Professional Documents
Culture Documents
MY Cable
MY Cable
1. Application
2. Service characteristics
The permitted temperature to work is 65 degree. Its smallest bending radius is six times the size of cable diameter. The yellow
sheath cable can’t exposure in the sunshine for long time.
Table 1
Type Designation Usage
MY-0.38/0.66 Rubber sheath cable movable used Rated voltage 0.38/0.66KV for various coal-mining equipments to
in the mine connect power supply in the mines
4. Cable structure
MY 0.38/0.66 kV 3×50+1×16
5.MY 0.38/0.66 Specifications Size (table 2)
Table 2
Core ×nominal cross-sectional area Power core Nominal sheath Cable outer dia. (mm)
mm2 insulation nominal thickness(mm) MY-0.38/0.66
Power core Ground core thickness (mm) Min Max
7. Technical property
1) Power core insulation resistance:
Table 3
Power core nominal section(mm) 20 degree Insulation resistance min value≥(MΩ.km)
4 750
6 650
10 550
16 450
25 400
35 350
50 300
70 250
95 250
120 250
150 200
185 200
240 150
300 150
400 150
2) Outer sheath rubber tensile strength should not be less than 5.0N/mm2