Electrical Signaling, Alarm Signal Initiating Devices, Fire Detection, Heat-Actuated, Fire Detection, Heat-Actuated
MS1000 Series Linear Heat Detectors used with MS1000-I Linear Detector Interface and MS1000-P End of Line Unit. Alarm operating
temperature ratings: 68, 88, 105, 138, and 180ºC, (154, 190, 221, 280, and 356°F). The heat detectors’ individual Model designations are
MS1000 plus the ºC operating temperature rating. Each detector is a continuous line type open circuit detector that shorts when in an alarm
condition. Spacing guide for the cables: MS1000 68ºC and 88ºC, 25 x 25 ft (7.6 x 7.6 m); MS1000 105ºC and 138ºC, 15 x 15 ft (4.6 x 4.6
m). MS1000 180ºC is intended for proximity detection only. MS1000-I Interface operates on 24 V dc and provides alarm relay output for
connection to a compatible Approved control. The MS1000-I operating temperature range is -49ºF (-45ºC) to 140ºF (60ºC).
This certifies that the equipment described has been found to comply with the applicable requirements, as stated in the Approval Report(s),
of the following FM Approval Standards and other documents:
Related Report:
Subsequent Revisions:
15 February 2018
_________________________ _________________________
J. E. Marquedant Date
VP, Manager of Electrical Systems
FM Approvals
1151 Boston-Providence Turnpike,