Professional Documents
Culture Documents
Cheetah Error Messages
Cheetah Error Messages
30
LATCHING EVENTS
ALARM PRESENT Alarm state for this zone Find active device and determine cause for
activated alarm.
Device has reached the Alarm Find active device and determine cause for
ALARM ACTIVE ---- threshold. Analog Datat alarm.
appended to this message.
Sensor is contaminated. Locate the detector by using the address on
CONTAMINATED DEVICE the custom message on the 2nd line and the
address on the 4th line of the display.
Determine cause for elevated obscuration
Intelligently interfaced VESDA Locate the detector by using the address on
detector has reached the FIRE 1 the custom message on the 2nd line and the
FIRE 1 X.XXX%/Y.YYY% level (3RD). The FIRE 1 address on the 4th line of the display.
threshold is xxx. The current Determine cause for elevated obscuration
obscuration is yyy.
Intelligently interfaced VESDA Locate the Scanner detector by using the
Scanner detector pipe 1 has address on the custom message on the 2nd
FIRE-1 SECT-n X.XXX% reached the Fire 1 Level. line and the address on the 4th line of the
display. Determine cause for elevated
obscuration
Intelligently interfaced VESDA Locate the detector by using the address on
detector has reached the FIRE 2 the custom message on the 2nd line and the
FIRE 2 X.XXX%/Y.YYY% level (4TH). The FIRE 2 address on the 4th line of the display.
threshold is xxx. The current Determine cause for elevated obscuration
obscuration is yyy.
NON-LATCHING EVENTS
ABORT PRESENT Abort input active in zone. Locate the active abort using the previous
events.
ABORT RESTORED Abort input restored to normal in None.
zone.
ABORT PRESSED Addressable input device Locate the device and determine cause for
programmed for Abort is active. activation.
ABORT RELEASED Abort input restored to normal None.
(device).
AC power input on main Measure input AC voltage. Measurement
controller is below 85% of should be 120VAC or 240VAC. If it is normal,
AC1 POWER TROUBLE normal. check the Secondary of the transformer (input
at controller). It should be 24VAC. Check the
AC fuse, F1.
AC power input on main None.
AC1 POWER RESTORED controller restored to 90% of
normal.
AUD SWITCH DISABLED Audible Disable Switch is in the Locate Audible Switch and return to normal
Disable position. SW1.
AUD SWITCH RESTORED Audible Disable Switch is in the None.
Normal position (restored).
AUX POWER MISSING SPS configured but not installed.
Install SPS or remove from SPS from System
Configuration.
AUX POWER UNCONFIG Aux Power Module detected, but Configure Aux. Power module if being used.
not configured.
AUX POWER CORRECTED SPS configured and installed. None.
Auxiliary Power Input on main Measure Aux Power input (P2 Batt). This
AUX1 POWER TROUBLE board below 20.4VDC. should be 24VDC. If below 20.4VDC check
for cause. Check Battery fuse F2 on main
board.
AUX1 POWER RESTORED Auxiliary Power Input restored None.
above 20.4VDC.
SPS Auxiliary Power Input below Measure Aux Power input (P2 Batt). This
AUX2 POWER TROUBLE 20.4VDC. should be 24VDC. If below 20.4VDC check
for cause. Check Battery fuse F2 on SPS
board.
AUX2 POWER RESTORED SPS Auxiliary Power Input None.
restored above 20.4VDC
Addressable device trouble. Bring device back to panel and remove field
Communication device has errors wiring. If no troubles, check field wiring for
BAD COMMUNICATION (parity, checksum, etc.). induced voltage. If still troubles, replace
device.
Addressable device bad None.
COMMUN RESTORED communication trouble restored
to normal.
Battery Charger on Main panel Measure Battery Charger Output at Battery
has low voltage output. Terminal. Batteries must be connected to
BAT1 CHARGE VOLT LOW obtain valid reading or replace with 1500uF,
50V capacitor. Check Battery Fuse. Factory
adjusts charging voltage output to 27.6VDC.
BAT1 CHARGE Battery Charger on main panel None.
RESTORED returned to normal.
SPS Battery Charger has low Measure Battery Charger Output at SPS
voltage output. Battery Terminal. Batteries must be
BAT2 CHARGE VOLT LOW connected to obtain valid reading or replace
with 1500uF, 50V capacitor. Check Battery
Fuse. Factory adjusts charging voltage
output to 27.6VDC.
SPS Battery Charger returned to None.
BAT2 CHARGE normal
RESTORED
Battery on main panel is low or Measure the Battery input at the control
missing. panel. It should be 24-27.6VDC with
batteries. Measurement without batteries
should not be trusted. Install 1500uF, 50V
BATTERY1 TROUBLE capacitor to measure the charging circuit
voltage. It should be 27.6VDC. Measure
each cell of battery to check for defective
battery. They should measure 12 VDC each.
Check Battery Fuse, F2.
BATTERY1 RESTORED Battery on main panel restored to None.
normal.
SPS Battery is low or missing. Measure the Battery input at the control
panel. It should be 24-27.6VDC with
batteries. Measurement without batteries
should not be trusted. Install 1500uF, 50V
BATTERY2 TROUBLE capacitor to measure the charging circuit
voltage. It should be 27.6VDC. Measure
each cell of battery to check for defective
battery. They should measure 12 VDC each.
Check SPS Battery Fuse, F2.
BATTERY2 RESTORED SPS Battery restored to normal. None.
Fault detected in the calibration Manually calibrate the device using the CAL
CALIBRATION FAULT of the addressable device. SENS menu. Replace the device if unable to
resolve problem.
CALIBRATION RESTORED Calibration fault restored to None.
normal.
Configuration error #1. No Program Manual Release in this zone.
CFG ERROR 1: MR----- Manual Release in this zone. Change Zone Config to Alarm Zone or set
Manual Release Y/N to N (No).
CFG RESTO 1: MR---- Configuration error #1 restored. None.
Configuration error #2. No output Determine input. Add output or move input to
CONFIG ERROR 2: IN/O available to input. different zone where output exists. Cheetah
Tracker Configure View Zone I/O may aid in
viewing input and output relationships.
CONFIG RESTO 2: IN/O Configuration error #2 restored. None.
Configuration error #3. Alarm Change to Alarm Zone or remove Alarm
CONFIG ERROR 3: AL V Verification is programmed on a Verification programming from addressable
device in a suppression zone. sensor.
CONFIG RESTO 3: AL V Configuration error #3 restored. None.
Configuration error #4. Analog Change configuration for addressable device.
CONFIG ERROR 4:SENS photo has too high alarm Lower the alarm sensitivity.
sensitivity.
CONFIG RESTO 4:SENS Configuration error #4 restored. None.
CFG ERROR 5: W------ Configuration error #5. Configure SRM in the Watermist Zone or
Watermist Zone needs an SRM. change the zone config to alarm zone.
CFG RESTO 5: W------ Configuration error #5 restored. None.
Configuration error #6. Remove abort from watermist zone (or
CFG ERROR 6: W----- Watermist Zone has an abort (not change zones).
allowed).
CFG RESTO 6: W------ Configuration error #6 restored. None.
Configuration error #7. SRM Configure ON-Time for SRM or remove
CFG ERROR 7:ON TIME assigned to Watermist and Zone Watermist Zone from Config.
has no on-time.
CFG RESTO 7:ON TIME Configuration error #7 restored. None.
Configuration error #8. SRM SRM is configured for Watermist and Zone is
CFG ERROR 8:ZN-TYPE assigned to Watermist and Alarm set for Alarm. Change Zone type to
type of zone. Watermist or change SRM configuration.
CFG RESTO 8:ZN-TYPE Configuration error #8 restored. None.
Configuration error #9. Manual Change Zone configuration to Suppression
CFG ERROR 9: MR---- Release is in an Alarm Zone only. Zone or change the zone of the Manual
Release. Change input module to selection
other than Manual Release.
Configuration error #9 restored. None.
CFG RESTO 9: MR----
RAM has garbled information for Re-send device, zone, system, etc.
CHECKSUM ERROR ----- device, zone, system, etc. in configuration to over-write the current
configuration. configuration. May require Fike assitance.
CHECKSUM OK ----- Fixed Checksum error. None.
Configuration in addressable Perform TO DEV in Configuration menu or re-
device does not match send device configuration. Device was not
CONFIGURE FAULT configuration stored in the control powered properly on first download of
panel. configuration. If device is now functioning, it
needs its configuration.
Configuration in addressable None.
CONFIGURE RESTORED device matches configuration
stored in the control panel.
DRILL INPUT ACTIVE Drill switch is active (addressable Locate addressable device or panel and
or panel). determine cause for activation.
DRILL INPUT RESTORED Drill switch is returned to normal. None.
DRILL PRESENT The zone has an active drill Locate the active drill switch using the event
switch. history.
DRILL RESTORED The zone drill switch is restored None.
to normal.
Addressable Device was polled Locate addressable device and check to see
and no device responded. if loop power (38VDC) and 24V power (if
necessary) are present at device. Check
DEVICE MISSING device address with programmer. If all are
good, check wiring for polarity swap. Move
device to directly at control panel to test
individual unit.
DEVICE PRESENT Addressable Device restored None.
from missing poll.
DISABLED ZONE ---- Zone Disabled, either from Zone Determine source of Disable and determine
Disable or Enable/Disable menu. cause. Enable if desired.
ENABLED ZONE ---- Zone is Enabled from previous None.
disable.
Board Level Output Circuit Enable circuit in the Enable/Disable menu.
DISABLED CKT ---- Disabled. Circuit number
appended to the event.
ENABLED CKT ----- Output Circuit Enable from None.
previous disable.
Addressable Device is disabled, Use the Enable/Disable menu to check the
DISABLED DEVICE either from Enable/Disable menu status of the device. Determine cause of
or in addressable Device disable. Enable if desired.
Configuration.
ENABLED DEVICE Addressable Device is returned None.
to enabled.
DISABLED LOOP 1 Loop was disabled in the Enable the Loop in the Enable/Disable menu.
configuration
ENABLED LOOP 1 Loop was enabled in the None.
configuration.
DISABLED LOOP 2 Loop was disabled in the Enable the Loop in the Enable/Disable menu.
configuration
ENABLED LOOP 2 Loop was enabled in the None.
configuration.
DISABLED LOOP 3 Loop was disabled in the Enable the Loop in the Enable/Disable menu.
configuration
ENABLED LOOP 3 Loop was enabled in the config. None.
DISABLED LOOP 4 Loop was disabled in the Enable the Loop in the Enable/Disable menu.
configuration
ENABLED LOOP 4 Loop was enabled in the None.
configuration.
Ground Fault Detection has been Enable Ground Fault. Requires Fike
GRND FAULT DISABLED Disabled. Requires Factory assistance.
Password to Disable.
GRND FAULT ENABLED Fault Clear. None.
Ground Fault located on system. Remove GCA if unknown where fault exists
(disable releasing devices). Use diagnostics,
ground fault menu to aid in locating circuit
where ground fault exists. Remove terminals
GND FLT PRESENT one at a time while watching the counter and
looking for a decrease in the number (from
255). Once the circuit is found, remove
sections of the wiring using the same
diagnostics.
GND FLT RESTORED Ground Fault removed. None.
Addressable Device Trouble from Locate addressable device and monitor.
INTERNAL FAULT the 0x08 polling command. Move device to see if the environment is
causing malfunction.
INT FAULT RESTORED Internal Fault from addressable None.
device returned to normal.
Abort Switch is pressed in a zone Locate addressable device and determine
INVALID ABORT ACTIVE that does not have a current cause for Abort switch being pressed.
Alarm event.
INV ABORT RESTORED Abort Switch returned to normal. None.
INVALID VESDA FAULT Fault Code 201 from VESDA Call Fike for Assistance.
INVALID FAULT CLEAR Fault Clear. None.
VESDA unit configured but no Check the Cheetah configuration and make
similar zone found present on thesure that the VESDA programmed has a
INVALID VESDA ZONE VESDAnet. UNIT # that matches the VESDA detector
ZONE. Check the VESDAnet and make sure
that the VESDA zone matches (01-50).
INVALID V-ZONE CLEAR Fault Clear. None.
Intelligently interfaced VESDA Determine where ISOLATE was performed
ISOLATE ACTIVE detector has been (Display or software). Press ISOLATE again
isolated/disabled. to re-enable.
ISOLATE RESTORE Older Firmware None.
Loops 3 and 4 are configured but Power down unit and attach loop module.
LOOP MODULE MISSING panel does not recognize a SLM Remove loops 3 & 4 from the configuration.
attached.
LOOP MODULE Loop Module is found. None.
RESTORED
Class A wiring on Loop 1 has Locate wiring fault open circuit. Change to
L1 OPEN CLASS A open circuit trouble. class B wiring and determine where devices
are missing to locate open in wiring to
devices.
L1 CLASS A RESTORED Class A wiring open fault is None.
cleared to normal.
Class A wiring on Loop 2 has Locate wiring fault open circuit. Change to
L2 OPEN CLASS A open circuit trouble. class B wiring and determine where devices
are missing to locate open in wiring to
devices.
L2 CLASS A RESTORED Class A wiring open fault is None.
cleared to normal.
Class A wiring on Loop 3 has Locate wiring fault open circuit. Change to
L3 OPEN CLASS A open circuit trouble. class B wiring and determine where devices
are missing to locate open in wiring to
devices.
L3 CLASS A RESTORED Class A wiring open fault is None.
cleared to normal.
Class A wiring on Loop 4 has Locate wiring fault open circuit. Change to
L4 OPEN CLASS A open circuit trouble. class B wiring and determine where devices
are missing to locate open in wiring to
devices.
L4 CLASS A RESTORED Class A wiring open fault is None.
cleared to normal.
Addressable Address was polled Use ADR LOC diagnostics to locate devices
MULTIPLE DEVICES and response seen from multiple (turn ON LEDs). Remove sections of the loop
devices. to determine unknown location of other
multiple device.
RESTORED MULTIPLE Multiple Devices trouble restored None.
to normal.
Member Cheetah determines the Locate Manager Cheetah and check network
NET MANAGER MISSING MNGR. is missing from Network. wiring.
NET MANAGER RETURN Cheetah Manager has returned None.
to network.
NET MEMBER#a MISSING Network member Cheetah #a is Locate the member Cheetah and determine if
missing. Network wiring is connected.
NET MEMBER#a RETURN Network member Cheetah #a has None.
returned to network.
NETWORK ACT: ------- Network event message: zone- Locate originating Cheetah and determine
state has activated. source for event.
NETWORK CLR: ------- Clear of activation. None.
NETWORK DRILL PRESNT Drill State activated from network Determine which Cheetah has Drill Switch
- All zone only. pressed. Determine who pressed switch.
NETWORK DRILL RESTOR Drill Switch pressed again to None.
restore to normal.
Trouble Detected on the Network Make sure the Network card is fully seated in
NETWORK MODULE Card. P42 connector. Examine network card for
TROUBL foreign material or cause for fault. Replace
module if nothing is determined.
NETWORK MODULE Fault Clear. None.
CLEAR
Addressable sensor, input, or Locate device and determine cause for
PALARM1 ACTIVE ---- VESDA is above the PreAlarm 1 elevated obscuration or activation.
threshold. --- will show analog
data.
PALARM1 RESTORE ---- Device obscuration has returned None.
below the PreAlarm 1 threshold.
PRE-ALARM1 PRESENT This zone has an active PreAlarm Locate the source of the PreAlarm 1 using
1 state. previous events.
The PreAlarm 1 level has cleared None.
PRE-ALARM1 RESTORED in the zone.