NMISA_BLD4_LAB_AHU

CONTROL PHYLOSOPHY
CONTROLLER:- LP-FX15D61-000C
RETURN AIR TEMPRATURE:- TS-9101 8222
SUPPLY AIR TEMPRATURE:- TS-9101 8222
SPACE TEMP. SENSOR:- RS-1180-0002
TEMP. SETPOINT MODULE:- RS-1180-0002
OPERATIONAL SETPOINT:- Setpoint_1
CONTROLLER SETPOINT:- Setpoint
TEMP. SETPOINT MODULE:- Setpoint_fr_Rm

Setpoint selection is carried out through PARAMETER menu in the FX15 controller with
item Stp_select command (0 or 1). If 0 is selected Setpoint_1 = Setpoint
If 1 is selected Setpoint_1 = Setpoint_fr_Rm

The setpoint is being compare to the return air temperature for the control system decision
on cooling or heating.

.   1.         (T ) FOR HEATING SETPOINT WITH 1 OFFSET.

2.      (T ) FOR COOLING SETPOINT WITH OFFSET 0.5.

3.      T = RETURN AIR TEMPERATURE

4. SP = Setpoint_1

5. The above offset can be adjusted in the PARAMETER menu of the controller

Safety operations

Fire signal is always active in the controller as an indication of no fire occurrence and when it goes off the
machine will be automatically and immediately switch off.

Flow switch always need to be actively on in the controller whenever the fan is running for cooling valve,
heaters and humidifier to be operational.

Overheat start is always active in the controller as an indication of heaters availability