Module Description HDI-050-XX 2.7
Module Description HDI-050-XX 2.7
Module Description HDI-050-XX 2.7
Ch1
DC
Ch16
DC
Common
SW3
External Field
Wetting Voltage
HDI-050-XX
Group of 16 Channels
Ch49
Ch64
Common
SW6 XCell
Backplane
SW2 Power
VDC
DC
Internal Module
HDI-050-XX
Wetting Voltage via
External Supply
Introduction Contact:
Features
sales@microsol.com
The HDI-050-XX digital input module has 4 64 Digital Input Channels www.microsol.com
groups of 16 digital input channels with
common returns. Each group of 16 Interrupt driven 1ms time stamp
channels can be configured to operate with Voltage Input or Voltage Free
Internal Wetting Voltage or Field Wetting Operation
Voltage via onboard selector switches.
High Noise Immunity
There are different module options to cover No part of this
Compact D-type Connector
different field voltage ranges from 10.8V to document should be
165V DC. The HDI-050-XX module Field Voltage Options: reproduced without
provides optical isolation with bi-directional the prior approval of
HDI-050-01 :- 12 VDC
inputs for all input channels Microsol
HDI-050-02 :- 24 VDC
HDI-050-03 :- 48 VDC
HDI-050-04 :- 130 VDC
HDI-050-XX Module Description Rev: 2.7
1 CH1 + 1 CH33 +
20 CH2 + 20 CH34 +
2 CH3 + 2 CH35 +
21 CH4 + 21 CH36 +
3 CH5 + 3 CH37 +
22 CH6 + 22 CH38 +
4 CH7 + 4 CH39 +
23 CH8 + 23 CH40 +
5 CH9 + 5 CH41 +
CH10 + 24 CH42 +
6 CH11 + 6 CH43 +
25 CH12 + 25 CH44 +
7 CH13 + 7 CH45 +
26 CH14 + 26 CH46 +
8 CH15 + 8 CH47 +
27 CH16 + 27 CH48 +
9 COM1 − 9 COM3 −
28 Wetting Enable 1 − 28 Wetting Enable 2 −
10 CH17 + 10 CH49 +
29 CH18 + 29 CH50 +
11 CH19 + 11 CH51 +
30 CH20 + 30 CH52 +
12 CH21 + 12 CH53 +
31 CH22 + 31 CH54 +
13 CH23 + 13 CH55 +
32 CH24 + 32 CH56 +
14 CH25 + 14 CH57 +
33 CH26 + 33 CH58 +
15 CH27 + 15 CH59 +
34 CH28 + 34 CH60 +
16 CH29 + 16 CH61 +
35 CH30 + 35 CH62 +
17 CH31 + 17 CH63 +
36 CH32 + 36 CH64 +
18 COM2 − 18 COM4 −
37 EXTDC + 37 EXTDC +
19 EXTDC − 19 EXTDC −
CONNECTOR A CONNECTOR B
TOP CONNECTOR BOTTOM CONNECTOR
FRONT PLATE LAYOUT
37-WAY D-TYPE MALE 37-WAY D-TYPE MALE
SHOWING CONNECTORS
SOLDER BUCKET SOLDER BUCKET
EJECTOR HANDLES
AND MOUNTING SCREWS
Page 2 of 9
HDI-050-XX Module Description Rev: 2.7
CONNECTOR A
TOP MALE DB37
+EXT VDC
+ CH1 1
Ch1
+ CH2 20
2
+ CH4 21 Ch2
3
22
EXTERNAL FIELD WETTING
4
CONNECTION SHOWN HERE 23
5
24
6
25
7
26
8 Ch16
+ CH16 27
-EXT VDC - COM1 9
28
10 SW3
29
11
30
12
31 Ch17
13
32
14 Ch18
33
15
34
16
35
17 Ch32
36
18
37
19 SW4
+EXT VDC
+ CH33 1 Ch33
+ CH34 20
2
+ CH36 21 Ch34
3
22
EXTERNAL FIELD WETTING 4
CONNECTION SHOWN HERE 23
5
24
6
25
7
26
8 Ch48
+ CH48 27
-EXT VDC - COM1 9
28
10 SW3
29
11
30
12
31 Ch49
13
32
14 Ch50
33
15
34
16
35
17 Ch64
36
18
37
19 SW4
Page 3 of 9
HDI-050-XX Module Description Rev: 2.7
CONNECTOR A
TOP MALE DB37
+ CH1 1
Ch1
+ CH2 20
2
+ CH4 21 Ch2
3
22
INTERNAL MODULE WETTING 4
FROM EXTERNAL SOURCE 23
CONNECTION SHOWN HERE 5
24
6
25
7
26
8 Ch16
+ CH16 27
- COM1 9
28
10 SW3
29
11
30
12
31 Ch17
13
32
14 Ch18
33
15
34
16
35
17 Ch32
36
18
37
19 SW4
+ CH33 1
Ch33
+ CH34 20
2
+ CH36 21 Ch34
3
22
INTERNAL MODULE WETTING
4
FROM BACKPLANE CONNECTION 23
SHOWN HERE 5
24
6
25
7
26
8 Ch48
+ CH48 27
- COM1 9
28
10 SW3
29
11
30
12
31 Ch49
13
32
14 Ch50
TO ENABLE INTERNAL MODULE 33
WETTING USING VOLTAGE 15
SUPPLIED FORM THE BACKPLANE 34
16
PIN 9 & 28 MUST BE SHORTED
35
TOGETHER, THIS IS DONE BY 17 Ch64
INSTALLING JP1 ON THE 36
TDI-RACKTERM MODULE. LEAVE 18
JP1 OUT UNLESS USING THE 37
BACKPLANE FOR WETTING 19 SW4
VOLTAGE SUPPLY
Page 4 of 9
Page 5 of 9
FIELD TDI-RACKTERM INTERFACE DB37 CABLE HDI-050-XX
CONTACTS DIGITAL INPUT
TBXX
MODULE
DI1 1 1
DI2 2 2
3 C
DI3 4 3 J1 CONNECTOR A
DI4 5 4
6 C
DI5 7 5
DI6 8 6 + CH1 1 + CH1 1
Ch1
9 C + CH2 20 + CH2 20
DI7 10 7 + CH3 2 + CH3 2
DI8 11 8 + CH4 21 + CH4 21 Ch2
12 C + CH5 3 + CH5 3
DI9 13 9 + CH6 22 + CH6 22
DI10 14 10 + CH7 4 + CH7 4
15 C + CH8 23 + CH8 23
DI11 16 11 + CH9 5 + CH9 5
DI12 17 12 + CH10 24 + CH10 24
18 C + CH11 6 + CH11 6
DI13 19 13 + CH12 25 + CH12 25
DI14 20 14 + CH13 7 + CH13 7
21 C + CH14 26 + CH14 26
DI15 22 15 + CH15 8 + CH15 8 Ch16
DI16 23 16 + CH16 27 + CH16 27
- COM1 9 - COM1 9
NOTE 1 JP1 28 28
DI17 24 17 + CH17 10 + CH17 10 SW3
RACKTERM module description for additional information.
GND
Module Interface, HDI-RACKTERM Connection
The diagram below shows a typical connection to the TDI-RACKTERM module (32 channels), refer to the HDI-
HDI-050-XX Module Description Rev: 2.7
HDI-050-XX Module Description Rev: 2.7
SW4 SW3
DRY DRY
WET WET
HDI-050
SW6 SW5
DRY DRY
WET WET
SW1 SW2
SW1 SW2
When internal wetting is supplied by the backplane voltage, pins 9 & 28 must be shorted; this is accomplished at the
termination board by installing JP1. The wetting voltage enable circuit will then disconnect the voltage from the male DB37 on
the HDO-050 module when the termination connection cable is unplugged. This will prevent inadvertant contact with potentially
unsafe voltage levels on the DB37 pins. When not using the backplane voltage as wetting supply leave JP1 on termination
board out.
Page 6 of 9
HDI-050-XX Module Description Rev: 2.7
Page 7 of 9
HDI-050-XX Module Description Rev: 2.7
Module Troubleshooting
This section provides some basic information about troubleshooting the operation of the HDI-050-XX
module.
Page 8 of 9
HDI-050-XX Module Description Rev: 2.7
Technical Characteristics
Module Related Data
Number of Inputs 64
Type of Input Single Ended (4 groups of 16)
Indication processing Single, Fleeting, double indications
Bit pattern, transformer states (TAP’s), counting values (up to 30Hz)
Max. Differential voltage between inputs 165 V
Isolation 5 kVpp channel to cell
Module Power consumption 2W
Note 1
Input Circuit HDI-050-01 HDI-050-02 HDI-050-03 HDI-050-04
Nominal Voltage 12V DC 24V DC 48V DC 130V DC
Channel Input Voltage (Field Voltage) 8V – 30V DC 18V – 55V DC 40V – 75V DC 95V – 145V DC
Input resistance 4.4 KΩ 9.4 KΩ 20 KΩ 44 KΩ
Typical Switching Voltage 10.8 V 12V 25V 60V
Power Consumption (64 channels ON at nominal 2.8W 3.8W 7W 14.2W
voltage +20%)
Filter Times, Acquisition Times
Time Stamp Resolution 1 ms
User Configurable Validation filter 3 ms to 60 s
Indications and Diagnostics
Process Indications 1 green LED per channel on associated CPR module (indicating channel
state)
Electrical Noise Immunity
High Frequency disturbance • IEC 60255-22- 1 Class 3 and C37.90.1
Fast Transient disturbance • IEC 61000-4-4 Class 4 and C37.90.1
Electrostatic Discharge • IEC 61000-4-2
RFI Susceptibility • IEC 61000-4-3 CISPR 22
EMC Compliance • IEC 60255-22-3, EN50082-2
UK National Grid Company NGTS 2.13 • Class Z
Environmental Conditions
Temperature
• Continuous Operation • -10° to +70° C
• Transportation and storage • -40° to +70° C
IEC 60068-2-1 & IEC 60068-2-2
Note 1: HDI-050-02 is equivalent to the base model HDI-050, i.e. these two are interchangeable
© Microsol Ltd. 2006 The information in this document is subject to change without prior
notice. Microsol does not assume responsibility for any errors in fact or design in this
publication. The publication is provided for general information only and shall not form part
of any contract.
HDI-050 issue 2.5
Page 9 of 9