Relay Setting Calculation Latest
Relay Setting Calculation Latest
ADWEA
Agent for SIEMENS AG G-1456
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 1 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
1. INDEX
1. INDEX..................................................................................................................................... 2
2. INTRODUCTION.................................................................................................................... 3
3. REFERENCE DOCUMENTS..................................................................................................4
4. DATA...................................................................................................................................... 5
4.1 Network Data.................................................................................................................... 5
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 2 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
2. INTRODUCTION
O/C and E/F relay setting is calculated considering that only one
transformer is feeding the fault current for outgoing cable feeders,
capacitor feeders and station transformer feeders in case -1.
Based on above time multiplier setting operating time of the O/C & E/F
relay is calculated when two transformer in parallel in case-2.
O/C & E/F relay operating time for all cable feeders and capacitor
bank feeders shall be kept at 0.5 Sec.
O/C & E/F relay operating time for station Transformer shall be kept at
0.2 Sec.
O/C relay operating time for bus-section shall be kept at 0.8 Sec (Time
grading of 0.3 Sec with outgoing feeders). E/F relay shall be kept OFF.
O/C & E/F relay operating time for bus Inter-connector shall be kept at
0.8 Sec and 0.6 Sec
O/C relay operating time for Incomers shall be kept at 1.1 Sec. (Time
grading of 0.3 Sec with bus-section and bus Inter-connector)
E/F relay operating time for Incomers shall be kept at 0.8 Sec.
Normal Inverse characteristics curve shall be selected for O/C & E/F
protection.
High set for O/C and E/F protection for bus-section, bus Inter-
connector and Incomers shall be kept OFF.
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 3 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 4 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
3. REFERENCE DOCUMENTS
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 5 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
4. DATA
Maximum three phase 11kV through fault current for one Transformer:
Page 6 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
Maximum three phase 11kV through fault current when two 40 MVA
132/11KV transformer in parallel.
If = 24KA
Ief = 13.852KA
Ief = 13.696KA
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 7 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
The relay type 7SJ612 is intended to be used for three phase over current and
earth protection.
Relay operating time will be kept at 0.5 Sec at maximum fault current considering
that only one transformer is feeding the fault.
Relay operating time when two transformer in parallel is calculated at selected time
multiplier setting with one transformer feeding the fault current.
Technical data:
Available CT Ratio : 600-400/1
Selected CT Ratio : 400/1
Bay nominal current Ipr = 400A
Case-1 :
Time Multiplier Setting Calculation considering one transformer is feeding the
fault current :
Overcurrent Setting:
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 8 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
Tp = 0.251
0.5 = 0.14*Tep/((Ief/Ipr*Iep)0.02 –1 )
0.5 = 0.14*Tep/((6848/400*0.2)0.02 –1
Case-2 :
Operating time calculation of over current and earth fault relay at above
selected time multiplier setting (Tp and Tep) when two 40MVA transformer in
parallel.
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 9 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 10 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
The relay type 7SJ612 is intended to be used for three phase over current and
earth protection.
Relay operating time will be kept at 0.2 Sec at maximum fault current considering
that only one transformer is feeding the fault.
Relay operating time when two transformer in parallel is calculated at selected time
multiplier setting with one transformer feeding the fault current.
Technical data:
Case-1 :
Time Multiplier Setting Calculation considering one transformer is feeding the
fault current :
Overcurrent Setting:
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 11 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
Tp = 0.172
0.2 = 0.14*Tep/((Ief/Ipr*Iep)0.02 –1 )
0.2 = 0.14*Tep/((6848/50*0.2)0.02 –1
Case-2 :
Operating time calculation of over current and earth fault relay at above
selected time multiplier setting (Tp and Tep) when two 40MVA transformer in
parallel.
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 12 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 13 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
The relay type 7SJ612 is intended to be used for three phase over current and
earth protection.
Relay operating time will be kept at 0.5 Sec at maximum fault current considering
that only one transformer is feeding the fault.
Relay operating time when two transformer in parallel is calculated at selected time
multiplier setting with one transformer feeding the fault current.
Technical data:
Available CT Ratio : 1200-800/1
Selected CT Ratio : 800/1
Bay nominal current Ipr = 800A
Case-1 :
Time Multiplier Setting Calculation considering one transformer is feeding the
fault current :
Overcurrent Setting:
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 14 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
Tp = 0.198
0.5 = 0.14*Tep/((Ief/Ipr*Iep)0.02 –1 )
0.5 = 0.14*Tep/((6848/800*0.2)0.02 –1
Case-2 :
Operating time calculation of over current and earth fault relay at above
selected time multiplier setting (Tp and Tep) when two 40MVA transformer in
parallel.
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 15 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 16 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
The relay type 7SJ612 is intended to be used for three phase over current and
earth protection.
Relay operating time will be kept at 0.8 Sec at maximum fault current considering
time grading of 0.3 Sec with outgoing feeders.
Technical data:
Available CT Ratio : 2500/1
Selected CT Ratio : 2500/1
Bay nominal current Ipr = 2500A
Overcurrent Setting:
Tp = 0.182
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 17 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
The relay type 7SJ612 is intended to be used for three phase over current and
earth protection.
Relay operating time will be kept at 0.8 Sec at maximum fault current considering
time grading of 0.3 Sec with outgoing feeders.
Technical data:
Available CT Ratio : 2500/1
Selected CT Ratio : 2500/1
Bay nominal current Ipr = 2500A
Overcurrent Setting:
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 18 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
Tp = 0.182
0.6= 0.14*Tep/((Ief/Ipr*Iep)0.02 –1 )
0.6 = 0.14*Tep/((6848/2500*0.2)0.02 –1
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 19 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
The relay type 7SJ612 is intended to be used for three phase over current and
earth protection.
Relay operating time will be kept at 1.1 Sec for over current protection and 0.8 Sec
earth fault protection at maximum fault current considering time grading of 0.3 Sec
with bus section.
Technical data:
Available CT Ratio : 2500-2000/1
Selected CT Ratio : 2500/1
Bay nominal current Ipr = 2500A
Overcurrent Setting:
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 20 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
Tp = 0.250
0.8= 0.14*Tep/((Ief/Ipr*Iep)0.02 –1 )
0.8 = 0.14*Tep/((6848/2500*0.2)0.02 –1
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 21 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 22 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022
ELECTRO MECHANICAL Co. LLC. ADWEA
Agent for SIEMENS AG G-1456
Time
Plug High Set Time Setting
Sr. No. Feeder Type CT Ratio Multiplier
Setting Setting for High Set
Setting
P/F : 1.00 P/F : 0.25 P/F : 8A P/F : 0 Sec
1 Cable Feeder 600-400/1
E/F : 0.20 E/F : 0.33 E/F : 6A E/F : 0 Sec
P/F : 1.00 P/F : 0.19 P/F : 8A P/F : 0 Sec
2 Capacitor Feeder 1200-800/1
E/F : 0.20 E/F : 0.28 E/F : 6A E/F : 0 Sec
P/F : 0.80 P/F : 0.17 P/F : 8A P/F : 0 Sec
3 Station Tr. Feeder 150-50/1
E/F : 0.20 E/F : 0.20 E/F : 6A E/F : 0 Sec
P/F : 1.00 P/F : 0.18 P/F : OFF P/F : OFF
4 Bus-Section 2500/1
E/F : OFF E/F : OFF E/F : OFF E/F : OFF
P/F : 1.00 P/F : 0.18 P/F : OFF P/F : OFF
5 Bus Inter-connector 2500/1
E/F : 0.20 E/F : 0.23 E/F : OFF E/F : OFF
P/F : 1.00 P/F : 0.25 P/F : OFF P/F : OFF
6 Incomer 2500-2000/1
E/F : 0.20 E/F : 0.31 E/F : OFF E/F : OFF
ELMEC REF:
REFURBISHMENT AND EXTENSION OF
33KV AND 11KV SWITCHGEAR IN VI/725
EASTERN REGION OF ABU DHABI
Page 23 OF 23
RE
CSD NO 1456 EA 7500 Z 101 A 9/3/2022