FM Installation Drawing 960411-1006 C: Display FHX40
FM Installation Drawing 960411-1006 C: Display FHX40
FM Installation Drawing 960411-1006 C: Display FHX40
CCS/FM 9.0
FM/C 05.04.12
Class I, Div. 1, Groups A, B, C, D
Class I, Zone 0 or Zone 1, IIC
Class I, Div. 2, Groups A, B, C, D Display FHX40 for connection to FM approved Endress+Hauser instruments
Class I, Zone 2, IIC with an intrinsically safe (IS) display output circuit
XA01085F-C/00/EN/01.12
71206322
T* (see table)
Type 4X, IP66 Notes: INTRINSICALLY SAFE CLASS I, DIV. 1, GROUPS A, B, C, D or AEx ia IIC
HAZARDOUS LOCATION INSTALLATION
1. Control room equipment may not use or generate over 250 Vrms.
Display FHX40 connected to Endress+Hauser
level, pressure or flow transmitter 2. Installation should be in accordance with ANSI/ISA 12.06.01
with an intrinsically safe display output circuit “Installation of intrinsically safe systems for hazardous (classified)
FM approved associated
intrinsically safe apparatus locations” and the National Electrical Code (ANSI/NFPA 70).
FHX40
Display
4. Display FHX40 entity parameters with 30 m cable are:
Display FHX40 Vmax = 5.6 V
Imax = 47 mA
Pi = 66 mW
Ci = 11 mF
Ground stud
Li = 30 mH
960411-1006 C
Display FHX40 with cable can be connected to FM approved
Endress+Hauser apparatus with intrinsically safe display output circuits
Straight cable connectors which meet the following requirements:
molded-on cable Voc or Vt or Uo £ Vmax
Isc or It or Io £ Imax
Endress+Hauser
Po £ Pi
FM Installation Drawing
level, pressure or
flow transmitter Ca ³ Ci
La ³ Li
Local potential equalization
5. Permissible cable length between transmitter and display FHX40 is 40 m.