DBV 5 Pro - R410A - 50Hz - 27.10.2021
DBV 5 Pro - R410A - 50Hz - 27.10.2021
DUNHAM-BUSH PRODUCT
OVERVIEW
The DBV-5 Pro central VRF offering a flexible combination with 2 HP increment, could be up to 96 HP in combination. User
friendly design, meeting multiple requirements of different environment, and it’s widely used in today’s intelligent buildings,
such as offices, shopping malls, schools, hospitals, commercial buildings etc.
High efficiency DC inverter scroll compressor with large capacity, combined with the latest 180°sine wave DC inverter
technology, stepless vector variable frequency drive technology, R410A environmental refrigerant, makes DBV to be
energy-saving and environmentally friendly, long performance life, with ease of maintenance.
Nomenclature
Outdoor Unit DBV - D 280 W / Z R1
DBVP : Top Discharge Refrigerant Type
DBV : Side Discharge R1 : R410A
Series Code Power Supply
D : T1/ T3 Full DC Inverter Cooling / Heat Pump Blank : 220-240V/1PH/50Hz
C : T1/ T3 Full DC Inverter Cooling Only Z : 380-415V/3PH/50Hz
13 Basic Modules
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP
Capacity
25.2kW 28kW 33.5kW 40kW 45kW 50kW 56kW 61.5kW 67kW 73kW 78.5kW 85kW 90kW
Compressor DC DC DC DC DC DC DC DC DC+DC DC+DC DC+DC DC+DC DC+DC
Fan motor DC DC DC DC DC DC+DC DC+DC DC+DC DC+DC DC+DC DC+DC DC+DC DC+DC
6 5.5
5.38 5.1
4.75 4.82 4.71 5.10 4.86 4.73
5 4.5 4.6 4.45
4.11 4.45 4.11
4.01 4.1 4.09 4.02
3.87 3.82 4.01 3.92 3.80
3.70 3.63
4
0
8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP
IPLV (C)
IPLV:Integrated Part Load Value(ARI 550/590) 9.60 9.50
10.0 9.40 9.30 9.10 9.10 8.90 8.80
(C):Cooling condition 9.0
The Integrated Part Load VaIue (IPLV) is a performance 8.0
characteristic developed by the Air-Conditioning, Heating
7.0
and Refrigeration institute (AHRI). It is most commonly
used to describe the performance of a AC system capable 6.0
of capacity modulation. Unlike an EER (Energy Efficiency 5.0
Ratio) or COP (coefficient of performance), which 3.60 3.60
4.0
describes the efficiency at full load conditions, the IPLV is 3.55 3.55 3.55 3.55 3.55 3.55
derived from the equipment efficiency while operating at 3.0
various capacities. Since a VRF system does not always 2.0
run at l00% capacity, the EER or COP is not an ideal
1.0
representation of the typical equipment performance. The
IPLV is a very important value to consider since it can 0
affect energy usage and operating costs throughout the 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP
lifetime of the equipment.
National Standard (GB 21454-2008) DBV-5 Pro
Combination Table
DBVP-D - Cooling / Heat Pump
Combination Max.
Capacity
IDU
(HP) 8HP 10HP 12HP 14HP 16HP 18HP 20HP 22HP 24HP 26HP 28HP 30HP 32HP Qty
8 13
10 16
12 19
14 23
16 26
18 29
20 33
22 36
24 39
26 43
28 46
30 50
32 53
34 56
36 59
38 63
40 100
42 100
44 100
46 100
48 100
50 100
52 100
54 100
56 100
58 100
60 100
62 100
64 100
66 100
68 100
70 100
72 100
74 100
76 100
78 100
80 100
82 100
84 100
86 100
88 100
90 100
92 100
94 100
96 100
*Note: Max 4 outdoor units can be freely combined up to 96HP. Whenever 4 outdoor units are combined, the single unit capacity can not exceed 24HP.
AI Cloud Server
Voltage
Refrigerant Cooling Design -30°C -20°C -10°C 0°C 10°C 20°C 30°C
We use refrigerant to cool down inverter modular board to
keep it in a safe condition even when outdoor temperature is
up to 55°C.
40% ~ 100%
Rs485 WIFI
Function setting
12 Status Checking
Commissioning
Auto Charging
* when 4 outdoor units are combined, the single unit capacity can not exceed 24HP.
Stepless Control
DC fan motor can be stepless contolled by outdoor PCB according to system's operating pressure. And it is able to reduce the
energy consumption and maintain the system in the best performance.
Load-Revolution curve
1400
1200
700
50%
energy
saved
200
Load
0% 50% 100% 130%
DC motor stepless adjustment AC motor 2-speed adjustment Energy wasted Low performance
5000 8000
K)
100 200 300 400 100 200 300 400
CCT Inner-grooved Tube Conventional Tube CCT Inner-grooved Tube Conventional Tube
Increase the
liquidrefrigerant
volumeproportion
Gas Liquid
Conventional design
Gas Liquid
2-in-1 Refrigerant
Flow Path Design
Conventional Fins
100
70
1 2 3 4
Convention Fins Cross Flow Fins Face velocity(m/s)
Time
Dunham-Bush VRF system Conventional fixed speed system
Brushless DC motor
Streamline air duct design
Circuit Silencer
100
Load drops
50
Load %
0
8hrs 10hrs
Noise dB(A)
58 Silent mode
50
Max.10 dB(A) of noise drops
Snow-Proof Function
In the cold weather, outdoor fan will start to run for a while at intervals, to prevent
snow accumulation on the fan blade. The accumulated snow will possibly block fan
blade movement and damage the motor.
It only start when temperature is lower than 0°C.
√ √
√ √ √
Time x:
Start order:A →B→C
Time x+2:
Start order:C →A→B
Time x+1:
In one combination system, any outdoor unit can run as master unit.
Start order:B →C →A
Balance the lifespan among outdoor units in one system.
Stop
Addressing Methods
Environment Friendly
Refrigerant R410A(HFC), low carbon footprint, no harm to 2 addressing methods:
Ozone. Automatically addressing: system
R410A(HFC), low carbon footprint, no harm to Ozone. will distribute address to indoor
Lig
ht Stra
tos
phe
unit automatically.
UV re
UV light Manually setting by wireless
ere
sph
remote controller.
o
Trop
Automatic Addressing
Automatic addressing will reduce artificial faults by 35% and 5% manual works.
54% system failure were caused by communication faults.
65% communication faults were caused by address problems.
Most of the address problems were: address setting forgotten,wrong settings, address repeat.
Failure chart
Communication faults Others
65%
54%
Others
Addressing problems
Address faults was awarded to the most hated fault after had investigated 120 VRF after-sale engineers in 2011.
Service Window
Thanks to the service window, checking outdoor unit's
Error Code Check
status and setting is now easy, no need to remove the
electric control box cover.
Mode Restriction
6 kinds of mode restriction
Auto priority(Default Setting) Cooling(or heating)priority mode. Cooling only(or heating only)mode. VIP unit priority
Auto priority Heating priority Cooling priority Heating only Cooling only VIP unit priority
(Default Setting)
4 th stage 5 th stage
Oil balance between compressors Oil return bysystem oil return program
3rd stage:
Oil return from
the system oil separator
All key components are designed to close to outside, it is convenient for repair and
replacement.
Thanks to the new balance technology, gas balance pipe does no longer exist
brazing points and leaking risk are decreased.
Easy Installation
Easy for the outdoor unit to
transport to roof floor by elevatordue
to its compact size. Easy for transportation
Between IDUs m 40 40
Between ODUs m 0 0
Operation temperature range
Outdoor side °C -5~55 -5~55
Cooling Indoor side 16~32 16~32
°C
Outdoor side °C -30~30 -30~30
Heating
Indoor side °C 16~32 16~32
Notes: 1. Cooling operating temperature range is from -5°C to 55°C (It can be customized down to -10°C). Heating operating temperature range from -30°C to 30°C.
2. The cooling conditions: indoor side 27°C (80.6F) DB, 19°C (60℉)WB outdoor side 35°C (95℉) DB.
3. The heating conditions: indoor side 20°C (68℉) DB, 15°C (44.6℉)WB outdoor side 7°C (42.8℉) DB.
4. Sound level: measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation, these values are normally somewhat higher as a result of ambient conditions.
5. The above data may be changed without notice for future improvement on quality and performance.
1 2
DC Inverter Scroll DC Inverter Scroll
HITACHI HITACHI
R410A
15 16 20 23
EXV EXV
1340x1740x840 1990x1740x840
1410x1900x910 2060x1900x910
285 290 297 388 433 480
303 308 315 406 452 498
62 63 62 63 64
4.5
Φ15.88 Φ22.2
Φ28.6 Φ35.0
1000 1000
200 200
240 240
40/90 40/90
100 100
110 110
40 40
0 0
-5~55 -5~55
16~32 16~32
-30~30 -30~30
16~32 16~32
Quantity 1
Type R410A
Refrigerant
Volume Kg 10 12.5
Between OU & IU m
(OU above IU) 100
Max. m
Between OU & IU
Vertical (OU below IU) 110
length
Between IUs m 40
Between Ous m 0
*The above data may be changed without noitce for future improvement.
1 2
DC Inverter Twin-Rotary
Mitsubishi
R410A
840x1740x1340 840x1740x1990
910x1900x1410 910x1900x2060
62 63 65 66 67
4.5
Φ15.9 Φ22.2
Φ28.6 Φ35
1000
200
240
90
100
110
40
-15~55
16~32
20kW
DC
DC+DC
5 4.27 4.21
4.29 3.98 4.11 4.17 4.10
4.13 3.91 3.85
3.70 3.47 3.45 3.54 3.49
4 3.55 3.63 3.53
3.39 3.33 3.38 3.32
3.37
3.08
3
0
8KW 10KW 12.5KW 14KW 16KW 18KW 20KW 22.4KW 26KW 28KW 33.5KW Average
High
High Efficiency, Low Noise reliability
Optimized the efficiency and noise during operation with the latest
technology.
Scroll inverter compressor
Low
vibration
Environmental Protection
Developed the compressor with alternativere frigerant which can protect
environment.
Low
noise
Low Vibration
Reduced the vibration during compressor start and operation. Long
life
Twin-rotary inverter compressor
Silent Technology
Brushless Adopting permanent magnet
DC motor rotor,low vibration and low noise.
Outdoor unit running above 50°C need customization in factory, please contact Dunham-Bush sales representative.
Time
Power factor refers to the relationship between effective power and total power consumption, power factor is
effective power divided by total power consumption.
Power factor can measure power utilization rate. Bigger power factor indicates, higher power utilization rate.
Silent EXV
DC motor
DBV-D260W/ZR1 380-415/3/50 26 88700 7.54 3.45 28.5 97200 6.77 4.21 6.1 1278 1120 142 162 12
x x
DBV-D280W/ZR1 380-415/3/50 28 95500 8.31 3.37 31.5 107500 8.18 3.85 8 60 1703 1549 154 174 22.2 15
x x Φ12.7
DBV-D335W/ZR1 380-415/3/50 33.5 114300 9.46 3.54 37.5 128000 8.99 4.17 8 560 528 154 174 18
Notes: 1.Cooling Operation Conditions: Indoor Air Inlet Temperature: 27°C DB / 19°C WB, T1: Outdoor Air Inlet Temperature: 35°C DB, T3: Outdoor Air Inlet Temperature: 46°C DB
2.Heating Operation Conditions: Indoor Air Inlet Temperature: 20.0°C DB,Outdoor Air Inlet Temperature: 7°C DB / 6°C WB
Accessories
Specification
DBV
DBV
DBV
DBV
DBV
DBV
Accessories
Specification
DBV
DBV
DBV
DBV
Accessories
Specification
4-Way Cassette (Compact Type)
DBV
DBV
DBV
DBV
Round-Flow Cassette
DBV-V56QR/HR1 50Hz 5.6 19.1 6.3 21.4 500 32-39 24 30 Ø12.7 Ø6.5
DBV-V71QR/HR1 50Hz 7.1 24.2 8.0 27.2 920×265×985 833×232×900 24 30
700 35-39
DBV-V80QR/HR1 50Hz 8.0 27.2 8.8 30 24 30
DBV-V90QR/HR1 50Hz 9.0 30.7 10 34.1 28.5 35
Ø25
DBV-V100QR/HR1 50Hz 10 34.1 11 37.5 1030×105×1030 950×50×950 28.5 35 Ø15.9 Ø9.52
820 37-41
DBV-V112QR/HR1 50Hz 11.2 38.2 12.5 42.6 28.5 35
920×310×985 833×286×900
DBV-V125QR/HR1 50Hz 12.5 42.6 14 47.7 28.5 35
DBV-V140QR/HR1 50Hz 14 47.7 15 51.1 28.5 35
1050 38-42
DBV-V160QR/HR1 50Hz 16 54.5 17 58 28.5 35
Accessories
DC Motor
Flexible In Installation
Specification
Capacity Motor Sound Dimension (WxHxD) Body weight Connecting pipe
Power Air flow Standard
Model name Cooling Heating input level Packing Body Net Gross Gas Liquid Drain
type controller
DBV-D22G/HR1 50Hz 2.2 7.5 2.5 8.5 15 410 241 24~33 870x365x280 782x277x210 8.5 10
9.52
DBV-D28G/HR1 50Hz 2.8 9.5 3.2 10.9 15 410 241 24~33 870x365x280 782x277x210 8.5 10
DBV-D36G/HR1 50Hz 3.6 12.2 4.0 13.6 18 640 377 27~36 1045x400x330 948x314x239 13.0 15 6.35
Remote
20
12.7 control
DBV-D45G/HR1 50Hz 4.5 15.3 5.0 17.0 20 640 377 29~38 1045x400x330 948x314x239 13.0 15
DBV-D56G/HR1 50Hz 5.6 19.1 6.3 21.5 23 800 471 32~42 1045x400x330 948x314x239 13.0 15
DBV-D71G/HR1 50Hz 7.1 24.2 8.0 27.3 35 990 583 35~43 1150x400x330 1050x314x242 14.5 17 15.9 9.52
Accessories
Specification
DBV
DBV
DBV
DBV
DBV
DBV
DBV
DBV
Accessories
Specification
DBV
DBV
DBV
DBV
DBV
DBV
Accessories
70Pa ESP, suitable for long distance air supply 30Pa (can be set on site), suitable for low noise
requirement rooms
Specification
Medium Static Ducted
DBV
DBV
DBV
DBV
DBV
DBV
1.
2.
3.
Accessories
Specification
High Static Ducted
Accessories
Notes: 1. When VRF system connect fresh air indoor unit and other type indoor units together, the capacity combination ratio between indoor unit and outdoor unit should
within 100%.
2. Fresh air unit capacity can’t bigger than 30% of total indoor units capacity.
Specification
DBV
DBV
DBV
DBV
DBV
1. 45kW & 56kW units power supply are 380~415V/3PH, others power supply are 220~240V/1PH.
Router Controller
DBV systems
Rs485
Honeywell
Siemens
Johnson controls
Etc...
DBV
How It Work
When air flow formed by exhaust air and outdoor air through the heat exchanged core in cross way, because of
temperature difference in the two sides of flat partition board, the heat transmission is occurred.
In summer, outdoor air acquire cooling from air exhaust to decrease environment temperature; In winter,
outdoor air acquire heating from air exhaust to increase temperature, that is to say, it realizing the energy
recovery during air exhaust process to exchange the heating in heat exchanged core to outdoor air.
Application for : business office buildings, hotels, restaurants, meeting rooms, exhibition centres, leisure
centres, workshop and other places.
Specification
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
DB
Thailand Vietnam
48/39 Soi Praditmanutham 19 10th Floor, Nam A Bank Tower,
Praditmanutham Road, 201-203 Cach Mang Thang 8 Street,
Lat Pharo, Bangkok 10230 District 3, Ho Chi Minh City,
Thailand Vietnam
info@dunham-bush.com
www.dunham-bush.com
R
The manufacturer reserves the right to change specifications without prior notice. M-S-0336C-1021
©Dunham-Bush. All rights reserved.