XCell

“Automation platform for HV and MV substations”


XCell Datasheet Features / Description

Introduction form large systems. Its scalability allows it to be used in


large HV substations with tens of thousands of I/O points
XCell is an advanced substation automation platform and small MV substations with a few hundred points.
designed specifically for HV and MV substations. Its state-
of-the-art technology provides real-time access to hardwired Each processor module supports two Ethernet ports and five
plant data, intelligent IEDs, networked IEC 61850 devices serial ports (RS232/ RS485/ RS422), along with a display
and smart meters. This makes it ideal for new substations for status and diagnostic information. The I/O module range
or upgrading and integrating existing substations. includes 64 channel digital inputs, 32 channel digital
outputs and 32 channel DC analogue inputs.
XCell is designed for use in the most demanding electrical
environments. XCell’s exceptional reliability and redundancy IEC 61850 Gateway
guarantees high system availability through dual power
sources, redundant processors and redundant SCADA links. XCell can operate as a substation gateway, interfacing
between the substation IEDs and the SCADA Control Centre.
Features XCell supports a variety of IED protocols including
IEC61850, IEC103, DNP3 and Modbus. XCell also supports
Scalable, Flexible, Architecture a rich suite of SCADA protocols including DNP3 (serial and
Exceptionally High Reliability TCP/IP), IEC101/104 and an extensive range of proprietary
IEC 61850 Integration protocols. It also supports multiple SCADA links, generally
SCADA Protocol Support preferred for increased system availability.
IED Integration
IEC 61131 PLC programming smartLogic Programming
High Density Plant Interface
Redundancy To provide flexible site-specific solutions, XCell supports the
Comprehensive diagnostics IEC 61131 graphical programming standard, allowing simple
graphical application development using:
It’s the ideal platform for new substations, facilitating the Ladder Diagrams
integration of new technologies including IEC 61850. Function Block Diagrams
However, it`s equally suited to substation retrofits where Structured Text
there’s already a wide variety of installed equipment Sequential Function Charts
requiring integration and migration to the latest technologies.

Modularity Substation Toolset


Each 19” rack supports a processor and up to fifteen plug The XCell product is supported by a comprehensive suite of
and play I/O modules. I/O modules range in functionality, tools for both configuration and diagnostics. Configurations
point counts, and interface/termination options. Multiple can be downloaded via direct connection or remotely via a
processors can be installed to provide redundancy, data TCP/IP connection. Remote diagnostics are also supported,
segregation and additional communication ports. Critical giving access to data values, hardware status, event logs
software applications can run on multiple processors for and internal diagnostic logs. A local display panel on the
redundancy. Multiple processors can be combined to form a front of the processor module provides current I/O data
data concentrator and multiple racks can be networked to values and diagnostics.
XCell Datasheet Technical Characteristics

Communication Interfaces
Ethernet 2 x 10/100Base-TX (RJ-45 connection)
Serial Ports 5 selectable RS-232 / RS-422 / RS-485 (9-way Male D-Type)
Extended Communications Module Option available for additional 4 serial ports
FieldNet Network Redundant 2.5 M/bit/s inter-rack RS485 connection
Expansion
Number of I/O Modules 15 I/O slots. (Data concentrator up to 8 CPR-041-C processor modules)
FieldNet Netwaork Operational distances up to 10Km achievable using optional OPI-045 optical interface
module(s) with both point to point and redundant ring topologies supported.
Power Supply Module
Input Voltage Range 18-72 VDC
Power Consumption Maximum of 50W (refer to specific module datasheets)
Power Supply Rating 50W (multiple processors provide redundant supplies)
Isolation 5 kVDC
Redundant Input Connections Redundant wire-ored connections (DC1 +/- & DC2 +/-) with filtered input stage
Data Display
OLED Data Display 128 x 64 OLED data display for Status/Values and Diagnostics on CPR-041-C module.
DI Digital Input Module [HDI-05X] (Optional)
Inputs 64 (37 way D-sub connectors with one common for each 16 inputs)
Input Voltage 18-72 VDC standard card with options for higher field voltages up to 150 VDC
Input Type Switch selectable Voltage –driven or Volt-free
Input Resistance 44 kΩ
Isolation 5kVDC
DO Digital Output Module [HDO-04X] (Optional)
Outputs 32 One normally open single pole relay contact per channel
Maximum Carrying Current 5 A
Switching Current 5 A @ 250 VAC, 5 A @ 30 VDC 0.6 A @ 100 VDC
Contact to Coil Isolation 5 kVDC
DC Analogue Inputs [HAI-03X] (Optional)
Inputs 32
Nominal Range ±20 mA,± ±10V Nominal Inputs with a 20% over range
Accuracy and Resolution 0.1% of full span with 24 bit resolution
Input Resistance 200Ω for current or > 1MΩ for voltage
Linearity 0.008% of full span
Isolation 5 kVDC
Electromagnetic Immunity
High Frequency Disturbance IEC 61000-4-12, C37.90.1, IEC 60255-22-1
Fast Transient Disturbance IEC 61000-4-4, C37.90.1, IEC 60255-22-4
Electrostatic Discharge IEC 61000-4-2, IEC 60255-22-2
Radiated Immunity IEC 61000-4-3 CISPR 22
High Frequency Conducted Immunity IEC 61000-4-6
Power Frequency Magnetic Field Immunity IEC 61000-4-8
Emissions IEC 61000-6-4
Environmental Conditions
Temperature Continuous Operation -20° to +60° C
Transportation and storage -40° to +70° C IEC 60068-2-1 & IEC 60068-2-2
Relative Humidity 0 to 95% non-condensing IEC 60068-2-3 & IEC 60068-2-30
Vibration; and Drop & Shock IEC 60068-2-6; IEC 60068-2-31
Dimensions
Dimensions (W * H * D) 483 mm (W) x 266 mm (H) x 221 mm (D) Standard 19 inch chassis 6U height
Mounting Rear or Front mounting options
Weight 6.6 Kg (approx)

ACTUAL PRODUCT MAY DIFFER FROM THAT SHOWN,


PRODUCT SPECIFICATIONS AND DATA ARE SUBJECT TO CHANGE WITHOUT NOTICE TO IMPROVE RELIABILITY, DESIGN OR OTHERWISE.
XCell Datasheet Contact Details

CG Automation Systems Ireland Ltd.


Herbert House,
Harmony Row,
Dublin 2,
Ireland.
T: +353 1 415 3700
F: +353 1 678 7913
E: sales.as.uk@cgglobal.com
W: www.cgglobal.com

CG Automation Systems UK Ltd.


Unit F Network Centre,
Jarrow,
Tyne & Wear NE31 1SF,
United Kingdom.
T: +44 191 425 5200
F: +44 191 425 5202
E: sales.as.uk@cgglobal.com
W: www.cgglobal.com

XCell Product Datasheet 2.4a2 ©