Subdivision Storm Sewers Sample Annotated
Subdivision Storm Sewers Sample Annotated
SILVERADO GLEN RD SE
GENERAL NOTES (GN):
1. ALL PIPE SIZES ARE IN MILLIMETRES AND ALL DIMENSIONS ARE IN METRES UNLESS
OTHERWISE NOTED.
PHASE 1 OFFSITE TO 2. ALL COORDINATES AND DISTANCES ARE BASED ON 3TM COORDINATE SYSTEM
BE SUBMITTED UNDER (NAD 83).
SEPARATE COVER
BLOCK 11 BLOCK 11 3. ALL CONSTRUCTION AND MATERIALS TO BE IN ACCORDANCE WITH CURRENT CITY
OF CALGARY SPECIFICATIONS.
7510858 PLAN 7510858 PLAN 4. NO CONSTRUCTION SHALL PROCEED UNTIL ALL APPROPRIATE REGULATORY
SILVERTON WY SE
APPROVALS ARE OBTAINED.
SILVERTON BV SE
5. ALL PLANS SUBJECT TO TERMS OF THE DEVELOPMENT AGREEMENT/PERMIT AND
RIM=1058.225 REMOVE CAP
135 AND TIE TO EX
THE CONTRACT DOCUMENTS.
(190 AV SE)
6. ANY ERRORS OR DISCREPANCIES TO BE REPORTED TO THE ENGINEER PRIOR TO
6.00
7.00 PAVED LANE 12.30
l
7. ALL FILL MATERIAL SHALL BE PLACED AND COMPACTED TO CITY OF CALGARY
SPECIFICATIONS.
1048.894
7510507 PLAN 5
l
D 8. ALL ELEVATIONS ARE GEODETIC.
BLOCK 12
136
130
C-301 PROP SD 150 PVC WTD
9. CONTRACTOR TO BE RESPONSIBLE FOR LOCATION AND ALIGNMENT OF ALL
EXISTING UTILITIES.
L=47.50 S=0.80%
l
MTEXT:
134
129
W INV 1054.582
1 2 7 8 BLOCK 18 13 14 17 BLOCK 20 7.75
E INV 1054.126
STYLE: Proposed 1.8 Anno 11. CONTRACTOR TO COORDINATE ALL CONSTRUCTION WITH ASSOCIATED OWNER(S)
WHEN WORKING NEAR EXISTING INFRASTRUCTURE.
PROP SD LAYER: C-STRM-TEXT
BLOCK 7 INSTALL CAP
E
CURVE DATA 12. EXISTING SURFACE FEATURES TO BE REINSTATED TO CONDITIONS PRECEDING
2 'C' CB
43.44 R=4000.00 18 CONSTRUCTION WHERE EXISTING CONDITIONS WILL BE MAINTAINED.
7510858 PLAN 'C' CB 'K2' CB ICD R30
123
l
124 124 13. COMBINED FACTOR APPLIED=0.999736 (1.000264).
11.00
Δ=0°17'37"
ICD R30 l NO ICD
Lc=20.50 1 125 c/w EXTRA
0.30 BARREL
PIPE: 14. ALL NORTHING-EASTING COORDINATES ARE AT SEA LEVEL.
FUT STORM
10 49.274
l l
l
l l l l l l l
TEMP TYPE C 'K2' CB SD-32 'K2' CB SD-15 'C' CB
'K2' CB
l l
(Plan Profile Section) STORM SEWER NOTES (STSN):
13.00
13.00
13.00
'K2' CB
13.00
13.00
SD-17A
13.00
ICD R30
13.00
TEMP GTMH RIM=1057.330 ICD R30 RIM=1057.930 NO ICD RIM=1057.070 1. ALL PVC STORM SEWERS TO BE DR35 UNLESS OTHERWISE NOTED.
NO ICD
L
FUT RIM=1058.050 RIM=1057.680 c/w EXTRA 30 NO ICD
0
INSTALL CAP 2. ALL CIRCULAR CONCRETE PIPES TO BE CLASS IV UNLESS OTHERWISE NOTED.
30
1050.410 0
0.45 BARREL 1049.374 L
l
1051.750 PROP SD 1500 CONC 1051.565 1051.465 PROP SD 1500 CONC 1051.145 1051.045 1050.756 1050.656 1050.310 PROP SD 1500 CONC 1052.253 PROP SD 450 CONC 1053.523 1053.623 1054.112 FUT SD 3 3. ALL CATCH BASIN LEADS ARE TO BE 250 DIAMETER UNLESS OTHERWISE NOTED.
30 7
L=6 4.63 S 5 P VC
L=92.18 S=0.20% L=106.59 S=0.30% PROP SD 1500 CONC PROP SD 1500 CONC L=143.95 S=0.65% L=94.10 S=1.35% 4. ALL PIPE BACKFILL SHALL SATISFY A MINIMUM TYPE 2 INSTALLATION
0L PROP SD 375 PVC
l
SD-11 =1.00%
1051.510 00L
1050.474
l
L=52.67 S=0.55% L=44.79 S=0.55% L=48.94 S=1.00% SPECIFICATION WITH CLASS 1A BEDDING.
30
SILVERTON ST SE SD-17
SILVERTON ST SE RIM=1056.670
1051.870
SILVERTON ST SE 5. CONTRACTOR TO TAKE CARE IN THE PLACEMENT OF MINIMUM AND NEAR MINIMUM
0L
'K2' CB SD-12
RIM=1057.721 'K2' CB
8.25 ICD R30 RIM=1058.090 SLOPE SEWERS.
l
C-301
ICD R30 E -4634.11 16 17 ICD R70 TYPE 'K2' ICD R30 7. EXACT LOCATION OF ALL EXISTING INFRASTRUCTURE (HORIZONTAL AND
L
ICD R50 8 9 NO ICD ICD R70 61 SEPARATE COVER
B
STRUCTURE: c/w EXTRA c/w EXTRA VERTICAL) TO BE CONFIRMED IN THE FIELD BEFORE CONSTRUCTION BEGINS.
PR STORM CB (Plan Profile Section) c/w EXTRA 8. ALL EXISTING STORM SEWERS ARE OPERATIONAL AND MUST BE MAINTAINED AS
18 0.30 BARREL
L=93.52 S=2.05%
15 0.45 BARREL 60
SILVERTON HE SE
l
SILVERTON HE SE
10 SUCH DURING CONSTRUCTION OR SUITABLE ALTERNATE DRAINAGE CONDITIONS
L=93.51 S=4.65%
PROVIDED.
137
DEVELOPMENT AND INCLUDED IN SEPARATE DRAWING SUBMISSION SETS.
l
129
138
127
STRUCTURE LABEL: 11. TWO PIECE CATCH BASIN SIDE INLET TYPE 'C' AS PER CITY OF CALGARY STANDARD
l
MTEXT:
131
FUT SD 600 CONC
23
STYLE: Proposed 3.5 Anno A 10 BLOCK 12
BLOCK 7 LAYER: C-ROAD-TEXT-F C-301 7.75
133
E
P
24 15 54 7410507 PLAN
7510858 PLAN 9 C-301
BLOCK 15 2
105 3.4 27
l
105 4.8 2 2
L=153.25 S=2.54%
BLOCK:
BLOCK 16 1 'C' CB 128 16 'C' CB 53
NO ICD NO ICD
122
GNRL Ref Sect Indicators For Bldg With Break Std (Anno) PROP SD
LAYER: G-ANNO-SECT-MARK CURVE DATA PROP SD
l
R=50.00 1053.718 1055.12 2 CURVE DATA
PROP SD 150 PVC WTD
Δ=16°02'15" R=50.00 STRUCTURE:
BLOCK: SD-16 L=140.42 S=1.00% SD-14
7.75
7.75
Lc=14.00 30 Δ=16°02'03" PR STORM NULL STRUCTURE (Plan Profile Section)
RIM=1059.613 0L 300L
GNRL Ref Grid Indicator - Num (Anno)
LAYER: G-GRID-LOCL-MARK
DIMENSION: N 5638199.82
SILVERTON HE SE RIM=1059.764 Lc=13.99
STYLE: Existing 1.5 Anno E -4727.89 N 5638059.80
PROP SD 'K2' CB 'K2' CB
l
l
PIPE LABEL: Δ=16°00'30"
FILE: Z:\SPECIAL\TI_CONTRACT_SEED_DIRECTORIES\CONSTRUCTION DRAFTING STANDARDS AND TEMPLATES\DEVL\SMPL-EXP~\2PRODUCT\12345678C-105.DWG | DATE: Friday, November 20, 2020 10:43:04 AM
*** PR STORM Plan Invert (End) *** EX STORM Plan Invert (Start)
30 35 36 BLOCK 16 41 42 47 48
Lc=13.97
9.41 2
132 NAD 83
1055.763
STRUCTURE LABEL:
M
11.18 COORDINATES
*** PR STORM Plan (Structure Name)
126 'K2' CB
'K2' CB 1
l
NO ICD
NO ICD l l l l 7.00 PAVED LANE
l l l l l
1.95
9.95
9.95
RIM=1060.081 SD-35B STYLE: Proposed 2.0 Anno STYLE: Proposed 3.5 Anno
'C' CB
SILVERTON RD SE
l
c/w EXTRA
4.89
A
l
9712011 PLAN
l
STRUCTURE: DATE
NO. DESCRIPTION (YYYY-MM-DD)
BY APPD
EX STORM 2.4 S-1 MH (Plan Profile Section) PROP SD 675 CONC
L=82.63 S=3.22% PERMIT SEAL
PIPE LABEL:
W INV 1058.520
*** EX STORM Plan Invert (End) 9.41 E INV 1055.860 PIPE LABEL:
*** PR STORM Plan
121
STRUCTURE:
l
l
- PROPOSED / FUTURE LABEL TEXT SIZE = 1.8 mm
S
- EXISTING LABEL TEXT SIZE = 1.5 mm
LEGEND: BY
DATE
(YYYY-MM-DD)
C-105 007
DATE
BY (YYYY-MM-DD)
PROFILE NO.
DRAWN
THIS DRAWING SAMPLE IS INTENDED TO ILLUSTRATE THE NEW CAD STANDARDS AND ARE FOR REFERENCE PURPOSES ONLY. PLEASE CONFIRM WITH YOUR APPROPRIATE CITY OF CALGARY CONTACT FOR SPECIFIC CONTENT REQUIREMENTS. ISC: SHEET SIZE ANSI D 25 mm 0