Module Description HDI-050-XX 2.7

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 9

HDI-050-XX Module Description

64 CHANNEL DIGITAL INPUT MODULE


Group of 16 Channels

Ch1
DC

Ch16
DC

Common

SW3
External Field
Wetting Voltage

HDI-050-XX

Group of 16 Channels
Ch49

Ch64

Common

SW6 XCell
Backplane
SW2 Power
VDC
DC
Internal Module
HDI-050-XX
Wetting Voltage via
External Supply

Introduction Contact:
Features
sales@microsol.com
The HDI-050-XX digital input module has 4 64 Digital Input Channels www.microsol.com
groups of 16 digital input channels with
common returns. Each group of 16 Interrupt driven 1ms time stamp
channels can be configured to operate with Voltage Input or Voltage Free
Internal Wetting Voltage or Field Wetting Operation
Voltage via onboard selector switches.
High Noise Immunity
There are different module options to cover No part of this
Compact D-type Connector
different field voltage ranges from 10.8V to document should be
165V DC. The HDI-050-XX module Field Voltage Options: reproduced without
provides optical isolation with bi-directional the prior approval of
HDI-050-01 :- 12 VDC
inputs for all input channels Microsol
HDI-050-02 :- 24 VDC
HDI-050-03 :- 48 VDC
HDI-050-04 :- 130 VDC
HDI-050-XX Module Description Rev: 2.7

I/O Interface Characteristics

1 CH1 + 1 CH33 +
20 CH2 + 20 CH34 +
2 CH3 + 2 CH35 +
21 CH4 + 21 CH36 +
3 CH5 + 3 CH37 +
22 CH6 + 22 CH38 +
4 CH7 + 4 CH39 +
23 CH8 + 23 CH40 +
5 CH9 + 5 CH41 +
CH10 + 24 CH42 +
6 CH11 + 6 CH43 +
25 CH12 + 25 CH44 +
7 CH13 + 7 CH45 +
26 CH14 + 26 CH46 +
8 CH15 + 8 CH47 +
27 CH16 + 27 CH48 +
9 COM1 − 9 COM3 −
28 Wetting Enable 1 − 28 Wetting Enable 2 −
10 CH17 + 10 CH49 +
29 CH18 + 29 CH50 +
11 CH19 + 11 CH51 +
30 CH20 + 30 CH52 +
12 CH21 + 12 CH53 +
31 CH22 + 31 CH54 +
13 CH23 + 13 CH55 +
32 CH24 + 32 CH56 +
14 CH25 + 14 CH57 +
33 CH26 + 33 CH58 +
15 CH27 + 15 CH59 +
34 CH28 + 34 CH60 +
16 CH29 + 16 CH61 +
35 CH30 + 35 CH62 +
17 CH31 + 17 CH63 +
36 CH32 + 36 CH64 +
18 COM2 − 18 COM4 −
37 EXTDC + 37 EXTDC +
19 EXTDC − 19 EXTDC −

CONNECTOR A CONNECTOR B
TOP CONNECTOR BOTTOM CONNECTOR
FRONT PLATE LAYOUT
37-WAY D-TYPE MALE 37-WAY D-TYPE MALE
SHOWING CONNECTORS
SOLDER BUCKET SOLDER BUCKET
EJECTOR HANDLES
AND MOUNTING SCREWS

Page 2 of 9
HDI-050-XX Module Description Rev: 2.7

Module Interface Characteristics, Field Wetting


The diagram below shows an example of the wiring necessary to connect the HDI-050-XX module to the plant
equipment where the wetting voltage is provided from the field (SW3-SW6 set to DRY). The recommended
termination board for this card is the TDI-RACKTERM module (32 channels), refer to the TDI-RACKTERM
module description for additional information.

CONNECTOR A
TOP MALE DB37

+EXT VDC

+ CH1 1
Ch1
+ CH2 20
2
+ CH4 21 Ch2
3
22
EXTERNAL FIELD WETTING
4
CONNECTION SHOWN HERE 23
5
24
6
25
7
26
8 Ch16
+ CH16 27
-EXT VDC - COM1 9
28
10 SW3
29
11
30
12
31 Ch17
13
32
14 Ch18
33
15
34
16
35
17 Ch32
36
18
37
19 SW4

MALE XCELL BACKPLANE


SW2 SW1 POWER
+VDC
WETTING VOLT.
ENABLE CIRCUIT -VDC
CONNECTOR B
BOTTOM MALE DB37

+EXT VDC

+ CH33 1 Ch33
+ CH34 20
2
+ CH36 21 Ch34
3
22
EXTERNAL FIELD WETTING 4
CONNECTION SHOWN HERE 23
5
24
6
25
7
26
8 Ch48
+ CH48 27
-EXT VDC - COM1 9
28
10 SW3
29
11
30
12
31 Ch49
13
32
14 Ch50
33
15
34
16
35
17 Ch64
36
18
37
19 SW4

MALE XCELL BACKPLANE


SW2 SW1 POWER
+VDC
WETTING VOLT.
ENABLE CIRCUIT -VDC

Page 3 of 9
HDI-050-XX Module Description Rev: 2.7

Module Interface Characteristics, Internal Wetting


The diagram below shows an example of the wiring necessary to connect the HDI-050-XX module to the plant
equipment where the wetting voltage is provided internally from the HDI Module (SW3-SW6 set to WET).
Connector A is configured for internal wetting supplied by an external supply, connector B in configured for
internal wetting supplied by the backplane voltage. The recommended termination board for this card is the TDI-
RACKTERM module (32 channels), refer to the TDI-RACKTERM module description for additional information.

CONNECTOR A
TOP MALE DB37

+ CH1 1
Ch1
+ CH2 20
2
+ CH4 21 Ch2
3
22
INTERNAL MODULE WETTING 4
FROM EXTERNAL SOURCE 23
CONNECTION SHOWN HERE 5
24
6
25
7
26
8 Ch16
+ CH16 27
- COM1 9
28
10 SW3
29
11
30
12
31 Ch17
13
32
14 Ch18
33
15
34
16
35
17 Ch32
36
18
37
19 SW4

MALE XCELL BACKPLANE


SW2 SW1 POWER
+VDC
WETTING VOLT.
ENABLE CIRCUIT -VDC
CONNECTOR B
BOTTOM MALE DB37

+ CH33 1
Ch33
+ CH34 20
2
+ CH36 21 Ch34
3
22
INTERNAL MODULE WETTING
4
FROM BACKPLANE CONNECTION 23
SHOWN HERE 5
24
6
25
7
26
8 Ch48
+ CH48 27
- COM1 9
28
10 SW3
29
11
30
12
31 Ch49
13
32
14 Ch50
TO ENABLE INTERNAL MODULE 33
WETTING USING VOLTAGE 15
SUPPLIED FORM THE BACKPLANE 34
16
PIN 9 & 28 MUST BE SHORTED
35
TOGETHER, THIS IS DONE BY 17 Ch64
INSTALLING JP1 ON THE 36
TDI-RACKTERM MODULE. LEAVE 18
JP1 OUT UNLESS USING THE 37
BACKPLANE FOR WETTING 19 SW4
VOLTAGE SUPPLY

MALE XCELL BACKPLANE


SW2 SW1 POWER
+VDC
WETTING VOLT.
ENABLE CIRCUIT -VDC

Page 4 of 9
Page 5 of 9
FIELD TDI-RACKTERM INTERFACE DB37 CABLE HDI-050-XX
CONTACTS DIGITAL INPUT
TBXX
MODULE
DI1 1 1
DI2 2 2
3 C
DI3 4 3 J1 CONNECTOR A
DI4 5 4
6 C
DI5 7 5
DI6 8 6 + CH1 1 + CH1 1
Ch1
9 C + CH2 20 + CH2 20
DI7 10 7 + CH3 2 + CH3 2
DI8 11 8 + CH4 21 + CH4 21 Ch2
12 C + CH5 3 + CH5 3
DI9 13 9 + CH6 22 + CH6 22
DI10 14 10 + CH7 4 + CH7 4
15 C + CH8 23 + CH8 23
DI11 16 11 + CH9 5 + CH9 5
DI12 17 12 + CH10 24 + CH10 24
18 C + CH11 6 + CH11 6
DI13 19 13 + CH12 25 + CH12 25
DI14 20 14 + CH13 7 + CH13 7
21 C + CH14 26 + CH14 26
DI15 22 15 + CH15 8 + CH15 8 Ch16
DI16 23 16 + CH16 27 + CH16 27
- COM1 9 - COM1 9
NOTE 1 JP1 28 28
DI17 24 17 + CH17 10 + CH17 10 SW3
RACKTERM module description for additional information.

DI18 25 18 + CH18 29 + CH18 29


26 C + CH19 11 + CH19 11
DI19 27 19 + CH20 30 + CH20 30
DI20 28 20 + CH21 12 + CH21 12
29 C + CH22 31 + CH22 31 Ch17
DI21 30 21 + CH23 13 + CH23 13
DI22 31 22 + CH24 32 + CH24 32
32 C + CH25 14 + CH25 14 Ch18
DI23 33 23 + CH26 33 + CH26 33
DI24 34 24 + CH27 15 + CH27 15
35 C + CH28 34 + CH28 34
DI25 36 25 + CH29 16 + CH29 16
DI26 37 26 + CH30 35 + CH30 35
38 C + CH31 17 + CH31 17 Ch32
DI27 39 27 + CH32 36 + CH32 36
DI28 40 28 - COM2 18 - COM2 18
41 C 37 +EXT VDC 37
DI29 42 29 19 -EXT VDC 19 SW4
DI30 43 30 F1
44 C
DI31 45 31
DI32 46 32 XCELL BACKPLANE
F2 FEMALE MALE FEMALE MALE
SW2 SW1 POWER
TB3
VDC INPUT +V +VDC
-V WETTING VOLT.
WETTING ENABLE CIRCUIT -VDC
TB4

GND
Module Interface, HDI-RACKTERM Connection
The diagram below shows a typical connection to the TDI-RACKTERM module (32 channels), refer to the HDI-
HDI-050-XX Module Description Rev: 2.7
HDI-050-XX Module Description Rev: 2.7

Module Switch Settings


The HDI-050-XX digital input module has a number of user configurable settings selectable by switches, the
position and function of these switches is shown in the diagram below.

SW4 SW3
DRY DRY

WET WET

HDI-050

SW6 SW5
DRY DRY

WET WET

SW1 SW2

Neg Pos Front Back

SW1 SW2

Backplane Backplane Module Module


Negative Positive Powered Powered
Wetting Wetting from Front from
Voltage Voltage Connector Backplane

When internal wetting is supplied by the backplane voltage, pins 9 & 28 must be shorted; this is accomplished at the
termination board by installing JP1. The wetting voltage enable circuit will then disconnect the voltage from the male DB37 on
the HDO-050 module when the termination connection cable is unplugged. This will prevent inadvertant contact with potentially
unsafe voltage levels on the DB37 pins. When not using the backplane voltage as wetting supply leave JP1 on termination
board out.

Page 6 of 9
HDI-050-XX Module Description Rev: 2.7

Switch Position Function


SW1 Backplane Wetting Polarity
Common Neg Vdc- is commond internally to all channels and Vdc+ is
Select availableon the Common Pins of the Front Connectors for
applying to each channel.
Pos Vdc+ is commoned internally to all channels and Vdc- is
available on the Common Pins of the Front Connectors for
applying to each channel
SW2 Source of Wetting Voltage
Power Front Contacts are Wet from the Front Connector
Back Contacts are Wet from the Backplane
SW3 Volt Free/Voltage Input Mode Channels 1-16
Wet Contacts are internally Wet and do not require Field
Voltage
Dry Contacts are internally Dry and require Field Voltage
SW4 Volt Free/Voltage Input Mode Channels 17-32
Wet Contacts are internally Wet and do not require Field
Voltage
Dry Contacts are internally Dry and require Field Voltage
SW5 Volt Free/Voltage Input Mode Channels 33-48
Wet Contacts are internally Wet and do not require Field
Voltage
Dry Contacts are internally Dry and require Field Voltage
SW6 Volt Free/Voltage Input Mode Channels 49-64
Wet Contacts are internally Wet and do not require Field
Voltage
Dry Contacts are internally Dry and require Field Voltage

Page 7 of 9
HDI-050-XX Module Description Rev: 2.7

Module Troubleshooting
This section provides some basic information about troubleshooting the operation of the HDI-050-XX
module.

Symptoms Possible Cause Possible Action


Error message when downloading The hardware configuration has Verify and save the hardware
a configuration not been saved configuration
In Internal Module Wetting mode, The card has no external DC Verify the LED display. Verify
no input seems to be detected supply the presence of external DC.
Verify the switch settings on the
card.
In External Field Wetting mode, The card or channel has no Verify the LED display. Verify
no input seems to be detected incoming DC supply or the presence of external DC.
reference to ground Verify the reference to ground.
Verify the switch settings on the
card.
No inputs are reported via a Incorrect protocol configuration Using Workbench, visualise the
protocol IO module and verify the correct
operation of the channel. Then
check the protocol
Inputs are detected, but the Possible overlap in the protocol Verify the integrity of the
wrong message is reported via configuration protocol mapping
the protocol

Page 8 of 9
HDI-050-XX Module Description Rev: 2.7

Technical Characteristics
Module Related Data
Number of Inputs 64
Type of Input Single Ended (4 groups of 16)
Indication processing Single, Fleeting, double indications
Bit pattern, transformer states (TAP’s), counting values (up to 30Hz)
Max. Differential voltage between inputs 165 V
Isolation 5 kVpp channel to cell
Module Power consumption 2W
Note 1
Input Circuit HDI-050-01 HDI-050-02 HDI-050-03 HDI-050-04
Nominal Voltage 12V DC 24V DC 48V DC 130V DC
Channel Input Voltage (Field Voltage) 8V – 30V DC 18V – 55V DC 40V – 75V DC 95V – 145V DC
Input resistance 4.4 KΩ 9.4 KΩ 20 KΩ 44 KΩ
Typical Switching Voltage 10.8 V 12V 25V 60V
Power Consumption (64 channels ON at nominal 2.8W 3.8W 7W 14.2W
voltage +20%)
Filter Times, Acquisition Times
Time Stamp Resolution 1 ms
User Configurable Validation filter 3 ms to 60 s
Indications and Diagnostics
Process Indications 1 green LED per channel on associated CPR module (indicating channel
state)
Electrical Noise Immunity
High Frequency disturbance • IEC 60255-22- 1 Class 3 and C37.90.1
Fast Transient disturbance • IEC 61000-4-4 Class 4 and C37.90.1
Electrostatic Discharge • IEC 61000-4-2
RFI Susceptibility • IEC 61000-4-3 CISPR 22
EMC Compliance • IEC 60255-22-3, EN50082-2
UK National Grid Company NGTS 2.13 • Class Z

Environmental Conditions
Temperature
• Continuous Operation • -10° to +70° C
• Transportation and storage • -40° to +70° C
IEC 60068-2-1 & IEC 60068-2-2

Relative Humidity • 0 to 95% non-condensing


IEC 60068-2-3 & IEC 60068-2-30

Vibration • IEC 60068-2-6


Drop & Topple • IEC 60068-2-31
MTBF
For continuous operation at average temperature 241,967 hrs
of 40°C
Dimensions and Weight
Dimensions (W * H * D) 5 hp x 6U (1 x 10.5 x 6.7 inches) / (25.4 x 266.7 x 170mm)
Weight Approx. 0.55 lbs / 250 grams

Note 1: HDI-050-02 is equivalent to the base model HDI-050, i.e. these two are interchangeable

Model / Part Number Description


HDI-050-01 64 Channel Digital Input Module (Input Range: 8-30V DC or Volt free)
HDI-050-02 64 Channel Digital Input Module (Input Range: 18- 55V DC or Volt free)
HDI-050-03 64 Channel Digital Input Module (Input Range: 40-75V DC or Volt free)
HDI-050-04 64 Channel Digital Input Module (Input Range: 95-145V DC or Volt free)

Email: sales@microsol.com Web: www.microsol.com

© Microsol Ltd. 2006 The information in this document is subject to change without prior
notice. Microsol does not assume responsibility for any errors in fact or design in this
publication. The publication is provided for general information only and shall not form part
of any contract.
HDI-050 issue 2.5