Professional Documents
Culture Documents
Detector Service Manual
Detector Service Manual
Governor
ELECTRONIC GOVERNOR
Generator frequency is in direct ratio to engine
speed, which is controlled by the governor. The
governor control has four potentiometers for
making adjustments. See Figure 6-1. Use a
frequency meter or tachometer to monitor the unit
during adjustment procedure.
GROUND
Gain: The Gain control is a one-turn potentiometer.
It is used to adjust the sensitivity of the governor. A
clockwise rotation of the potentiometer will shorten
the response time to load changes.
Droop: The Droop control is a one-turn
potentiometer. It is adjustable for 0 % (isochronous)
1 2 3 4 5 6 7 8 9 10 11
to more than 5% speed droop. Fully
IDLE SPEED
counterclockwise rotation is 0% speed droop.
RUN SPEED
Idle Speed: The Idle Speed control is a 20-turn
potentiometer for adjusting the idle speed. A GAIN
clockwise rotation will increase the idle speed. DROOP
Run Speed: The Run Speed control is a 20-turn
potentiometer for setting the desired no-load
governed speed. A clockwise rotation will increase
the run speed.
Refer to the following adjustment procedures.
Adjustments
Preliminary Adjustments: FIGURE 6-1. ELECTRONIC GOVERNOR CONTROL
1. Frequency Adjust (engine speed) potentiome-
ter on control panel (if equipped).
A. Loosen the locking nut.
B. With a screwdriver, turn the potentiometer
fully counterclockwise, then fully clock-
wise, then to mid position.
C. Hold mid position setting with screwdriver,
and tighten locking nut.
2. Idle Speed potentiometer.
A. Turn the screw counterclockwise until the
clutch slips (noticeable click).
B. Turn the screw clockwise 10 turns.
C. This will set the idle speed potentiometer
to its mid position.
Performance Checks
F
F
If the generator set operation is rough or surges,
review the following:
ACTUATOR
1. Start the generator set and check voltage read- STUDS FUEL
ings at governor control terminals for; magnetic SHUTOFF
pickup (1.5 VAC minimum at cranking, to 30 VALVE
VAC maximum at genset operating speed),
battery B+ (24 VDC), fuel pump actuator
(19-20 VDC).
2. Stop generator set, disconnect the leads to the
actuator (see Figure 6-3), and connect battery
voltage directly to the actuator studs. An audi-
ble click in the actuator should be heard when
battery voltage is applied and removed. This
check only shows that the actuator is operating
(rotating to open and closed position), but not if
its binding, further disassembly of fuel pump
may be required to inspect/repair O-rings,
pump, etc.
FUEL
3. If further tests and repair is required, contact FLOW
your Cummins Power Generation distributor
for further information, or request a copy of
Electric Fuel Control Governor brochure (bulle-
tin no. 3379231-03). F
F