DESIGN NUMBER: XA1244

Customer BAKKER Project Jumbo 1


Customer spec. 1.126787 Customer ref. Bow Thruster Transformer

THREE PHASE TRANSFORMER TYPE:


1900 KVA
440 ± 2x4% / 721.3V – 721.5V – 60Hz
Vector Group: Dd11.75d0.75
Enclosure: IP44
Painting: RAL7035
Cooling: AF / WF
Impedance: 8%
Earthed screen between primary and secondary
Third party certification: LRS
Ambient temperature: 50 °C
Weight: 5.000 kg ca.

AIR WATER COOLER DATASHEET:


Water flow m3/h 8.73
Water inlet / water outlet °C / °C 38 / 43
Water pressure drop Kpa 74
Rated water pressure Bar 6
Test water pressure Bar 9
Motor (voltage/frequency/power) V / Hz / Kw 440 / 60 / 0.9

O/A Reference No. of revision


No. Drawing. Sh. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
2-26439 1 X X
2-26439 2 X X
2-26439 3 X
2-26439 4 X X

Wiring diagram Reference No. of revision


No. Drawing Sh. 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
SE-02618 1 to 8 X

SG-02750 1 X

3
2
1 Revised: 2-26439 sh. 1-2-4 09.10.12 TMNR.
0 Issue 06.08.12 THMV
Rev. Description Date Drawn Checked

All right for transmission reserved Denomination


Sheet No. 1/4
TRASFOR SA TNT 8FS 1M9/N
No. Drawing
Lugano Switzerland 2-26439