comply Remove the right side junction box
with local electrical codes. (see previous instructions) to access
the terminal base.
Wiring Important Safeguards:
- Check the unit nameplate for System Wiring Routing
electrical rating. Be sure wiring is - Pass the system wiring through the
done according to local codes and PVC pipe, referred to in the Section
wiring diagram. of Installation Method (both power
- Use a separate power line with and control lines) to interconnect
circuit breaker for each air indoor and outdoor units.
conditioning unit. - Connect the wire terminals to the
- Connect electrical ground to all terminal base. See connection
units. indication on system wiring
- Wiring should not touch refrigerant diagram.
tubing, compressor, motors or - Make sure all connections are tight.
moving parts.
- The manufacturer will accept no Outdoor Unit
responsibility for problems caused See the electrical installation
by unauthorized changes in the instructions in the Installation Manual
internal wiring. for the Outdoor Unit.
- Connect the wiring firmly.

MS-SVN004-EN 11

L/O- 02091985TRA 11 18/3/03, 1:41 PM


Wiring Diagram

CONCEALED FAN COIL UNITS


COOLING ONLY
MCD 512-536 DB/D1
MCD 048-060 DB/D1

Remove HI-BR wire from TB-1 and replace


with EXTRA HI-BLK wire when high speed/cfm
is required in the field.

BLK
EXTRA–HI
HI BR
1
BLOWER MED BL
MOTOR
2
LOW RD
3
COM WH LOW MED HI
4
3 SPEED SWITCH

THERMOSTAT

L2 L1 C1 C2

POWER SUPPLY
200-240V/1PH/60Hz
NOTE : LEGEND : 220-240V/1PH/50Hz
1. Power wiring and grounding of equipment 200-240 VAC
must comply with local codes. FIELD WIRING CONTROL WIRING
2. Ensure that power supply agrees with TO CONDENSING
FACTORY WIRING
UNIT.
equipment nameplate.
3. Use only copper conductors.

12 MS-SVN004-EN

L/O- 02091985TRA 12 18/3/03, 1:41 PM


Wiring Diagram

CONCEALED DX AIR HANDLER


COOLING-HEATING
MCD 512-524 DB/D1

REMOVE HI-BR WIRE FROM TB-1 AND REPLACE


WITH EXTRA HI-BLK WIRE WHEN HI SPEED/CFM
IS REQUIRED IN THE FIELD.
BLK
EXTRA–HI
HI BR
1
BLOWER MED BL
2
MOTOR LOW RD 3
COM WH 4 LOW MED HI
BLK 5
HEAT
OFF
TO HEATING
RD 6
RD
TO COOLING h
0 1 COOL 3 SPEED
2 4 6 8 SWITCH
COOLING-HEATING THERMOSTAT
SWITCH

HEATER THERMAL OVERLOAD


PROTECTOR (MANUAL RESET)
(MAX.20AMP. NON-INDUCTIVE
FULL LOAD CURRENT)
H C H C L N C1 C2
HEATER
POWER SUPPLY 200-240 VAC
HEATER THERMAL OVERLOAD 200-240V/1PH/60Hz CONTROL WIRING
PROTECTOR (AUTO RESET) 220-240V/1PH/50Hz TO CONDENSING UNIT.
(MAX.20AMP. NON-INDUCTIVE
FULL LOAD CURRENT) LEGEND: NOTE:
1. POWER WIRING AND GROUDING OF
FIELD WIRING EQUIPMENT MUST COMPLY WITH LOCAL
FACTORY WIRING CODE.
2. ENSURE THAT POWER SUPPLY AGREES
WITH EQUIPMENT NAME PLATE.
3. USE ONLY COPPER CONDUCTORS.

MS-SVN004-EN 13

L/O- 02091985TRA 13 18/3/03, 1:41 PM


Wiring Diagram

CONCEALED FAN COIL UNITS


COOLING-HEATING
MCD 530-536 DB/D1
MCD 048-060 DB/D1

REMOVE HI-BR WIRE FROM TB-1 AND REPLACE


WITH EXTRA HI-BLK WIRE WHEN HI SPEED/CFM
IS REQUIRED IN THE FIELD.
EXTRA–HI BLK

HI BR
1
BLOWER MED BL
MOTOR
2
LOW RD
3
COM WH LOW MED HI
4
BLK HEAT
OFF
5 TO HEATING
RD
6
RD
TO COOLING h
0 1 COOL 3 SPEED
2 4 6 8 SWITCH
COOLING-HEATING THERMOSTAT
SWITCH

HEATER THERMAL OVERLOAD


PROTECTOR (MANUAL RESET)
(MAX.20AMP. NON-INDUCTIVE
FULL LOAD CURRENT)
H C H C L N C1 C2
HEATER
POWER SUPPLY 200-240 VAC
HEATER THERMAL OVERLOAD 200-240V/1PH/60Hz CONTROL WIRING
PROTECTOR (AUTO RESET) 220-240V/1PH/50Hz TO CONDENSING UNIT.
(MAX.20AMP. NON-INDUCTIVE
FULL LOAD CURRENT) LEGEND: NOTE:
1. POWER WIRING AND GROUDING OF
FIELD WIRING EQUIPMENT MUST COMPLY WITH LOCAL
FACTORY WIRING CODES.
2. ENSURE THAT POWER SUPPLY AGREES
WITH EQUIPMENT NAME PLATE.
3. USE ONLY COPPER CONDUCTORS.

14 MS-SVN004-EN

L/O- 02091985TRA 14 18/3/03, 1:41 PM


Dimensional Data

HANGER HOLES - X6
SEE VIEW "A"
Ø16

111

32
127
63.5

VIEW "A"

A
B
284 C
252
SUCTION CONNECTION
LIQUID CONNECTION
166
210
234

254

40 174
DRAIN CONN. Ø22.5 MPT

External Dimensions (No Plenum)

All External Dimensions are in inch (mm.) Refrig. Line Conn. Size Number Of
Model
A B C Suction Liquid Fan(s) Motor(s)

MCD 512 30"(762) 34 3/4"(882) 37 1/4"(946) 1/4"(6.35) 1/2"(12.7) 2 1

MCD 518 30"(762) 34 3/4"(882) 37 1/4"(946) 1/4"(6.35) 1/2"(12.7) 2 1

MCD 524 30"(762) 34 3/4"(882) 37 1/4"(946) 3/8"(9.52) 5/8"(15.87) 2 1

MCD 530 36"(914) 40 1/4"(1034) 43 1/4"(1098) 3/8"(9.52) 5/8"(15.87) 2 1

MCD 536 42"(1067) 34 7/8"(1087) 49 1/4"(1251) 3/8"(9.52) 3/4"(19.05) 2 1

Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the lenght of the air duct should be more than 3 meters.

MS-SVN004-EN 15

L/O- 02091985TRA 15 18/3/03, 1:41 PM


Dimensional Data

E
D

Ø20

HANGER HOLES - X6
SEE VIEW "A"
Ø16

32
111

VIEW "A"
127
63.5

A
B
C

625
490 SUCTION CONNECTION
165

LIQUID CONNECTION
254
300
266

40 174
DRAIN CONN. Ø22.5 MPT

External Dimensions (Return Air Plenum is option)


All External Dimensions are in inch (mm.) Refrig. Line Conn. Sizes Number Of
Model
A B C D E Suction Liquid Fan(s) Motor(s)

MCD 512 30"(762) 34 3/4"(882) 37 1/4"(946) 30"(762) 33 15/16"(862) 1/4"(6.35) 1/2"(12.7) 2 1

MCD 518 30"(762) 34 3/4"(882) 37 1/4"(946) 30"(762) 33 15/16"(862) 1/4"(6.35) 1/2"(12.7) 2 1

MCD 524 30"(762) 34 3/4"(882) 37 1/4"(946) 30"(762) 33 15/16"(862) 3/8"(9.52) 5/8"(15.87) 2 1

MCD 530 36"(914) 40 1/4"(1034) 43 1/4"(1098) 36"(914) 39 15/16"(1014) 3/8"(9.52) 5/8"(15.87) 2 1

MCD 536 42"(1067) 42 7/8"(1087) 49 1/4"(1251) 42"(1067) 45 15/16"(1167) 3/8"(9.52) 3/4"(19.05) 2 1

Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the lenght of the air duct should be more than 3 meters.

16 MS-SVN004-EN

L/O- 02091985TRA 16 18/3/03, 1:41 PM


Dimensional Data

E
D

Ø20

HANGER HOLES - X6
SEE VIEW "A"

32
Ø16

111

VIEW "A"
139
75

A
B
759 C
615
SUCTION CONNECTION
352
394
354

408

LIQUID CONNECTION 180 C


DRAIN CONN. Ø21 MPT 30

External Dimensions (Return Air Plenum is Standard)

All External Dimensions are in inch (mm.) Refrig. Line Conn. Size Number Of
Model
A B C D E Suction Liquid Fan(s) Motor(s)

MCD048 36.06"(916) 40.70"(1034) 43.58"(1107) 35.70"(907) 39.88"(1013) 1-1/8"(28.57) 3/8"(9.52) 2 1

MCD060 42.08"(1069) 46.73"(1187) 49.21"(1250) 41.73"(1060) 45.90"(1166) 1-1/8"(28.57) 3/8"(9.52) 2 1

Note: From the experience of our Trane technician, based on the design condition, at velocity at supply air grille of 300 ft/min for bedroom and 400
ft/min for office (based on free face area), the lenght of the air duct should be more than 3 meters.

MS-SVN004-EN 17

L/O- 02091985TRA 17 18/3/03, 1:41 PM


Maintenance

Regular Maintenance Note: Once the air filter is washed,


Be sure to disconnect the power dry it completely before returning it to
before inspection or maintenance of its original position.
air conditioner. After cleaning be sure to return it to its
original position.
1. Cleaning the air filter
Air flow is reduced and cooling Cautions
efficiency impaired if the filter is - Do not wash the air filter in water
clogged. Be sure to clean the filter that is over 40ºC or it may shrink.
every two weeks during the cooling - Do not expose the air filter to fire.
season. - Do not expose the air filter to direct
1.1 How to remove the air filters sunlight for a long time.
- Loose screws located under - Clean the air filter more frequently
the filter in return air plenum when the air is very dirty.
set.
- Remove air filter frame from
return air plenum set.
1.2 How to clean the air filter.
- Wash away dust from the air
filter with clean water or
vacuum it with an electric
vacuum cleaner.

Figure 8

18 MS-SVN004-EN

L/O- 02091985TRA 18 18/3/03, 1:41 PM


Notes

MS-SVN004-EN 19

L/O- 02091985TRA 19 18/3/03, 1:41 PM


Literature Order Number MS-SVN004-EN 0200
Trane Thailand
New MCD-SV1801-EN 0698
7th Floor, Ploenchit Center Building
2 Sukhumvit Road, Klongtoey Stocking Location Bangkok, Thailand
Bangkok 10110
Amair Limited ∫√‘…—∑ ·Õ¡·Õ√å ®”°—¥ 35 À¡Ÿà 8 ∂.ªŸ‡É ®â“ ¡‘ßæ√“¬ µ. ”‚√ß„µâ Õ.æ√–ª√–·¥ß ®. ¡ÿ∑√ª√“°“√ 10130
35 Mu 8, Poochaosamingprai Road
Samrong Tai, Samutprakarn 10130
http://www.trane.com Since The Trane Company has a policy of continuous product and product data improvement,
An American Standard Company it reserves the right to change design and specifications without notice.

L/O- 02091985TRA 20 18/3/03, 1:41 PM

You might also like