WATER SPRAY CALCULATION

CLIENT : PT PERTAMINA MOR III


PROJECT : PERBAIKAN TANGKI TIMBUN T.104 & T.211 INTREGATED TERMINAL BALONGAN
LOCATION : BALONGAN, INDRAMAYU - JAWA BARAT
DOC. NO. : ITB-PPTT-HSE-HS-CAL-002

Page No. Kontrak Item No. Service REV


1 of 1 3950191232 T.104/T.211 Fire Water B

WATER SPRAY FOR SHELL T.104 WATER SPRAY FOR SHELL T.211
DATA DESIGN DATA DESIGN
Tinggi Tangki = 43900 mm 43,9 m Tinggi Tangki = 47000 mm 47 m
Diameter Tangki = 9150 mm 9,15 m Diameter Tangki = 12880 mm 12,88 m
Shell to Ring = 500 mm 0,5 m Shell to Ring = 500 mm 0,5 m
Diameter Ring = 44400 mm 44,4 m Diameter Ring = 47500 mm 47,5 m
Jumlah Spray = 177 pcs (As per BOQ) Jumlah Spray = 189 pcs (As per BOQ)

BASIS DESIGN BASIS DESIGN


Application Rate = 4,1 L/menit.m2 Application Rate = 4,1 L/menit.m2
2
Supply Pressure = 4,1 kg/cm Supply Pressure = 4,1 kg/cm2

CALCULATION CALCULATION
Keliling Tangki = 139416 mm 139,42 m Keliling Tangki = 149150 mm 149,15 m
Jarak antar Spray = 787,66 mm 0,79 m Jarak antar Spray = 789,15 mm 0,79 m
Luas Area Shell = 1261,29 m2 Luas Area Shell = 1900,83 m2
Kebutuhan Fire Water = 5171,29 L/menit Kebutuhan Fire Water = 7793,40 L/menit
Kebutuhan Air per Nozzle = 29,22 L/menit Kebutuhan Air per Nozzle = 41,23 L/menit

Spesifikasi Nozzle Shell T.104 Spesifikasi Nozzle Shell T.211


K factor Q Flowrate (LPM) Verification Status K factor Q Flowrate (LPM) Verification Status
20 40,50 ACCEPTED Dipilih 20 40,50 ACCEPTED Dipilih
30 60,75 ACCEPTED Recommended 30 60,75 ACCEPTED Recommended
37 74,92 ACCEPTED Recommended 37 74,92 ACCEPTED Recommended
42 85,04 ACCEPTED Recommended 42 85,04 ACCEPTED Recommended
58 117,44 ACCEPTED Recommended 58 117,44 ACCEPTED Recommended
79 159,96 ACCEPTED Recommended 79 159,96 ACCEPTED Recommended

WATER SPRAY FOR ROOF T.211


DATA DESIGN
Diameter Tangki = 47000 mm 47 m
Panjang Sisi Miring = 23521,27 mm 23,5 m
Shell to Ring = 500 mm 0,5 m
Diameter Ring #1 = 5000 mm 5 m
Diameter Ring #2 = 21400 mm 21,4 m
Diameter Ring #3 = 38800 mm 38,8 m
Inside Diameter Gossneck = 77,92 mm 0,07792 m

BASIS DESIGN
Application Rate = 4,1 L/menit.m2
Supply Pressure = 4,1 kg/cm2
Velocity = 6,1 m/s
Coverage Area of Spray = 2 m

CALCULATION
Quantity of Nozzles
Keliling Diameter Ring #1 = 15,70 m
Spray Nozzle Ring #1 = 7,85 pcs
= 9 pcs Spesifikasi Nozzle Roof T.211
Jarak antar Nozzle Ring #1 = 1,74 m K factor Q Flowrate (LPM) Verification Status
Keliling Diameter Ring #2 = 67,20 m 18 36,45 NOT ACCEPTED Tidak Sesuai
Spray Nozzle Ring #2 = 33,60 pcs 22 44,55 ACCEPTED Dipilih
= 37 pcs 26 52,65 ACCEPTED Recommended
Jarak antar Nozzle Ring #2 = 1,82 m 30 60,75 ACCEPTED Recommended
Keliling Diameter Ring #3 = 121,83 m 35 70,87 ACCEPTED Recommended
Spray Nozzle Ring #3 = 60,92 pcs 41 83,02 ACCEPTED Recommended
= 75 pcs 51 103,27 ACCEPTED Recommended
Jarak antar Nozzle Ring #3 = 1,62 m 64 129,59 ACCEPTED Recommended
Total Water Spray = 121 pcs 79 159,96 ACCEPTED Recommended
Water Demand 91 184,26 ACCEPTED Recommended
Luas Area Roof = 1735,63 m2 102 206,53 ACCEPTED Recommended
Kebutuhan Fire Water = 7116,10 L/menit
2
Luas Area Gossneck = 0,0048 m
Supply Air Gossneck = 1744,41 L/menit
Kebutuhan Air Spray = 5371,69 L/menit
Kebutuhan Air per Spray = 44,39 L/menit