Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

Pump motor selection

It’s important to size an electric motor properly. Doing so will produce a


pumping unit that is more efficient and provides a longer service life.
Failing to size the motor correctly will result in a pumping unit that
demands more power than it should or one that produces repeated electric
faults and may suffer from premature motor failure.

A Basic Introduction to Pump


Motors

Electric motors are generally sized at predetermined intervals. What this


means is that in most cases you will need to round up to the next available
motor size when determining how large a motor to couple up to a pump.
So if the pump power requirements indicate that the motor should be rated
for at least 4.5 HP, you’ll have to round up to the next normal motor
rating: 5 HP.

While you don’t want to an undersize and electric motor, the vast majority
of motors are designed with a 1.15 service factor which will provide a bit
of an insurance policy. What this means is that a motor rated for 100 HP is
actually capable of continuous operation at up to 115 HP (100 x 1.15).
However, if the motor is operated on a variable frequency drive additional
heat will be generated and the service factor will no longer come into play.
Factors that Drive Motor Sizing
There are at least three major considerations to keep in mind when sizing a
motor to drive a centrifugal pump:

1. What are the power demands of the pump?


2. What will a typical operation look like for this pump?
3. Will the pump be operated on a variable frequency drive (VFD)?

What are the Power Demands of the


Pump?
This first question has two parts:

 What is the power demand at the rated design condition?


 What is the maximum power required to operate the pump at any point on
the pump performance curve?

The power required to drive the pump at the rated design condition should
always be less than the nameplate horsepower rating of the motor. So if
the pump will require 4.5 HP at the design condition, at a minimum, the
motor should be sized for 5 HP – the next nominal size above 4.5 HP.

In many cases, it will make sense to select a motor large enough to handle
the maximum power demanded by the pump at any point along the curve.
This maximum power value is referred to as the non-overloading brake
horsepower of the pump, or NOL BHP. Sizing a motor to handle this
power demand will ensure that the motor will be able to operate the pump
even if the operating conditions change dramatically.

What Will Typical Operation Look Like


for This Pump?
Some pumps are installed into systems where it is known that the pump
will operate at the rated design condition 100% of the time. However,
most systems will require that the pump operates across a wide range of
conditions. For those cases where the pump will operate continuously at a
single condition, sizing the motor for the power demands at that condition
is acceptable. In other cases, where a range of operating heads will be
encountered, it is best to size the motor to handle the NOL BHP of the
pump.

Will the Pump be Operated by a Variable


Frequency Drive?
If a pump will be operated on a VFD, then the motor should be sized for
the pump NOL BHP, and the motor nameplate HP should be more than the
pump NOL BHP without any consideration given to the motor service
factor. Remember, the motor service factor disappears when the motor is
operated by a VFD. The only exception to this is a case where the pump
will operate at a single condition 100% of the time.

If the pump will not be operated on a VFD, then sizing the motor becomes
a matter of choice. Best practice dictates that in all cases the motor
nameplate HP rating should exceed the power demanded by the pump at
the design condition, and many customers also want the NOL BHP to be
less than the motor nameplate HP.

In other cases, the motor nameplate HP rating will be selected to exceed


the power demanded by the pump at the design condition but will be less
than the NOL BHP. This is ok as long as the customer understands how
the motor was selected, and as long as NOL BHP is less than the
nameplate HP rating of the motor plus the service factor.

In Conclusion
Selecting the right motor rating is an important step in ensuring that the
entire pumping unit provides reliable and efficient performance for years
to come. Understanding and following the basic guidelines in this blog
will help ensure the right motor rating is selected every time.

You might also like