Professional Documents
Culture Documents
VALVULAS Piloto Solenoide EVM DANFOSS
VALVULAS Piloto Solenoide EVM DANFOSS
REFRIGERATION AND
AIR CONDITIONING Technical leaflet
Technical leaflet Pilot valves for servo operated main valves
Contents Page
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Constant-pressure pilot valve, type CVP (LP) and CVP (HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
Differential-pressure pilot valve, type CVPP (LP) and CVPP (HP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
High pressure pilot valve, type CVP (XP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Pressure-operated pilot valve with reference pressure connection, type CVC . . . . . . . . . . . . . . . . . . . . . . . . .9
Temperature-operated pilot valve (pressure-independent), type CVT/CVTO . . . . . . . . . . . . . . . . . . . . . . . . 11
Electronically operated constant-pressure pilot valve, type CVQ (pressure-dependent). . . . . . . . . . . . . . 13
Motor-operated constant-pressure pilot valve, type CVPM (pressure-dependent) . . . . . . . . . . . . . . . . . . . 15
Pilot valve for motor-operated constant-pressure pilot valve, type CVP(M) . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Solenoid pilot valve, type EVM (NC) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Solenoid pilot valve, type EVM (NO) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Housing for pilot valves, type CVH, for mounting in external pilot lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Introduction
Features Applicable to all common non flammable All pilot valves can be used on all sizes of main
refrigerants including R 717 and non corrosive valves.
gases/liquids dependent on sealing material Extremely accurate pressure and temperature
compatability. control.
The pilot valves can be screwed direct into Several pilot valves can be connected in series
the main valve, thus avoiding the necessity of or in parallel to provide many functions in the
welding, soldering and separate pilot lines. same ICS or PM main valve.
The pilot valves can be mounted direct in a
ICS or PM main valve or be connected via an
external pilot line and a CVH housing.
Design Each pilot valve is designed to give the optimum Mounted in a CVH housing, the pilot valves can
control accuracy within the specific function be used in external lines, either as independently
range of the valve. operating valves or as external control valves for
the main valve.
Several pilot valves can be mounted in series
and/or in parallel on a ICS or PM main valve to The pilot valves can be used for all sizes of ICS or
give a very large number of functions. PM main valves.
Low-pressure version
CVP (LP) 247 psi g 0.46 US gal/min –58 to 248°F 0 psi g to 102 psi g 027B1100
CVP (LP) 247 psi g 0.46 US gal/min –58 to 248°F 19.5 in. Hg to 29 psi g 027B1101
High-pressure version
CVP (HP) 406 psi g 0.46 US gal/min –58 to 248°F 58 psi g to 319 psi g 027B1160
CVP (HP) 406 psi g 0.46 US gal/min –58 to 248°F 58 psi g to 406 psi g 027B1161
CVP (HP) 406 psi g 0.46 US gal/min –58 to 248°F 19.5 in. Hg to 102 psi g 027B1164
P-band for a valve system regulated by CVP and ICS or PM main valve: < 0.2 bar g (2.9 psi g)
Low-pressure version
mm 122 98 53 0.4 kg
CVP (LP) 32 M 24 × 1.5
in. 4.80 3.86 2.09 0.88 lb.
High-pressure version
mm 170 146 90 1.7 kg
CVP (HP) 32 M 24 × 1.5
in. 6.69 5.75 3.54 3.75 lb.
Weights are approximate values only
(continued)
Low-pressure version
CVPP (LP) 247 psi g 0.46 USgal/min –58 to 248°F ∆p = 0 to 102 psi g 027B1102
High-pressure version
CVPP (HP) 406 psi g 0.46 USgal/min –58 to 248°F ∆p = 0 to 102 psi g 027B1162
CVPP (HP) 406 psi g 0.46 USgal/min –58 to 248°F ∆p = 58 to 319 psi g 027B1168
P-band for a valve system regulated by CVPP and ICS or PM main valve: <0.2 bar g (2.9 psi g).
Low-pressure version
mm 136 112 53 26 53 0.5 kg
CVPP (LP) 32 M 24 × 1.5
in. 5.35 4.41 2.09 1.02 2.09 1.1 lb.
High-pressure version
mm 170 146 90 6 1.7 kg
CVPP (HP) 32 M 24 × 1.5
in. 6.69 5.75 3.54 0.24 3.7 lb.
(continued)
High-pressure version
CVP (XP) 754 psi g 0.52 USgal/min –58 to 248°F 363 psi g to 754 psi g 027B0080
P-band for a valve system regulated by CVP and ICS or PM main valve: < 1.6 bar g (23.2 psi g)
CVP (XP)
CVC
Low-pressure version
mm 110 129 153 43 33 53 M 24 0.7 kg
CVC 32 G 1/4 19
in 4.33 5.08 6.02 1.69 1.30 2.09 × 1.5 1.5 lb.
P-band for a valve system regulated by CVT/CVTO and ICS or PM: <5°C (41°F)
CVT/CVTO
CVT/CVTO
CVQ 246 psi g 0.52 USgal/min –29.5 in. Hg to 72.5 psi g 027B1139
CVQ 246 psi g 0.52 USgal/min 0 psi g to 87 psi g 027B1140
CVQ 246 psi g 0.52 USgal/min 24.7 psi g to 116 psi g 027B1141
The P-band for a valve system regulated by CVQ and ICS or PM depends on the control parameters of
the EKC 361 or EKC 366.
Electrical data
Supply voltage 24V a.c. ±10%
Frequency 50 to 60 Hz
Power consumption, operation 50 VA
start 75 VA
Enclosure NEMA 3 / IP 55
Cable entry Pg 13.5
Ambient temperature, operation –30 to 50°C (–22 to 122°F)
transport –50 to 70°C (–58 to 158°F)
EMC-Directive 89/336/EEC, EMC-Directiv 89/336/
-marking EN 50081-1 and EN 50082-1
CVQ
(continued)
CVQ
CVPM CVP(M)
P-band for a valve system regulated by CVP(M) and ICS or PM: < 0.2 bar g (2.9 psi g)
(continued)
CVPM CVP(M)
CVP(M)
Normally closed
EVM (NC) 508 psi g 0.43 USgal/min MOPD: 305 psi g 027B1120
Normally open
EVM (NO) 508 psi g 0.14 USgal/min MCPD: 305 psi g 027B1130
EVM
mm 107 83 82 72 0.5 kg
EVM 32 M 24 × 1.5
in. 4.21 3.27 3.23 2.83 1.1 lb.
EVM
Housing for pilot valves, type CVH, for mounting in external pilot lines