(1) High torque 200%/0.5Hz is realized by Advanced magnetic flux vector control (3.7K or less) (1) Improved setting dial
• Standard 7
By the advancement of General-purpose magnetic flux vector control to Advanced magnetic flux vector control, top level of driving Setting dial is the feature of Mitsubishi inverters. Specifications
performance became possible. •Displayed numbers can be jumped by turning the setting dial quickly, and numbers
Since V/F control and General-purpose magnetic flux vector control operations are available, operation after replacement of the can be changed one by one by turning it slowly, enabling speedy parameter setting.
conventional model (FR-E500 series) is ensured. • The nonslip setting dial is easier to turn. • Outline
Dimension 10
For the 5.5K to 15K, 150%/0.5Hz torque is realized. (2) Easy setting mode Drawings
Speed/torque characteristics example Advanced auto tuning According to the desired command sources for start frequency and speed, Pr.79 can be set in simple steps.
• Terminal Connection
Many kinds of three phase induction motors can be Diagram
Blinking Blinking 15
FR-E720-3.7K(Advanced magnetic flux vector control) optimally controlled with Mitsubishi's original "non- Operation method Panel display • Terminal Specification
Load SF-JR 4P 3.7kW rotation" auto tuning function. High precision tuning is
Start command Speed command Monitor LED
Setting is Explanation
torque (%) RUN button Setting dial 79 - 1
PU EXT
completed
enabled even when a test operation of a machine cannot Blinking
EXT
and • Parameter unit 17
STF/STR
Setting dial 79 - 3 ON Blinking
flicker.
• FR Configurator
Press and button Turn to select RUN button Analog voltage
PU EXT
100% input
79 - 4 Blinking ON Press to set.
simultaneously (0.5s). operation method.
3Hz 30Hz 60Hz
0
(3) With a provided USB connector, setting is easily done from • Parameter List 21
500 1000 1500 2000
-100%
a personal computer using FR Configurator
An USB connector (mini-B connector) is provided as standard. The inverter can be easily connected without a USB-RS-485 converter.
-200%
• Explanations 28
Wizard (interactive) function of FR Configurator (inverter setup software) provides setting support. of Parameters
In addition, a high-speed graph function with USB enables high speed sampling display.
Expanded advanced
Speed (r/min) operability with USB
Setting wizard function (example: acceleration/deceleration time setting)
and FR Configurator • Protective 51
Functions
High speed graph function
Advanced magnetic flux vector control is ideal
Mini-B
for a lift in an automated-storage system which connector • Option and 52
requires high torque at low speed. Peripheral Devices
Acceleration/deceleration
(2) Short time overload capacity pattern setting • Precautions for
Operation/Selection
is increased (200% 3s) (3) Torque limit/current limit function 63
• Precautions for Peripheral
Short time overload capacity is increased to 200% 3s (200% 0.5s Improved torque limit/current limit function provides a machine Acceleration/deceleration Device Selection
time setting
for the conventional model). Overcurrent trip is less likely to occur. protection, load limit, and stop-on-contact operation.
Inverter
• Application 68
USB cable to Motor
Parameter list display FR Configurator
(4) Enclosure surface operation panel (5) Parameter unit FR-PU07/ • Main Differences and
Compatibilities with 72
FR-PA07 (option) FR-PU07BB(-L) (option) the FR-E500 Series
Optional enclosure surface operation panel (FR-PA07) The FR-PU07/FR-PU07BB(-L), an optional parameter unit, can
can be connected. be connected as well.
In addition, an operation panel for conventional model (FR-
A parameter unit connection cable (FR-CB20 ) is separately • Warranty 73
required. (Parameter unit connection cable FR-CB203 (3m) is
E500 series) can be connected. enclosed with FR-PU07BB(-L).)
The operation panel of the inverter cannot be removed. •Setting such as direct input method with a numeric keypad,
A parameter unit connection cable (FR-CB20 ) is operation status indication, and help function are useful.
separately required. • Service
When a bogie runs over a bump, the impact Using the torque limit function, machine
The display language can be selected from 8 languages. • International FA Center 74
•Parameter settings of maximum of three inverters can be stored.
can be beared by this function. breakage from overload can be avoided.
•A battery pack type (FR-PU07BB(-L)) allows parameter
For example, edge chipping of a tool can be avoided.
setting and parameter copy without powering on the inverter.
To use a parameter unit with battery pack (FR-PU07BB) outside of Japan, order a
“FR-PU07BB-L” (parameter unit type indicated on the package has L at the end).
1 2
Enhanced expandability Ensured maintenance
Features
Expandability catching up with the FR-A700 series are available. 700 series are the pioneer of long life and high reliability.
(1) A variety of plug-in options are mountable (1) Long-life design (3) Easy replacement of cooling fan
Peripheral
Devices
Plug-in options supporting digital input, analog output extension, and a variety of communications provide extended functions which is •The design life of the cooling fan has been extended to 10 A cooling fan is provided on top of the
almost equivalent to the FR-A700 series. (One type of plug-in option can be mounted.) years*1. The life of the fan can be further extended utilizing the inverter for all capacities requiring a
it’s ON/OFF control. cooling fan*.
[ For the FR-E700 series, use the "FR-A7 E kit" which is a set of optional board and dedicated front cover.] •The design life of the capacitors has been extended to 10
Specifications
A cooling fan can be easily replaced
Standard
years by adopting a capacitor that endures 5000 hours at
without disconnecting main circuit wires.
105˚C surrounding air temperature*1,*2.
*: Cooling fans are equipped with FR-E720-1.5K or more,
*1: Surrounding air temperature : annual average 40˚C (free from corrosive gas, flammable gas, FR-E740-1.5K or more, and FR-E720S-0.75K or more.
oil mist, dust and dirt) Since the design life is a calculated value, it is not a guaranteed value.
Compatible Plug-in Options
Dimension
Drawings
*2: Output current : 80% of the inverter rated current
Outline
• FR-A7AX E kit ...16-bit digital input • FR-A7NC E kit ...CC-Link • Life indication of life components (4) Combed shaped wiring cover
• FR-A7AY E kit ...Digital output • FR-A7ND E kit ...DeviceNet Components Guideline of the FR-E700 Life Guideline of JEMA*3
Since a wiring cover can be installed
Cooling fan 10 years 2 to 3 years
Extension analog output • FR-A7NP E kit ...PROFIBUS-DP
Terminal Specification
Terminal Connection
Main circuit smoothing capacitor 10 years 5 years after wiring, wiring work is easily done.
Explanation
• FR-A7AR E kit ...Relay output • FR-A7NL E kit ...LONWORKS
Diagram
Printed board smoothing capacitor 10 years 5 years
*3: Excerpts from “Periodic check of the transistorized inverter” of JEMA (Japan Electrical Manufacturer’s Association)
Operation panel
FR Configurator
Parameter unit
Plug-in option
Plug-in option dedicated front cover •Degrees of deterioration of main circuit capacitor, control circuit
capacitor, and inrush current limit circuit can be monitored.
(5) Removable control terminal block
(2) Control terminals are •Trouble can be avoided with the self-diagnostic alarm*4 that is
Parameter
output when the life span is near. Wiring of the control circuit when replacing the same series
selectable according to applications (3) Various kinds of networks are supported
List
*4: Any one of main circuit capacitor, control circuit capacitor, inrush current limit circuit or inverter can be done by changing the terminal block.
cooling fan reaches the output level, an alarm is output.
Terminal cards other than standard EIA-485 (RS-485), ModbusRTU (equipped as standard), CC-Link, Capacity of the main circuit capacitor can be measured by setting parameter at a stop and
terminal such as analog, pulse train PROFIBUS-DP, DeviceNet®, LONWORKS® (option) turning the power from off to on. Measuring the capacity enables an alarm to be output.
Explanations
Parameters
(available soon), two port RS-485 LONWORKS® is a registered trademark of Echelon Corporation, DeviceNet® is of ODVA,
of
terminal are available as options. and PROFIBUS is of PROFIBUS User Organization.
A crimp ring terminal type is also Terminal
card
Other company and product names herein are the trademarks of their respective owners.
Environment-friendly
available. (to be released)
(4) Brake resistor can be connected Human and environment-friendly inverter
Protective
Functions
A terminal card is removable and
can be easily replaced from a to the 0.4K to 15K
standard terminal card.
(1) Compliance with the EU Restriction (2) Filter options
A brake transistor is built-in to the 0.4K to 15K.
Connecting an optional brake resistor increases regeneration
of Hazardous Substances (RoHS) • The inverter with filterpack FR-BFP2 (a package of power factor
Options
capability. The inverter is human and environment-friendly by being improving DC reactor, common mode choke and capacitive
compliance with the RoHS Directive. filter) conforms to the Japanese harmonic suppression guideline.
• Noise filter option which is compatible with EMC Directive
(EN61800-3 2nd Environment Category C3) is available.
Instructions
Compact and space saving
Compact design expands flexibility of enclosure design. Full of useful functions
Enhanced functions for all sorts of applications
(1) Compact body with (2) Side by side installation saves space
Motor
high performance function Space can be saved by side by side
• Automatic restart after instantaneous power failure function • Power-failure deceleration stop function/operation
with frequency search continuation at instantaneous power failure function
Installation size is the same as the conventional mode (FR-E500 no clearance installation*.
The motor can be decelerated to a stop when a power failure
Compatibility
series) in consideration of intercompatibility. *: Use the inverter at the surrounding air temperature Input voltage Output frequency Input voltage Output frequency or undervoltage occurs to prevent the motor from coasting.
of 40˚C or less.
(7.5K or less) This function is useful to stop a motor at power failure as a fail
Motor speed Motor speed
safe of machine tool, etc.
With the new operation continuation function at instantaneous
Warranty
(3) Heatsink protrusion attachment option Output current Output current
power failure, the motor continues running without coasting
even if an instantaneous power failure occurs during operation.
(1.5K or more) (available soon) FR-E500 series FR-E700 series
*: The inverter may trip and the motor may coast depending on the load condition.
128mm Detection of coasting speed (frequency search function) prevents the motor speed from
A heatsink part of the inverter can be protruded outside of the decreasing at a restart, starting the motor smoothly with less output current.
enclosure by fitting an optional heatsink protrusion attachment
Inquiry
FR-E7CN.
• Brake sequence mode is useful for mechanical brake control of a lift.
• Regeneration avoidance function prevents regenerative overvoltage in a pressing machine.
Protruding a hot section outside of the enclosure can downsize • Optimum excitation control can save more energy with the maximum motor efficiency control.
FR-E720-0.2K FR-E520-0.2K enclosure and reduce cost for enclosure cooling equipments. • Main circuit power supply DC input can be connected to DC power supply.
• Enhanced I/O terminal function supports switchover of analog input (voltage / current).
and so on
3 4
Features
Lineup Connection with Peripheral Devices
AC power supply
Use within the permissible power supply
Peripheral
Devices
specifications of the inverter.
Specifications
Moulded case circuit breaker FR-PU07/FR-PU07BB(-L).
Standard
(MCCB) or earth leakage current Parameter unit
Symbol Voltage Symbol Number of Power Phases Symbol Inverter Capacity Symbol Protective Structure breaker (ELB), fuse (FR-PU07/FR-PU07BB(-L))
The breaker must be selected carefully
1 100V class None Three-phase input Represents the None Enclosed-type structure IP20 USB connector
since an in-rush current flows in the
2 200V class S Single-phase input 0.1K to 15K inverter capacity C Totally enclosed structure IP40 A personal computer and an inverter can
Dimension
Drawings
inverter at power on.
Outline
4 400V class Single-phase input "kW". be connected with a USB (Ver1.1) cable.
W
(double voltage output)
Terminal Specification
Terminal Connection
safety. Do not use this magnetic
Explanation
Diagram
Inverter Capacity contactor to start and stop the inverter.
0.1K 0.2K 0.4K 0.75K 1.5K 2.2K 3.7K 5.5K 7.5K 11K 15K
Inverter Type Doing so will cause the inverter life to be
Enclosed-type shorten.
Three-phase 200V structure (IP20) Reactor (FR-HAL, FR-HEL option)
Operation panel
FR Configurator
Parameter unit
FR-E720- Totally enclosed Reactors (option) must be used when
power harmonics measures are taken,
structure (IP40)
the power factor is to be improved or the
Enclosed-type inverter is installed near a large power
Brake resistor
Three-phase 400V structure (IP20) supply system (500kVA or more). The (FR-ABR, MRS, MYS)
Parameter
Braking capability can be improved.
FR-E740- Totally enclosed inverter may be damaged if you do not
(0.4K or more)
List
use reactors. Select the reactor
structure (IP40) Always install a thermal relay when
according to the model. Remove the using a brake resistor whose
Single-phase 200V Enclosed-type jumpers across terminals P/+ - P1 to capacity is 11K or more.
FR-E720S- * structure (IP20) connect the DC reactor.
Explanations
Parameters
Single-phase 100V Enclosed-type
of
FR-E710W- * structure (IP20) AC reactor (FR-HAL) DC reactor (FR-HEL)*
*:Output of the single-phase 200V and single-phase 100V input specifications is three-phase 200V. :Available models :Models to be released :Not available
P/+
Protective
Functions
PR
P/+ P1 R/L1 S/L2 T/L3
P/+ N/- U VW
Earth
(Ground)
Options
Complies with UL, cUL, EN (LVD) standards EMC filter (ferrite core)*
(FR-BSF01, FR-BLF) EMC filter (ferrite core)
Install a noise filter to (FR-BSF01, FR-BLF)
reduce the electromagnetic Install a noise filter to reduce the
Instructions
noise generated from the
inverter. Effective in the EMC filter electromagnetic noise
range from about 1MHz to (capacitor)* generated from the inverter.
10MHz. When more wires (FR-BIF) Effective in the range from about
are passed through, a more Reduces 1MHz to 10MHz. A wire should be
effective result can be the radio wound four turns at a maximum.
obtained. A wire should be noise.
wound four turns or more. Motor
Motor
*Filterpack (FR-BFP2), which contains DC reactor and noise filter in one package, is also available.
Compatibility
Brake unit (FR-BU2)
Earth
(Ground)
Warranty
Devices connected to the output
P/+ PR
Do not install a power factor correction capacitor,
P/+ surge suppressor or radio noise filter on the output
PR side of the inverter. When installing a moulded case
circuit breaker on the output side of the inverter,
contact each manufacturer for selection of the
Inquiry
moulded case circuit breaker.
High power factor Power regeneration Register unit (FR-BR) Earth (Ground)
converter (FR-HC) common converter (FR-CV) Discharging resistor (GZG, GRZG) To prevent an electric shock, always earth (ground)
Power supply harmonics Great braking capability is obtained. The regenerative braking capability the motor and inverter. For reduction of induction noise
can be greatly suppressed. Install this as required. of the inverter can be exhibited fully. from the power line of the inverter, it is recommended
Install this as required. Install this as required. to wire the earth (ground) cable by returning it to the
earth (ground) terminal of the inverter.
5 6
Standard specifications
Rating
z Three-phase 200V power supply
Type FR-E720-
K(-C) ∗9 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Applicable motor capacity (kW) ∗1 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated capacity (kVA) ∗2 0.3 0.6 1.2 2.0 3.2 4.4 7.0 9.5 13.1 18.7 23.9
0.8 1.5 3 5 8 11 17.5 24 33 47 60
Rated current (A) ∗7
Output
(0.8) (1.4) (2.5) (4.1) (7) (10) (16.5) (23) (31) (44) (57)
Overload current rating ∗3 150% 60s, 200% 3s (inverse-time characteristics)
Voltage ∗4 Three-phase 200 to 240V
Regenerative braking torque ∗5 150% 100% 50% 20%
Rated input
Three-phase 200 to 240V 50Hz/60Hz (283 to 339VDC ∗8)
Power supply
AC (DC) voltage/frequency
Permissible AC (DC) voltage
170 to 264V 50Hz/60Hz (240 to 373VDC ∗8)
fluctuation
Permissible frequency fluctuation ±5%
Power supply capacity (kVA) ∗6 0.4 0.8 1.5 2.5 4.5 5.5 9 12 17 20 28
Protective structure (JEM1030) Enclosed type (IP20). IP40 for totally enclosed structure series.
Cooling system Self-cooling Forced air cooling
Approximate mass (kg) 0.5 0.5 0.7 1.0 1.4 1.4 1.7 4.3 4.3 6.5 6.5
Protective structure (JEM1030) Enclosed type (IP20). IP40 for totally enclosed structure series.
Cooling system Self-cooling Forced air cooling
Approximate mass (kg) 1.4 1.4 1.9 1.9 1.9 3.2 3.2 6.0 6.0
∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
∗2 The rated output capacity indicated assumes that the output voltage is 230V for three-phase 200V class and 440V for three-phase 400V class.
∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load.
∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about 2 that of the power supply.
∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A
brake unit (FR-BU2) may also be used. (Option brake resisitor cannot be used for 0.1K and 0.2K.)
∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation in the surrounding air temperature exceeding 40°C (totally-
enclosed structure is 30°C), the rated output current is the value in parenthesis.
∗8 y Connect DC power supply to terminal P/+ and N/-. Connect the plus side of the power supply to terminal P/+ and minus side to terminal N/-.
y Since the voltage between P/+ and N/- may increase due to the regeneration energy from the motor and exceeds 415V temporarily, select the DC power
supply which can withstand the voltage/energy during regeneration. If using the power supply which can not withstand voltage/energy during regeneration,
insert diodes in series for reverse current prevention.
y Although the FR-E700 series has the built-in inrush current limit circuit, select the DC power supply considering the inrush current at powering ON as the
inrush current four times of the rated inverter flows at powering ON.
y Since the power supply capacity depends on the output impedance of the power, select the power supply capacity which has enough allowance according
to the AC power supply system capacity.
∗9 Totally enclosed structure series ends with -C.
7
z Single-phase 200V power supply
Type FR-E720S-
K 0.1 0.2 0.4 0.75 1.5 2.2
Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75 1.5 2.2
Features
Rated capacity (kVA)∗2 0.3 0.6 1.2 2.0 3.2 4.4
0.8 1.5 3.0 5.0 8.0 11.0
Rated current (A)∗7
Output
Peripheral
Devices
Rated output voltage∗4 Three-phase 200 to 240V
Regenerative braking torque ∗5 150% 100% 50% 20%
Rated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60Hz
Power supply
Specifications
Permissible AC voltage fluctuation 170 to 264V 50Hz/60Hz
Standard
Permissible frequency fluctuation Within ±5%
Power supply capacity (kVA)∗6 0.5 0.9 1.5 2.5 4.0 5.2
Dimension
Drawings
Outline
Cooling system Self-cooling Forced air cooling
Approximate mass (kg) 0.6 0.6 0.9 1.4 1.5 2.0
Terminal Specification
Terminal Connection
z Single-phase 100V power supply
Explanation
Diagram
Type FR-E710W-
K 0.1 0.2 0.4 0.75
Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75
Rated capacity (kVA)∗2 0.3 0.6 1.2 2.0
Operation panel
FR Configurator
Parameter unit
0.8 1.5 3.0 5.0
Rated Current (A)∗7
(0.8) (1.4) (2.5) (4.1)
Output
Parameter
Rated output voltage Three-phase 200 to 230V ∗8, ∗9
List
Regenerative braking torque ∗5 150% 100%
Rated input AC voltage/frequency Single-phase 100 to 115V 50Hz/60Hz
Power supply
Explanations
Parameters
Permissible frequency fluctuation Within ±5%
of
Power supply capacity (kVA)∗6 0.5 0.9 1.5 2.5
Protective
Functions
Cooling system Self-cooling
Approximate mass (kg) 0.6 0.7 0.9 1.5
∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
Options
∗2 The rated output capacity indicated assumes that the output voltage is 230V.
∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or
power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection
level and load of 100% or more may not be available.
Instructions
∗4 The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
the pulse voltage value of the inverter output side voltage remains unchanged at about 2 that of the power supply.
∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A
Motor
brake unit (FR-BU2) may also be used. (Option brake resisitor cannot be used for 0.1K and 0.2K.)
∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
∗7 Setting 2kHz or more in Pr. 72 PWM frequency selection to perform low acoustic noise operation with the surrounding air temperature exceeding 40°C, the
rated output current is the value in parenthesis.
Compatibility
∗8 For single-phase 100V power input model, the maximum output voltage is twice the amount of the power supply voltage and cannot be exceeded.
∗9 In a single-phase 100V power input model, the output voltage may fall down when the load is heavy, and larger output current may flow compared to a
threephase input model. Use the motor with less load so that the output current is within the rated motor current range.
Warranty
Inquiry
8
Common specifications
Soft-PWM control/high carrier frequency PWM control (V/F control, Advanced magnetic flux vector control,
Control method General-purpose magnetic flux vector control, Optimum excitation control are available)
Output frequency range 0.2 to 400Hz
0.06Hz/60Hz (terminal2, 4: 0 to 10V/10bit)
Frequency setting Analog input 0.12Hz/60Hz (terminal2, 4: 0 to 5V/9bit)
Control specifications
Acceleration/deceleration time setting 0.01 to 360s, 0.1 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/
deceleration modes are available.
DC injection brake Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) can be changed.
Stall prevention operation level Operation current level can be set (0 to 200% adjustable), whether to use the function or not can be selected
Two terminals
Analog input Terminal 2: 0 to 10V, 0 to 5V can be selected
Frequency setting Terminal 4: 0 to 10V, 0 to 5V, 4 to 20mA can be selected
signal The signal is entered from the operation panel or parameter unit.
Digital input Frequency setting increment can be set.
4 digit BCD or 16bit binary data (when the option FR-A7AX E kit is used)
Start signal Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected.
Input signal The following signals can be assigned to Pr. 178 to Pr.184 (input terminal function selection): multi-speed selection,
(Standard control circuit terminal remote setting, stop-on contact selection, second function selection, terminal 4 input selection, JOG operation
selection, PID control valid terminal, brake opening completion signal, external thermal input, PU-External
Operation specifications
model:Seven terminals operation switchover, V/F switchover, output stop, start self-holding selection, forward rotation, reverse rotation
Safety stop function model: Six command, inverter reset, PU-NET operation switchover, External-NET operation switchover, command source
terminals) switchover, inverter operation enable signal, and PU operation external interlock
Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection,
automatic restart after instantaneous power failure operation, forward/reverse rotation prevention, remote setting,
Operational functions brake sequence, second function, multi-speed operation, stop-on contact control, droop control, regeneration
avoidance, slip compensation, operation mode selection, offline auto tuning function, PID control, computer link
operation (RS-485)
Output signal The following signals can be assigned to Pr.190 to Pr.192 (output terminal function selection): inverter operation, up-
Open collector output (Two terminals) to-frequency, overload alarm, output frequency detection, regenerative brake prealarm, electronic thermal relay
Relay output (One terminal) function prealarm, inverter operation ready, output current detection, zero current detection, PID lower limit, PID
upper limit, PID forward/reverse rotation output, brake opening request, fan alarm∗1, heatsink overheat pre-
Operating status alarm, deceleration at an instantaneous power failure, PID control activated, during retry, life alarm, current
average value monitor, remote output, alarm output, fault output, fault output 3, and maintenance timer alarm
The following signals can be assigned to Pr.54 FM terminal function selection: output frequency, motor current
For meter (steady), output voltage, frequency setting, motor torque, converter output voltage, regenerative brake duty,
Pulse train output (Max. 2.4kHz: electronic thermal relay function load factor, output current peak value, converter output voltage peak value,
one terminal) reference voltage output, motor load factor, PID set point, PID measured value, output power
Pulse train output (1440 pulses/s/full scale)
The following operating status can be displayed: output frequency, motor current (steady), output voltage,
frequency setting, cumulative energization time, actual operation time, motor torque, converter output voltage,
Operating status regenerative brake duty, electronic thermal relay function load factor, output current peak value, converter output
voltage peak value, motor load factor, PID set point, PID measured value, PID deviation, inverter I/O terminal
Indication
Operation panel
monitor, I/O terminal option monitor, output power, cumulative power, motor thermal load factor, and inverter
thermal load factor.
Parameter unit
(FR-PU07) Fault definition is displayed when a fault occurs. Past 8 fault definitions (output voltage/current/frequency/
Fault definition cumulative energization time right before the fault occurs) are stored
Interactive
Function (help) for operation guide ∗2
guidance
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage
during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection
Protective thermal operation, motor protection thermal operation, heatsink overheat, input phase failure∗4, output side earth
(ground) fault overcurrent at start∗3, output phase failure, external thermal relay operation ∗3, option fault ∗3,
functions parameter error, internal board fault, PU disconnection, retry count excess ∗3, CPU fault, brake transistor alarm,
Protective/warning
function inrush resistance overheat, communication error, analog input error, USB communication error, brake sequence
error 4 to 7 ∗3
Warning Fan alarm∗1, overcurrent stall prevention, overvoltage stall prevention, PU stop, parameter write error,
regenerative brake prealarm ∗3, electronic thermal relay function prealarm, maintenance output ∗3, undervoltage,
functions operation panel lock, password locked, inverter reset
Surrounding air temperature -10°C to +50°C (non-freezing) (-10°C to +40°C for totally-enclosed structure feature) ∗5
Environment
9
Outline Dimension Drawings
zFR-E720-0.1K to 0.75K
zFR-E720S-0.1K to 0.4K
zFR-E710W-0.1K to 0.4K
Features
φ5 hole When used with the plug-in option
Peripheral
Devices
118
128
Specifications
Standard
Rating
Rating
plate
plate
Capacity
plate
Dimension
Drawings
Outline
4 4
5
5
56 D1 D1
68 D D2 ∗
Terminal Specification
Terminal Connection
Inverter Type D D1 D2 ∗
Explanation
Diagram
FR-E720-0.1K, 0.2K
FR-E720S-0.1K, 0.2K 80.5 10 95.6
FR-E710W-0.1K
Operation panel
FR Configurator
Parameter unit
FR-E710W-0.2K 110.5 10 125.6
FR-E720-0.4K 112.5 42 127.6
FR-E720-0.75K 132.5 62 147.6
FR-E720S-0.4K
142.5 42 157.6
FR-E710W-0.4K
Parameter
∗ When the FR-A7NC E kit is mounted, a terminal block protrudes making the
List
depth approx. 2mm greater.
Explanations
Parameters
(Unit: mm)
of
zFR-E720-1.5K, 2.2K
zFR-E720S-0.75K, 1.5K
zFR-E710W-0.75K
Protective
Functions
When used with the plug-in option
2-φ5 hole
5
Options
*1
Rating Rating
118
128
plate plate
Instructions
Capacity
plate
5 5 5
5
D1 D1
Motor
96
108 D D2*2
∗1 FR-E710W-0.75K are not provided with the cooling fan.
Compatibility
Inverter Type D D1 D2 ∗2
FR-E720-1.5K, 2.2K
135.5 150.6
FR-E720S-0.75K 60
Warranty
(Unit: mm)
10
zFR-E720-3.7K
5
Rating
118
128
Rating
plate plate
Capacity
plate
5 5 5
5
158 66.5 66.5
170 D D1 *
Inverter Type D D1 ∗
FR-E720-3.7K 142.5 157.6
∗ When the FR-A7NC E kit is mounted, a terminal block protrudes
making the depth approx. 2mm greater.
(Unit: mm)
zFR-E720-5.5K to 15K
Rating Rating
plate plate
D3 D3
8
6 W1 D2 D2
W D D1*
Capacity
plate
Inverter Type W W1 W2 D D1 ∗ D2 D3
FR-E720-5.5K, 7.5K 180 164 180 165 180.1 71.5 10
FR-E720-11K, 15K 220 195 211 190 205.1 84.5 10.5
∗ When the FR-A7NC E kit is mounted, a terminal block protrudes making the depth approx. 2mm greater.
W2
(Unit: mm)
11
zFR-E740-0.4K to 3.7K
zFR-E720S-2.2K
Features
When used with the plug-in option
2-φ5 hole
6
*1 *1
Peripheral
Devices
138
150
Rating Rating
plate plate
Specifications
Standard
Capacity
plate
5 5
Dimension
5
Drawings
6
Outline
D1 D1
128
D D2 *2
140
∗1 FR-E740-0.4K, 0.75K are not provided with the cooling fan.
Terminal Specification
Terminal Connection
Explanation
Diagram
Inverter Type D D1 D2 ∗2
FR-E740-0.4K, 0.75K 114 39 129.1
FR-E740-1.5K to 3.7K 135 150.1
60
Operation panel
FR Configurator
Parameter unit
FR-E720S-2.2K 155.5 170.6
∗2 When the FR-A7NC E kit is mounted, a terminal block protrudes
making the depth approx. 2mm greater.
Parameter
List
(Unit: mm)
Explanations
Parameters
zFR-E740-5.5K, 7.5K
of
When used with the plug-in option
2-φ5 hole
6
Protective
Functions
150
138
Rating Rating
Options
plate plate
Capacity
Instructions
plate
5 10 10
6
208 68 68
220 D D1*
Motor
Inverter Type D D1 ∗
Compatibility
(Unit: mm)
Inquiry
12
zFR-E740-11K, 15K
8
2-φ6 hole
FAN FAN
244
260
Rating Rating
plate plate
6 10.5 10.5
8
Inverter Type D D1 ∗
FR-E740-11K, 15K 190 205.1
∗ When the FR-A7NC E kit is mounted, a terminal block protrudes making the
depth approx. 2mm greater.
211
(Unit: mm)
13
zParameter unit (option) (FR-PU07)
<Outline drawing> <Panel cut dimension drawing>
Features
25.05
(14.2) (11.45)
83
2.5
40 40
Peripheral
Devices
*1
*1
Air-bleeding
50
51
hole
4-R1
Specifications
Standard
*1
*1
135
67
56.8
57.8
Dimension
Drawings
Outline
26.5 26.5 4-φ4 hole
Terminal Specification
Terminal Connection
(Effective depth of the
Explanation
installation screw hole 5.0)
Diagram
M3 screw *2
∗1 When installing the FR-PU07 on the enclosure, etc., remove
screws or fix the screws to the FR-PU07 with M3 nuts.
∗2 Select the installation screw whose length will not exceed the
Operation panel
FR Configurator
Parameter unit
80.3 effective depth of the installation screw hole. (Unit: mm)
Parameter
83
List
8.2 46.7
18
6
Explanations
Parameters
of
135
Protective
Functions
Options
44.7
Instructions
46.7
(Unit: mm)
zEnclosure surface operation panel (option) (FR-PA07)
<Outline drawing> <Panel cut dimension drawing>
Motor
22
68
22
Compatibility
Warranty
59
2-M3 screw
Inquiry
(Unit: mm)
14
Terminal Connection Diagram
Earth
(Ground)
Main circuit Earth (Ground)
Control circuit
Standard control terminal block
Control input signals (No voltage input allowed) C Relay output
Forward STF
Terminal functions vary rotation start Terminal functions vary
B by Pr. 192 A,B,C terminal
with the input terminal Reverse STR Relay output
assignment (Pr. 178 to rotation start (Fault output) function selection
A
Pr. 184) RH
High
speed
RM Open collector output
Multi-speed selection Middle
speed Terminal functions vary with
*2 When using terminals PC- RUN
Low RL the output terminal assignment
SD as a 24VDC power Running
speed (Pr. 190 and Pr. 191)
supply, take care not to MRS
short across terminals Output FU
SOURCE
Reset
SD SE Open collector output common
Contact input common Sink/source common
24VDC power supply PC *2
(Common for external power supply transistor) Calibration resistor
Indicator
+ - (Frequency meter, etc.)
Frequency setting signals (Analog)
3 10(+5V) FM Moving-coil type
*3 Terminal input specifications Frequency 1mA full-scale
can be changed by analog setting *9
input specifications 2 2 0 to 5VDC *3 SD
switchover (Pr. 73). potentiometer (0 to 10VDC)
1/2W1kΩ *9 It is not necessary when
*4 It is recommended to use 2W1kΩ *4 PU calibrating the indicator
1 5(Analog common) from the operation panel.
when the frequency setting signal connector
is changed frequently.
Terminal 4 input (+) 4 4 to 20mADC
(Current input) (-) 0 to 5VDC
*5 Terminal input specifications can be changed by analog 0 to 10VDC *5 USB
input specifications switchover (Pr. 267). Set the connector
voltage/current input switch in the "V" position to select
voltage input (0 to 5V/0 to10V) and "I" (initial value) to I V
select current input (4 to 20mA).
To use terminal 4 (initial setting is current input), set "4" Voltage/current
in any of Pr.178 to Pr.184 (input terminal function selection) input switch *5
to assign the function, and turn ON AU signal.
Note
y To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
y After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
y The output of the single-phase power input model is three-phase 200V.
15
Terminal Specification Explanation
Terminal
Type Terminal Name Description
Symbol
Connect to the commercial power supply. Keep these terminals open when using the high power
R/L1, S/L2,
AC power input factor converter (FR-HC) or power regeneration common converter (FR-CV).
Features
T/L3 * ∗ When using single-phase power input, terminals are R/L1 and S/L2.
U, V, W Inverter output Connect a three-phase squirrel-cage motor.
Brake resistor Connect a brake transistor (MRS type, MYS type, FR-ABR) across terminals P/+-PR.
P/+, PR
Main circuit
connection (The brake resistor can not be connected to the 0.1K or 0.2K)
Connect the brake unit (FR-BU2), power regeneration common converter (FR-CV) or high power
Brake unit connection factor converter (FR-HC).
Peripheral
Devices
P/+, N/-
DC power input Connect the plus side of the power supply to terminal P/+ and minus side to terminal N/-.
Remove the jumper across terminals P/+-P1 and connect a DC reactor. Single-phase 100V power
P/+, P1 * DC reactor connection input model is not compatible with DC reactor.
∗ Terminal P1 is not available for single-phase 100V power input model.
Specifications
Standard
Earth (Ground) For earthing (grounding) the inverter chassis. Must be earthed (grounded).
STF Forward rotation start Turn on the STF signal to start forward rotation and turn it off to stop. When the STF and STR signals
are turned on simultaneously,
STR Reverse rotation start Turn on the STR signal to start reverse rotation and turn it off to stop. the stop command is given.
RH, RM, RL Multi-speed selection Multi-speed can be selected according to the combination of RH, RM and RL signals.
Dimension
Drawings
Outline
Turn on the MRS signal (20ms or more) to stop the inverter output.
MRS Output stop Use to shut off the inverter output when stopping the motor by electromagnetic brake.
Used to reset alarm output provided when protective circuit is activated. Turn on the RES signal for
RES Reset more than 0.1s, then turn it off. Initial setting is for reset always. By setting Pr. 75, reset can be set to
enabled only at fault occurrence. Recover about 1s after reset is cancelled.
Contact input
Terminal Specification
Terminal Connection
Contact input common
Explanation
Common terminal for contact input terminal (sink logic) and terminal FM.
Diagram
(sink) (initial setting)
When connecting the transistor output (open collector output), such as a programmable controller,
External transistor
SD when source logic is selected, connect the external power supply common for transistor output to this
common (source) terminal to prevent a malfunction caused by undesirable currents.
Control circuit/input signal
Operation panel
FR Configurator
Common output terminal for 24VDC 0.1A power supply (PC terminal).
Parameter unit
common Isolated from terminals 5 and SE.
External transistor When connecting the transistor output (open collector output), such as a programmable controller,
common when sink logic is selected, connect the external power supply common for transistor output to this
(sink) (initial setting) terminal to prevent a malfunction caused by undesirable currents.
PC
Contact input common
Common terminal for contact input terminal (source logic).
Parameter
(source)
List
24VDC power supply Can be used as 24VDC 0.1A power supply.
5VDC
Frequency setting Used as power supply when connecting potentiometer for frequency setting
10 permissible load
power supply (speed setting) from outside of the inverter.
current 10mA
Explanations
Parameters
Inputting 0 to 5VDC (or 0 to 10V) provides the maximum output
Input resistance 10kΩ ± 1kΩ
Frequency setting frequency at 5V (10V) and makes input and output proportional.
Frequency setting
of
(voltage) Use Pr. 73 to switch between input 0 to 5VDC (initial setting) and 0
20VDC
to 10VDC input.
Voltage input:
Inputting 0 to 20mADC (or 0 to 5V / 0 to 10V) provides the
Input resistance 10kΩ ± 1kΩ
maximum output frequency at 20mA makes input and output
Permissible maximum voltage
Protective
Functions
proportional. This input signal is valid only when the AU signal is on
Frequency setting 20VDC
4 (terminal 2 input is invalid). Use Pr. 267 to switch from among input
(current) 4 to 20mA (initial setting), 0 to 5VDC and 0 to 10VDC. Set the
Current input:
Input resistance 233Ω ± 5Ω
voltage/current input switch in the "V" position to select voltage
Maximum permissible current
input (0 to 5V/0 to 10V).
30mA.
Frequency setting
Options
5 Common terminal for the frequency setting signals (terminals 2 or 4). Do not earth (ground).
common
1 changeover contact output indicates that the inverter fault occurs.
Relay
Relay output
A, B, C Fault: discontinuity across B-C (continuity across A-C), Normal: continuity across B-C (discontinuity
(fault output)
Control circuit/output signal
across A-C) Contact capacity 230VAC 0.3A (power factor = 0.4) 30VDC 0.3A
Instructions
Switched low when the inverter output frequency is equal to or Permissible load 24VDC
RUN Inverter running higher than the starting frequency (initial value 0.5Hz). Switched (Maximum 27VDC) 0.1A
Open collector
high during stop or DC injection brake operation.∗ (a voltage drop is 3.4V maximum
when the signal is on)
Switched low when the inverter output frequency is equal to or ∗ Low indicates that the open
FU Frequency detection higher than the preset detected frequency and high when less than collector output transistor is on
the preset detected frequency.∗ (conducts). High indicates that the
Motor
y The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.
y indicates that terminal functions can be selected using Pr. 178 to Pr. 192 (I/O terminal function selection).
y Terminal names and terminal functions are those of the factory set.
y When connecting the DC power supply, be sure to connect the plus side of the power supply to terminal P/+ and
minus side to terminal N/-. Opposite polarity will damage the inverter.
16
Explanation of the Operation Panel
Output current
Output voltage
17
Basic operation of the operation panel
Features
Operation mode switchover
Peripheral
Devices
Specifications
Standard
PU Jog operation mode
Dimension
Drawings
Monitor/frequency setting
(Example)
Outline
PU operation mode
Value change and frequency flicker.
(output frequency monitor)
Terminal Specification
Terminal Connection
Frequency setting has been
Explanation
written and completed!!
Diagram
STOP
Operation panel
FR Configurator
Output current monitor
Parameter unit
Output voltage monitor
Parameter
List
Parameter setting
Explanations
Parameters
Display the
of
Parameter setting mode present setting
(Example)
Protective
Functions
Value change Parameter and a setting value
flicker alternately.
Parameter write is completed!!
Options
Parameter clear All parameter Faults history clear
Instructions
clear
Initial value
Motor
change list
Faults history
Compatibility
18
Explanations of Parameter unit
FR-PU07BB
z Main functions
Function Description
Monitor 6 types of monitors appear by simply pressing .
For PU operation mode and External/PU combined operation mode (Pr.79 = "3"), frequency setting is available.
Frequency setting Settings is performed by the direct setting, which sets frequency directly by to , and the step setting, which
sets frequency continuously by .
Reading parameter and changing setting values are easily done. To change the setting value of an parameter, specify
Parameter Setting
the parameter number, or select a parameter from the functional parameter list.
FR-PU07 (PU07BB) reads parameter settings of an inverter, and stores three different parameter settings.
Batch copy FR-PU07 (PU07BB) can also copy the stored parameter setting to another inverter of the same series, or verify its
stored parameter setting against the parameter setting stored in an inverter.
Switching between External operation mode [EXT] and PU operation mode [PU] is easy.
Operation
Start/stop is enabled during PU operation mode and External/PU operation mode (Pr.79 = "3").
∗ Available function differs by the inverter. Please refer to the instruction manual of the inverter and the parameter unit.
19
FR Configurator (INVERTER SETUP SOFTWARE)
FR-SW3-SETUP-WE
(Microsoft® Windows® 2000 Professional SP4 or later, XP Home Edition SP2 or later, XP Professional SP2 or later
Windows Vista® SP1 or later supported)
Features
FR Configurator is software offers an easy operating environment.
Can be utilized effectively from inverter setting up to maintenance.
Parameter setting, monitoring, etc. can be performed on a display of Windows *1 personal computer.
Peripheral
A personal computer and an inverter can be easily connected with a USB cable.
Devices
(RS-485 communication *2 using PU connector is also available.)
∗1 Microsoft, Windows, Microsoft Windows2000, Microsoft Windows XP, Microsoft Windows Vista are registered
trademarks of Microsoft Corporation in the United States and/or other countries.
∗2 RS-485⇔RS-232C converter is required.
Specifications
Standard
USB cable USB connector
Dimension
Drawings
Outline
<How to open the USB connector cover>
Terminal Specification
Terminal Connection
Explanation
Diagram
Pull the cover in the direction of arrow. Then turn it upward.
Operation panel
FR Configurator
Parameter unit
Startup Monitor area
Desired function can be performed just after a start-up of In Monitor area, inverter status can be monitored.
the software. (1) Displays monitor data in
Parameter
(1) Open the recent used waveform
List
System File Displays current
(2) Perform Easy Setup waveform with High
(3) Perform each functions Speed graph function
(4) Help [Graph]
Explanations
Parameters
(2) Monitors the status of I/O
of
terminals. [I/O Terminal
Monitor]
(3) Displays multiple data in batch. [Batch Monitor]
Easy Setup
Protective
Functions
From station number to parameter setting, setting with System area
wizard style dialog (interactive) is available. In System area, parameter setting, Diagnosis,
Procedure for Easy Setup Troubleshooting, etc. can be performed.
(1) System File setting (1) Parameter reading,
(2) Communication setting
Options
writing, verification,
(3) Inverter recognition Functional List and
(4) Control method selection Individual List display
(5) Motor setting are available.
(6) Start command,
Instructions
[Parameter List]
frequency command (2) Displays alarm history
setting and monitor value at
(7) Parameter setting each alarm
occurrence. [Diagnosis]
(3) Parameter setting conversion from conventional
Motor
be performed. Setting wizard can set parameters with wizard style dialog
(1) Frequency setting and forward/reverse (interactive). Inputting or selecting required items for each
rotation [Test operation] function, parameter setting can be made, without regard to
(2) Display the connected inverter in tree parameter number.
view [System List]
Warranty
FR-SW3-SETUP-WE (for 700 series) and FR-SW1-SETUP-WE (500 series) can be installed from the FR Configurator SW3.
FR-SW3-SETUP-WE is available for download (free of charge) from the below URL on the internet. FR Configurator SW3 (FR-SW3-SETUP-
WE or FR-SW1-SETUP-WE) needs to be installed to the personal computer prior to updating the software. Also, user registration is required
for the download (free of charge.) (Registration is free of charge.)
MELFANSweb homepage address http://www.MitsubishiElectric.co.jp/melfansweb
20
Parameter List
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. For details of parameters, refer to the instruction manual.
REMARKS
y indicates simple mode parameters. (initially set to extended mode)
y The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr.
77Parameter write selection.
Minimum Refer
Func- Initial Customer
Parameter Name Setting Range Setting to
tion Value Setting
Increments Page
Acceleration/deceleration reference
Acceleration/
Acceleration/deceleration time
21 0, 1 1 0 29
increments
prevention
21
Minimum Refer
Func- Initial Customer
Parameter Name Setting Range Setting to
tion Value Setting
Increments Page
Features
41 Up-to-frequency sensitivity 0 to 100% 0.1% 10% 32
Frequency
detection
Peripheral
rotation
Devices
44 Second acceleration/deceleration time 0 to 3600/360s 0.1/0.01s 5/10/15s ∗2 29
Second functions
Specifications
Standard
47 Second V/F (base frequency) 0 to 400Hz, 9999 0.01Hz 9999 28
Second stall prevention operation
48 0 to 200%, 9999 0.1% 9999 31, 45
current
51 Second electronic thermal O/L relay 0 to 500A, 9999 0.01A 9999 29
Dimension
Drawings
0, 5, 7 to 12, 14, 20,
Outline
52 DU/PU main display data selection 23 to 25, 52 to 57, 61, 1 0 33
62, 100
Monitor functions
Terminal Specification
Terminal Connection
24, 52, 53, 61, 62
Explanation
Diagram
55 Frequency monitoring reference 0 to 400Hz 0.01Hz 60Hz 33
Rated
56 Current monitoring reference 0 to 500A 0.01A inverter 33
Operation panel
FR Configurator
Parameter unit
current
Automatic restart
Parameter
List
58 Restart cushion time 0 to 60s 0.1s 1s 34
Explanations
Parameters
— 60 Energy saving control selection 0, 9 1 0 35
of
Automatic acceleration
Protective
Functions
62 Reference value at acceleration 0 to 200%, 9999 1% 9999 35
Options
— 65 Retry selection 0 to 5 1 0 36
Stall prevention operation reduction
— 66 0 to 400Hz 0.01Hz 60Hz 31
starting frequency
67 Number of retries at fault occurrence 0 to 10, 101 to 110 1 0 36
Instructions
Retry
Reset selection/disconnected PU
— 75 0 to 3, 14 to 17 1 14 37
detection/PU stop selection
— 77 Parameter write selection 0, 1, 2 1 0 37
— 78 Reverse rotation prevention selection 0, 1, 2 1 0 37
Warranty
22
Minimum Refer
Func- Initial Customer
Parameter Name Setting Range Setting to
tion Value Setting
Increments Page
80 Motor capacity 0.1 to 15kW, 9999 0.01kW 9999 39
81 Number of motor poles 2, 4, 6, 8, 10, 9999 1 9999 39
82 Motor excitation current 0 to 500A (0 to ****), 9999 ∗5 0.01A (1) ∗5 9999 39
200V/400V
83 Rated motor voltage 0 to 1000V 0.1V 39
∗4
84 Rated motor frequency 10 to 120Hz 0.01Hz 60Hz 39
Speed control gain (Advanced
89 0 to 200%, 9999 0.1% 9999 39
magnetic flux vector)
Motor constants
0 to 50Ω (0 to ****) ,
90 Motor constant (R1) 0.001Ω (1) ∗5 9999 39
9999 ∗5
0 to 50Ω (0 to ****) ,
91 Motor constant (R2) 0.001Ω (1) ∗5 9999 39
9999 ∗5
0 to 1000mH (0 to 50Ω, 0.1mH
92 Motor constant (L1) 9999 39
0 to ****), 9999 ∗5 (0.001Ω, 1) ∗5
23
Minimum Refer
Func- Initial Customer
Parameter Name Setting Range Setting to
tion Value Setting
Increments Page
Features
Automatic restart
Peripheral
Devices
Stall prevention operation level for
165 0 to 200% 0.1% 150% 34
restart
— 168
Specifications
Parameter for manufacturer setting. Do not set.
Standard
— 169
monitor clear
Cumulative
Dimension
Drawings
Outline
171 Operation hour meter clear 0, 9999 1 9999 33
Terminal Specification
Terminal Connection
173 User group registration 0 to 999, 9999 1 9999 42
Explanation
Diagram
174 User group clear 0 to 999, 9999 1 9999 42
0 to 5, 7, 8, 10, 12,
Input terminal function assignment
Operation panel
FR Configurator
Parameter unit
60, 62, 65 to 67, 9999
0 to 5, 7, 8, 10, 12,
179 STR terminal function selection 14 to 16, 18, 24, 25, 1 61 43
61, 62, 65 to 67, 9999
180 RL terminal function selection 1 0 43
Parameter
181 RM terminal function selection 1 1 43
List
182 RH terminal function selection 0 to 5, 7, 8, 10, 12, 1 2 43
14 to 16, 18, 24, 25,
183 MRS terminal function selection 62, 65 to 67, 9999 1 24 43
Explanations
Parameters
184 RES terminal function selection 1 62 43
of
0, 1, 3, 4, 7, 8, 11 to 16,
20, 25, 26, 46, 47, 64,
190 RUN terminal function selection 1 0 43
90, 91, 93, 95, 96, 98,
Output terminal function assignment
Protective
Functions
99, 100, 101, 103, 104,
107, 108,
111 to 116, 120, 125,
126, 146, 147, 164,
191 FU terminal function selection 1 4 43
190, 191, 193, 195, 196,
198, 199, 9999
Options
0, 1, 3, 4, 7, 8, 11 to 16,
20, 25, 26, 46, 47, 64,
90, 91, 95, 96, 98, 99,
100, 101, 103, 104, 107,
Instructions
192 A,B,C terminal function selection 108, 1 99 43
111 to 116, 120, 125,
126, 146, 147, 164,
190, 191, 195, 196, 198,
199, 9999
Motor
Inquiry
24
Minimum Refer
Func- Initial Customer
Parameter Name Setting Range Setting to
tion Value Setting
Increments Page
— 249 Earth (ground) fault detection at start 0, 1 1 0 44
0 to 100s,
— 250 Stop selection 1000 to 1100s, 0.1s 9999 44
8888, 9999
— 251 Output phase loss protection selection 0, 1 1 1 44
255 Life alarm status display (0 to 15) 1 0 44
Life diagnosis
199, 9999
(0 to 5), 1000 to 9998,
297 Password lock/unlock 1 9999 47
9999
— 298 Frequency search gain 0 to 32767, 9999 1 9999 39
Rotation direction detection selection
— 299 0, 1, 9999 1 0 34
at restarting
Communication operation command
RS-485 communication
338 0, 1 1 0 47
source
Communication speed command
339 0, 1, 2 1 0 47
source
340 Communication startup mode selection 0, 1, 10 1 0 38
Communication EEPROM write
342 0, 1 1 0 40
selection
343 Communication error count — 1 0 40
Second motor
constant
25
Minimum Refer
Func- Initial Customer
Parameter Name Setting Range Setting to
tion Value Setting
Increments Page
Features
495 Remote output selection 0, 1, 10, 11 1 0 48
Output
Peripheral
Devices
Stop mode selection at communication
— 502 0, 1, 2, 3 1 0 40
error
Maintenance
Specifications
Standard
Maintenance timer alarm output set
504 0 to 9998, 9999 1 9999 48
time
547 USB communication station number 0 to 31 1 0 48
Dimension
Drawings
USB
Outline
USB communication check time
548 0 to 999.8s, 9999 0.1s 9999 48
interval
549 Protocol selection 0, 1 1 0 40
Communication
Terminal Specification
Terminal Connection
NET mode operation command source
Explanation
Diagram
550 0, 2, 9999 1 9999 47
selection
PU mode operation command source
551 2 to 4, 9999 1 9999 47
selection
Operation panel
FR Configurator
Parameter unit
555 Current average time 0.1 to 1.0s 0.1s 1s 49
Current average
time monitor
Parameter
List
Rated
Current average value monitor signal
557 0 to 500A 0.01A inverter 49
output reference current
current
Explanations
Parameters
— 563 Energization time carrying-over times (0 to 65535) 1 0 33
of
— 564 Operating time carrying-over times (0 to 65535) 1 0 33
— 571 Holding time at a start 0 to 10s, 9999 0.1s 9999 29
— 611 Acceleration time at a restart 0 to 3600s, 9999 0.1s 9999 34
Protective
Functions
— 653 Speed smoothing control 0 to 200% 0.1% 0 49
Regeneration avoidance frequency
— 665 0 to 200% 0.1% 100 49
gain
— 800 Control method selection 20, 30 1 20 39
Options
0 to 500A (0 to ****) ,
— 859 Torque current 0.01A (1) ∗5 9999 39
9999 ∗5
Protective
functions
Instructions
Regeneration avoidance operation
Regeneration avoidance
882 0, 1, 2 1 0 49
selection
Regeneration avoidance operation 400VDC/
Motor
level 780VDC ∗4
Regeneration avoidance compensation
885 0 to 10Hz, 9999 0.01Hz 6Hz 49
frequency limit value
Compatibility
Warranty
26
Minimum Refer
Func- Initial Customer
Parameter Name Setting Range Setting to
tion Value Setting
Increments Page
C0
FM terminal calibration — — — 50
(900) ∗7
C2 Terminal 2 frequency setting bias
0 to 400Hz 0.01Hz 0Hz 41
(902) ∗7 frequency
C3
Terminal 2 frequency setting bias 0 to 300% 0.1% 0% 41
(902) ∗7
125 Terminal 2 frequency setting gain
0 to 400Hz 0.01Hz 60Hz 41
Calibration parameters
(903) ∗7 frequency
C4
Terminal 2 frequency setting gain 0 to 300% 0.1% 100% 41
(903) ∗7
C5 Terminal 4 frequency setting bias
0 to 400Hz 0.01Hz 0Hz 41
(904) ∗7 frequency
C6
Terminal 4 frequency setting bias 0 to 300% 0.1% 20% 41
(904) ∗7
126 Terminal 4 frequency setting gain
0 to 400Hz 0.01Hz 60Hz 41
(905) ∗7 frequency
C7
Terminal 4 frequency setting gain 0 to 300% 0.1% 100% 41
(905) ∗7
C22 Frequency setting voltage bias
0 to 400Hz 0.01Hz 0 41
(922) ∗6∗7 frequency (built-in potentiometer)
C23 Frequency setting voltage bias (built-in
0 to 300% 0.1% 0 41
(922) ∗6∗7 potentiometer)
C24 Frequency setting voltage gain
0 to 400Hz 0.01Hz 60Hz 41
(923) ∗6∗7 frequency (built-in potentiometer)
C25 Frequency setting voltage gain (built-in
0 to 300% 0.1% 100% 41
(923) ∗6∗7 potentiometer)
990 PU buzzer control 0, 1 1 1 50
PU
27
Explanations of Parameters
The abbreviations in the explanations below indicate V/F ...V/F control, AD MFVC ...advanced magnetic flux vector control,
GP MFVC ...general-purpose magnetic flux vector control. (Parameters without any indication are valid for all control)
Features
z Use Pr. 19 Base frequency voltage to set the base voltage (e.g. rated
Pr. 0, 46 motor voltage).
z This function is valid for V/F control only.
Manual torque boost V/F
Peripheral
Pr. 0 Torque boost Pr. 46 Second torque boost
Devices
You can compensate for a voltage drop in the low-frequency Pr. 19
Output frequency
region to improve motor torque reduction in the low-speed region. (Hz)
Pr. 3
z Motor torque in the low-frequency range can be adjusted to the load
Specifications
Pr. 47
Standard
to increase the starting motor torque.
z Two kinds of starting torque boost can be switched by using RT
signal. Pr. 4 to 6, 24 to 27, 232 to 239
z This function is valid for V/F control only.
Multi-speed setting operation
Dimension
Drawings
When Using
Outline
100%
the Mitsubishi Pr. 4 Multi-speed setting (high speed) Pr. 5Multi-speed setting (middle speed)
Pr. 0 Initial Value
Output voltage
Constant Pr. 6 Multi-speed setting (low speed) Pr. 24 Multi-speed setting (speed 4)
Torque Motor
Pr. 25 Multi-speed setting (speed 5) Pr. 26 Multi-speed setting (speed 6)
0.1K to Pr. 27 Multi-speed setting (speed 7) Pr. 232 Multi-speed setting (speed 8)
6% Å
Terminal Specification
Terminal Connection
0.75K
Pr. 0 Setting range Pr. 233 Multi-speed setting (speed 9) Pr. 234 Multi-speed setting (speed 10)
Explanation
1.5K to 3.7K 4% Å
Diagram
Pr. 46
Pr. 235 Multi-speed setting (speed 11) Pr. 236 Multi-speed setting (speed 12)
0 Base frequency
Output frequency (Hz)
5.5K, 7.5K 3% 2%∗ Pr. 237 Multi-speed setting (speed 13) Pr. 238 Multi-speed setting (speed 14)
11K, 15K 2% Å Pr. 239 Multi-speed setting (speed 15)
∗ If the Pr. 71 initial value is
Can be used to change the preset speed in the parameter with the
Operation panel
FR Configurator
Parameter unit
changed to the setting for use
with a constant-torque motor, contact signals.
the Pr. 0 setting changes to the
corresponding value in the
Any speed can be selected by merely turning on-off the contact
above table. signals (RH, RM, RL, REX signals).
z Operation is performed at the frequency set in Pr. 4 when the RH
Parameter
Pr. 1, 2, 18 signal turns on, Pr. 5 when the RM signal turns on, and Pr. 6 when
List
the RL signal turns on.
Maximum/minimum frequency
Pr. 1 Maximum frequency Pr. 2 Minimum frequency
Explanations
Parameters
Speed 1
Output frequency (Hz)
(High speed)
Pr. 18 High speed maximum frequency
of
Speed 2
Motor speed can be limited. (Middle speed)
z Clamp the upper and lower limits of the output frequency. Speed 3
(Low speed)
Protective
Functions
frequency in Pr. 18. Time
ON
(When Pr. 18 is set, Pr. 1 is automatically changed to the frequency RH
ON
set in Pr. 18. Also, when Pr. 1 is set, Pr. 18 is automatically changed RM
ON
RL
to the frequency set in Pr. 1.)
z Frequency from 4 speed to 15 speed can be set according to the
Options
combination of the RH, RM, RL and REX signals. Set the running
Clamped at the
Output frequency maximum frequency frequencies in Pr. 24 to Pr. 27, Pr. 232 to Pr. 239 (In the initial value
(Hz) setting, speed 4 to speed 15 are unavailable)
Instructions
Pr. 1
Pr. 18
Output frequency (Hz)
Speed 10
Frequency setting Speed 5 Speed 11
Pr. 2
Speed 6 Speed 9 Speed 12
0 5, 10V
(4mA) (20mA) Speed 4
Speed 13
Clamped at the Speed 8
Speed 14
minimum frequency
Speed 7 Speed 15
Motor
Time
Pr. 3, 19, 47
ON ON ON ON ON ON ON
RH
ON ON ON ON ON ON ON
RM
ON ON ON ON ON ON
V/F RL
ON ON ON ON ON ON ON ON
REX
Pr. 3 Base frequency Pr. 19 Base frequency voltage *1
Pr. 47 Second V/F (base frequency) ∗1 When "9999" is set in Pr. 232 Multi-speed setting (speed 8), operation is
performed at frequency set in Pr. 6 when RH, RM and RL are turned
z Used to adjust the inverter outputs (voltage, frequency) to the motor
OFF and REX is turned ON.
Warranty
rating.
z When running the standard motor, generally set the rated frequency
of the motor in Pr. 3 Base frequency. When running the motor using
electronic bypass operation, set Pr. 3 to the same value as the power
supply frequency.
Inquiry
z When you want to change the base frequency when switching two
types of motors with one inverter, use the Pr. 47 Second V/F (base
frequency).
When setting parameters, refer to the instruction manual (applied) and understand instructions. 28
Pr. 7, 8, 20, 21, 44, 45, 147 Pr. 10 to 12
Acceleration/deceleration time setting DC injection brake
Pr. 7 Acceleration time Pr. 8 Deceleration time Pr. 10 DC injection brake operation frequency Pr. 11 DC injection brake operation time
Pr. 20 Acceleration/deceleration reference frequency Pr. 21 Acceleration/deceleration time increments Pr. 12 DC injection brake operation voltage
Pr. 44 Second acceleration/deceleration time Pr. 45 Second deceleration time
The DC injection brake can be operated at a motor stop to adjust
Pr. 147 Acceleration/deceleration time switching frequency
the stop timing and braking torque.
Used to set motor acceleration/deceleration time.
When 0 is set in Pr. 11 or Pr. 12, DC injection brake is not
Set a larger value for a slower speed increase/decrease or a
performed.
smaller value for a faster speed increase/decrease.
z Use Pr. 7 Acceleration time to set the acceleration time to reach Pr. 20 When Using the
(initial
Time Range: range of table.
value) 0 to 3600s
Acceleration time Deceleration time acceleration/
Pr. 7, Pr. 44 Pr. 8, Pr. 45 Increments: deceleration
0.01s time setting
1 Range: 0 to
360s
can be
changed. Pr. 13, 571
Starting frequency
Output frequency
(Hz) Pr. 13 Starting frequency Pr. 571 Holding time at a start
You can set the starting frequency and hold the set starting
Set
frequency frequency for a certain period of time.
Pr. 147 Set these functions when you need the staring torque or want
setting
Time
smooth motor drive at a start.
Pr. 7 Pr. 44 Pr. 44 Pr. 8
(Pr. 45) Output
Acceleration time Deceleration time frequency (Hz)
60
Pr. 9, 51 Setting
range
29 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 14 Pr. 17
V/F pattern matching applications Logic selection of output stop signal (MRS)
Features
V/F Pr. 17 MRS input selection
Pr. 14 Load pattern selection The inverter output can be shut off by the MRS signal. Also, logic
for the MRS signal can be selected.
You can select the optimum output characteristic (V/F
Peripheral
When Pr. 17 is set to "4", the MRS signal from external terminal
Devices
characteristic) for the application and load characteristics.
(output stop) can be changed to the normally closed (NC contact)
This function is valid for V/F control only. input, and the MRS signal from communication can be changed to
For constant torque load the normally open (NO contact) input.
For variable torque load
Specifications
(initial value)
Standard
Setting value "0" (initial value) Setting value "2"
Pr. 14 = 0 Pr. 14 = 1 Inverter Inverter
The motor coasts to stop
Output stop Output stop
100% 100% MRS MRS
SD SD
Output voltage
Output voltage
Dimension
Drawings
Outline
Time
MRS Signal ON
Pr. 3 Base frequency Pr. 3 Base frequency
Output frequency (Hz) Output frequency (Hz) STF (STR) ON
Terminal Specification
Terminal Connection
signal
For constant torque vertical load For constant torque lift load
Explanation
Diagram
For vertical lift loads
Pr. 14 = 2
Pr. 14 = 3 Pr. 18 Refer to the section about Pr. 1.
Pr. 19
At forward rotation boost...Pr. 0 (Pr. 46) For vertical lift loads
setting
At reverse rotation boost...0%
At forward rotation boost...0%
At reverse rotation boost...Pr. 0 (Pr. 46)
Refer to the section about Pr. 3.
Operation panel
FR Configurator
Parameter unit
setting
Pr. 20, 21 Refer to the section about Pr. 7.
Output voltage
100% 100%
Output voltage
Forward Reverse
rotation rotation
Reverse Forward
Parameter
Pr. 0 rotation Pr. 0 rotation
Pr. 46 Pr. 46
Base frequency
List
Base frequency
Output frequency (Hz) Output frequency (Hz)
Pr. 15, 16
Explanations
Parameters
Jog operation
of
Pr. 15 Jog frequency Pr. 16 Jog acceleration/deceleration time
You can set the frequency and acceleration/deceleration time for
jog operation. Jog operation can be performed from either of the
Protective
Functions
external or the PU operation mode.
Can be used for conveyor positioning, test operation, etc.
Output frequency (Hz)
Options
Pr. 20
Pr. 15 Jog frequency Forward
setting range rotation
Reverse
Time
rotation
Instructions
Pr. 16
JOG signal ON
When setting parameters, refer to the instruction manual (applied) and understand instructions. 30
Pr. 22, 23, 48, 66, 156, 157, 277 Pr. 29
Stall prevention operation Acceleration/deceleration pattern
Pr. 23 Stall prevention operation level Pr. 29 Acceleration/deceleration pattern selection
Pr. 22 Stall prevention operation level
compensation factor at double speed
Pr. 66 Stall prevention operation You can set the acceleration/deceleration pattern suitable for
Pr. 48 Second stall prevention operation current
reduction starting frequency application.
Pr. 156 Stall prevention operation selection Pr. 157 OL signal output timer z Linear acceleration/deceleration (setting
Pr. 277 Stall prevention operation current switchover Setting value "0"
[Linear acceleration/ "0", initial value)
This function monitors the output current and automatically
Pr. 66 400Hz
Output frequency (Hz) Pr. 30 Pr. 70
Regeneration Unit
z Stall prevention operation and fast response current limit function Set Value Set Value
can be restricted according to the operation condition using Pr. 156. Brake resistor (MRS type, MYS type)
0
Brake unit (FR-BU2)
z When Pr. 277 = "1" , torque limit can be set. Torque limit level can be (initial ∗1
Power regeneration common converter (FR-CV)
set using Pr. 22 . value)
High power factor converter (FR-HC)
31 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 31 to 36 Pr. 40
Avoid mechanical resonance points RUN key rotation direction selection
Features
(frequency jump) Pr. 40 RUN key rotation direction selection
Pr. 31 Frequency jump 1A Pr. 32 Frequency jump 1B z Used to choose the direction of rotation by operating the RUN key of
Pr. 33 Frequency jump 2A Pr. 34 Frequency jump 2B the operation panel.
Pr. 35 Frequency jump 3A Pr. 36 Frequency jump 3B
Peripheral
Devices
Pr. 40 Setting Description
When it is desired to avoid
Set frequency (Hz) Frequency jump 0 Forward rotation
resonance attributable to Pr. 36
Pr. 35 1 Reverse rotation
the natural frequency of a
Specifications
mechanical system, these Pr. 34
Standard
Pr. 33
parameters allow
resonant frequencies to
Pr. 32
Pr. 31
Pr. 41 to 43
be jumped. Detection of output frequency (SU, FU signal)
Dimension
Pr. 41 Up-to-frequency sensitivity Pr. 42 Output frequency detection
Drawings
z Up to three areas may be set, with the jump frequencies set to either
Outline
Pr. 43 Output frequency detection for reverse
the top or bottom point of each area. rotation
z The settings of frequency jumps 1A, 2A, 3A are jump points, and
The inverter output frequency is detected and output at the output
operation is performed at these frequencies in the jump areas.
signals.
Terminal Specification
Terminal Connection
z Frequency jump is not performed if the initial value is set to "9999".
Explanation
z The Pr. 41 value can be adjusted within the range 0% ±100% on the
Diagram
z During acceleration/deceleration, the running frequency within the
assumption that the set frequency is 100%.
set area is valid.
z This parameter can be used to ensure that the running frequency
has been reached to provide the operation start signal etc. for
Operation panel
FR Configurator
Parameter unit
related equipment.
Pr. 37
Set frequency Adjustment
Speed display
Output frequency
range Pr.41
Parameter
The monitor display and frequency setting of the PU (FR-PU04/
List
FR-PU07) can be changed to the machine speed. (Hz)
Time
z To display the machine speed, set in Pr. 37 the machine speed for OFF ON OFF
SU
Explanations
60Hz operation.
Parameters
z When the output frequency rises to or above the Pr. 42 setting, the
output frequency detection signal (FU) is output. This function can
of
Output Set
Pr. 37 Frequency Parameter be used for electromagnetic brake operation, open signal, etc.
Frequency Frequency
Setting Setting Setting
Monitor Monitor z When the detection frequency is set in Pr. 43, frequency detection
0 (initial used exclusively for reverse rotation can also be set. This function is
Protective
Functions
Hz Hz Hz
value) effective for switching the timing of electromagnetic brake operation
Hz
0.01 to Machine Machine Machine
between forward rotation (rise) and reverse rotation (fall) during
9998 speed ∗1 speed ∗1 speed ∗1
vertical lift operation, etc.
∗1 Machine speed conversion formula..........Pr.37 x frequency/60Hz
∗2 Hz is displayed in 0.01Hz increments and machine speed is in 0.001.
Output frequency (Hz)
Options
Forward
rotation Pr.42 Time
Reverse Pr.43
rotation
Instructions
Output signal OFF OFF OFF
FU ON ON
When setting parameters, refer to the instruction manual (applied) and understand instructions. 32
∗4 The actual operation time is not added up if the cumulative operation
Pr. 52, 54, 170, 171, 268, 563, 564 time before power supply-off is less than 1h.
∗5 When using the parameter unit (FR-PU04/FR-PU07), "kW" is displayed.
Change of DU/PU monitor descriptions y Writing "0" in Pr. 170 clears the cumulative power monitor.
Cumulative monitor clear y You can check the numbers of cumulative energization time monitor
Pr. 52 DU/PU main display data selection Pr. 54 FM terminal function selection exceeded 65535h with Pr. 563 and the numbers of actual operation
Pr. 170 Watt-hour meter clear Pr. 171 Operation hour meter clear time monitor exceeded 65535h with Pr. 564.
Pr. 268 Monitor decimal digits selection Pr. 563 Energization time carrying-over times
y Writing "0" in Pr. 171 clears the actual operation time monitor.
Pr. 564 Operating time carrying-over times
The monitor to be displayed on the main screen of the control Pr. 268
panel and parameter unit (FR-PU04/FR-PU07) can be selected. Description
Setting
9999
Pr. 52 Setting
Pr. 54 No function
Types of (FM) Full-scale (initial value)
Unit Operation PU Main
Monitor Set Value For the first or second decimal places (0.1 increments or
Panel LED Monitor Value
0.01 increments) of the monitor, numbers in the first
Output frequency 0.01Hz 0/100 1 Pr. 55 0 decimal place and smaller are rounded to display an
Output current 0.01A 0/100 2 Pr. 56 integral value (1 increments).
100V, 200V class: The monitor value smaller than 0.99 is displayed as 0.
Output voltage 0.1V 0/100 3 400V When 2 decimal places (0.01 increments) are monitored,
400V class: 800V the 0.01 decimal place is dropped and the monitor
Fault or alarm 1 displays the first decimal place (0.1 increments).
— 0/100 — —
indication When the monitor display digit is originally in 1
Frequency increments, it is displayed unchanged in 1 increments.
0.01Hz 5 ∗1 5 Pr. 55
setting value
Rated torque of the y When Pr. 52 is set to "100", the set frequency monitor is displayed
Motor torque ∗2 0.1% 7 ∗1 7
applied motor × 2 during a stop and the output frequency monitor is displayed during
100V, 200V class:
Converter operation. (LED of Hz flickers during stop and is lit during operation.)
0.1V 8 ∗1 8 400V
output voltage
400V class: 800V
Regenerative Brake duty set in Pr. Pr. 52
0.1% 9 ∗1 9
brake duty 30 and Pr. 70
0 100
Electronic Electronic thermal
thermal O/L 0.1% 10 ∗1 10 relay function During During
relay load factor operation level During stop
running/stop running
Output current
0.01A 11 ∗1 11 Pr. 56 Output Output Set frequency Output
peak value
Converter 100V, 200V class: frequency frequency ∗ frequency
output voltage 0.1V 12 ∗1 12 400V
peak value 400V class: 800V Output current Output current
33 When setting parameters, refer to the instruction manual (applied) and understand instructions.
z When Pr. 162 = "1" (initial value) or "11", automatic restart operation
Pr. 30, 57, 58, 162, 165, 299, 611 is performed in a reduced voltage system, where the voltage is
gradually risen with the output frequency unchanged from prior to an
Automatic restart operation after
Features
instantaneous power failure independently of the coasting speed of
instantaneous power failure/flying start the motor.
Pr. 30 Regenerative function selection Pr. 57 Restart coasting time Instantaneous (power failure) time
Pr. 162 Automatic restart after
Pr. 58 Restart cushion time
instantaneous power failure selection Power supply
Peripheral
Devices
Pr. 299 Rotation direction detection (R/L1, S/L2, T/L3)
Pr. 165 Stall prevention operation level for restart
selection at restarting
Pr. 611 Acceleration time at a restart Motor speed N
(r/min)
You can restart the inverter without stopping the motor in the
Specifications
following cases: Inverter output
Standard
*
frequency f (Hz)
y When power comes back on after an instantaneous power failure
y When motor is coasting at start Inverter output
voltage E (V)
Pr. Setting
Dimension
Description
Drawings
Outline
Number Range Coasting time
0 (initial value), When MRS (X10) turns ON then OFF Pr. 57 setting Restart cushion time
(Pr. 58 setting)
1 The motor starts at the starting frequency
30 * The output shut off timing differs according to the load condition.
When MRS (X10) turns ON then OFF
Terminal Specification
Terminal Connection
2
Explanation
Automatic restart operation z When "0" or "10" is set in Pr. 162, the inverter smoothly starts after
Diagram
1.5K or less ......... 1s, detecting the motor speed upon power restoration. (The motor
2.2K to 7.5K ........ 2s, capacity should be equal to or one rank lower than the inverter
0
11K or more ........ 3s capacity)
Operation panel
FR Configurator
Parameter unit
The above times are coasting time. When using the frequency search, perform offline auto tuning.
57
Set the waiting time for inverter-triggered Also be noted that there is a wiring length limit. (Refer to page 65)
0.1 to 5s
restart after an instantaneous power failure. z Even when the motor is rotating in the opposite direction, the
9999 inverter can be restarted smoothly as the direction of rotation is
No restart
Parameter
(initial value) detected. (You can select whether to make rotation direction
List
58 0 to 60s Set a voltage starting time at restart. detection or not with Pr. 299 Rotation direction detection selection at
0 With frequency search restarting.)
Without frequency search
1 (initial value) Instantaneous (power failure) time
Explanations
Parameters
162 (reduced voltage system)
Power supply
10 Frequency search at every start
of
(R/L1, S/L2, T/L3)
165 0 to 200% 100% and sets the stall prevention Inverter output *
Protective
Functions
frequency f (Hz)
operation level during restart operation.
0 (initial value) Without rotation direction detection Inverter output
voltage E (V)
1 With rotation direction detection Restart cushion time
When Pr. 78 = 0, the rotation direction is Coasting time Speed (Pr. 58 setting)
299 (Pr. 57 )
+
Options
detection time
detected.
9999
When Pr. 78 = 1, 2, the rotation direction is * The output shut off timing differs Acceleration time
according to the load condition. at a restart
not detected. (Pr. 611 setting)
Acceleration time to reach Pr. 20 z Restart operation after turning MRS (X10) signal ON then OFF can
Instructions
0 to 3600s Acceleration/deceleration reference frequency be selected using Pr. 30. Set when restart operation after
611 at a restart. instantaneous power failure is selected while using the high power
9999 Acceleration time for restart is the normal factor converter (FR-HC).
(initial value) acceleration time (e.g. Pr. 7).
Motor
Compatibility
Warranty
Inquiry
When setting parameters, refer to the instruction manual (applied) and understand instructions. 34
Pr. 59 Pr. 61 to 63, 292, 293
Remote setting function Automatic acceleration/deceleration
Pr. 59 Remote function selection Pr. 61 Reference current Pr. 62 Reference value at acceleration
Pr. 63 Reference value at deceleration Pr. 292 Automatic acceleration/deceleration
z If the operation panel is located away from the enclosure, you can
Pr. 293 Acceleration/deceleration separate selection
use contact signals to perform continuous variable-speed operation,
without using analog signals. The inverter automatically sets appropriate parameters for
z By merely setting this parameter, you can use the acceleration, operation.
deceleration and setting clear functions of the motorized speed z The inverter operates in the same conditions as when appropriate
setter (FR-FK). values are set in each parameter even if acceleration/deceleration
time and V/F pattern are not set. This operation mode is useful when
Description you just want to operate, etc. without fine parameter setting.
Pr. 59 Setting RH, RM, RL signal Frequency setting z If the automatic acceleration/deceleration has been selected,
function storage function inputting the jog or RT (second function selection) signal during an
0 (initial value) Multi-speed setting — inverter stop will switch to the normal operation and give priority to
1 Remote setting With JOG operation or second function selection.
2 Remote setting Not used After automatic acceleration/deceleration operation has been
Not used started, none of JOG signal and RT signal are accepted.
3 Remote setting (Turning off STF/STR clears
remotely set frequency)
Automatic
Pr. 292
Operation Setting
Setting
Output frequency (Hz)
35 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 65, 67 to 69 Pr. 71, 450
Retry function at fault occurrence Motor selection (applied motor)
Features
Pr. 65 Retry selection Pr. 67 Number of retries at fault occurrence Pr. 71 Applied motor Pr. 450 Second applied motor
Pr. 68 Retry waiting time Pr. 69 Retry count display erase
Setting of the used motor selects the thermal characteristic
If a fault occurs, the inverter resets itself automatically to restart. appropriate for the motor.
You can also select the fault description for a retry.
Peripheral
Setting is required to use a constant-torque motor. Thermal
Devices
When you have selected automatic restart after instantaneous characteristic of the electronic thermal relay function suitable for
power failure (Pr. 57 Restart coasting time ≠ 9999), restart operation the motor is set.
is performed at the retry operation time which is the same of that of
Specifications
Pr. 71, Pr. 450
a power failure. Thermal Characteristic of
Standard
Motor ({: Motor used)
Setting
z Use Pr. 65 to select the fault to be activated for retries. the Electronic Thermal
Relay Function Standard Constant-torque
Pr. 71 Pr. 450 (SF-JR, etc.) (SF-JRCA, etc.)
"z" indicates the alarms selected for retry.
Fault Display Pr. 65 Setting Thermal characteristics of a standard
0 {
motor (Pr. 71 initial value)
Dimension
for Retry 0 1 2 3 4 5
Drawings
Thermal characteristics of the
Outline
E.OC1 z z z z z 1 {
Mitsubishi constant-torque motor
E.OC2 z z z z Thermal characteristic of Mitsubishi
40 — { ∗1
E.OC3 z z z z z high efficiency motor SF-HR
E.OV1 z z z z Thermal characteristic of Mitsubishi
50 — { ∗2
Terminal Specification
Terminal Connection
E.OV2 z z z z constant torque motor SF-HRCA
Explanation
Diagram
E.OV3 z z z z 3 — Standard {
E.THM z 13 — Constant-torque {
E.THT z Mitsubishi standard
E. BE z z 23 — motor SF-JR4P Select "Offline {
Operation panel
FR Configurator
(1.5kW or less) auto tuning
Parameter unit
E. GF z z
Mitsubishi high setting"
E.OHT z 43 — { ∗1
efficiency SF-HR
E.OLT z z
Mitsubishi constant-
E.OP1 z z 53 — { ∗2
torque SF-HRCA
E. PE z z
4 — Standard {
E.MB4 z z
Parameter
14 — Constant-torque {
E.MB5 z z
List
Mitsubishi standard
E.MB6 z z Auto tuning
24 — motor SF-JR4P
data can be {
E.MB7 z z (1.5kW or less)
E.USB z z read, changed,
Mitsubishi high and set.
44 — { ∗1
Explanations
E.ILF z z
Parameters
efficiency SF-HR
Mitsubishi constant-
54 — { ∗2
of
z Set the number of retries at fault occurrence in Pr. 67. torque SF-HRCA
5 — Standard∗3 {
Pr. 67 Setting Description Direct input of
15 — Constant-torque ∗3 motor {
0 (initial value) No retry function constants is
6 — Standard ∗4 {
Protective
Functions
Set the number of retries at fault occurrence. enabled
1 to 10 16 — Constant-torque ∗4 {
A fault output is not provided during retry operation.
— 9999 Without second applied motor (Pr. 450 initial value)
Set the number of retries at fault occurrence.
(The setting value of minus 100 is the number of ∗1 Motor constants of Mitsubishi high efficiency motor SF-HR
101 to 110 ∗2 Motor constants of Mitsubishi constant-torque motor SF-HRCA.
retries.)
A fault output is provided during retry operation. ∗3 Star connection
Options
∗4 Delta connection
z Use Pr. 68 to set the waiting time from when the inverter trips until a z For the 5.5K and 7.5K, the Pr. 0 Torque boost and Pr. 12 DC injection
retry is made in the range 0 to 10s. (When the setting value is "0s", brake operation voltage settings are automatically changed according
the actual time is 0.1s.) to the Pr. 71 settings as follows.
Instructions
z Reading the Pr. 69 value provides the cumulative number of
successful restart times made by retry. (Use setting value "0" to
Automatic Change Standard Motor Constant-torque
Parameter Setting ∗1 Motor Setting ∗2
clear.)
Pr. 0 3% 2%
Pr. 12 4% 2%
Pr. 66 Refer to the section about Pr. 22.
∗1 Pr. 71 setting: 0, 3 to 6, 23, 24, 40, 43, 44
Motor
Pr. 67 to 69 Refer to the section about Pr. 65. ∗2 Pr. 71 setting: 1, 13 to 16, 50, 53, 54
setting is in [kHz].
72 0 to 15
Note that 0 indicates 0.7kHz and 15 indicates
14.5kHz.
0 Soft-PWM is invalid
240
1 When Pr. 72 = "0 to 5", Soft-PWM is valid.
When setting parameters, refer to the instruction manual (applied) and understand instructions. 36
Pr. 73, 267 Pr. 75
Analog input selection Reset selection, disconnected PU
Pr. 73 Analog input selection Pr. 267 Terminal 4 input selection detection
z You can select the function that switches between forward rotation Pr. 75 Reset selection/disconnected PU
and reverse rotation according to the analog input terminal detection/PU stop selection
specifications and analog input level. You can select the reset input acceptance, disconnected PU (FR-
z Either voltage input (0 to 5V, 0 to 10V) or current input (4 to 20mA) PU04/FR-PU07) connector detection function and PU stop
can be selected for terminals 4 used for analog input. function.
Set the voltage/current input switch in the "V" position to select
voltage input (0 to 5V/0 to10V) and "I" position to select current input Pr. 75 Disconnected PU Stop
Reset Selection
(4 to 20mA), and change the parameter setting (Pr. 267). Setting PU Detection Selection
( indicates main speed setting) Reset input normally If the PU is
0
enabled disconnected,
Reset input is enabled operation will be Pressing
Pr. 73 Terminal 2 Reversible 1
Terminal 4 Input only when a fault occurs. continued.
Setting Input Operation decelerates the
0 0 to 10V Reset input normally When the PU is motor to a stop
2
1 Not function enabled disconnected, only in the PU
0 to 5V When the AU signal is off operation mode.
(initial value) Reset input is enabled the inverter
× 3
10 0 to 10V only when a fault occurs. output is shut off.
Yes
11 0 to 5V 14
Reset input normally If the PU is
0 When the AU signal is on (initial
enabled disconnected, Pressing
1 × According to Pr. 267 setting Not function value)
operation will be decelerates the
(initial value) 0:4 to 20mA (initial value) Reset input is enabled
15 continued. motor to a stop in
10 only when a fault occurs.
1:0 to 5V any of the PU,
× Yes Reset input normally When the PU is
11 2:0 to 10V 16 external and
enabled disconnected, communication
Reverse Forward Reset input is enabled the inverter operation modes.
Set frequency (Hz)
17
rotation rotation only when a fault occurs. output is shut off.
Pr. 125
Reversible
z Reset selection
You can select the operation timing of reset function (RES signal,
Not
reversible
reset command through communication) input.
z Disconnected PU detection
C2(Pr. 902) Terminal 2
0 2.5V 5V input (V) This function detects that the PU (FR-PU04/FR-PU07) has been
C3(Pr.902) C4(Pr.903) disconnected from the inverter for longer than 1s and causes the
Frequency setting signal inverter to provide a fault output (E.PUE) and come to trip.
z PU stop selection
In any of the PU operation, external operation and network operation
Pr. 74 modes, the motor can be stopped by pressing of the PU.
Pr. 78
Prevention of reverse rotation of the
motor
Pr. 78 Reverse rotation prevention selection
This function can prevent reverse rotation fault resulting from the
incorrect input of the start signal.
Pr. 78 Setting Description
0 (initial value) Both forward and reverse rotations allowed
1 Reverse rotation disabled
2 Forward rotation disallowed
37 When setting parameters, refer to the instruction manual (applied) and understand instructions.
z Specify the operation mode at power on (Pr. 340)
Pr. 79, 340 y When power is switched on or when power comes back on after
instantaneous power failure, the inverter can be started up in the
Operation mode selection network operation mode.
Features
Pr. 79 Operation mode selection Pr. 340 Communication startup mode selection After the inverter has started up in the network operation mode,
z Used to select the operation mode of the inverter. parameter write and operation can be performed from a program.
Mode can be changed as desired between operation using external Set this mode for communication operation using the inverter RS-
485 communication or communication option.
Peripheral
signals (external operation), operation from the PU (FR-PU04/FR-
Devices
PU07), combined operation of PU operation and external operation y You can set the operation mode at power on (reset) according to
the Pr. 79 and Pr. 340 settings.
(external/PU combined operation, and network operation (when RS-
485 communication or a communication option is used) Operation Mode at
Specifications
.
Pr. 340 Pr. 79 Power-on, Power Operation Mode
Standard
Pr. 79 LED Indication Setting Setting Restoration, Switching
Description : OFF Reset
Setting : ON
0
Use external/PU switchover mode External
operation mode (initial As set in Pr. 79.
Dimension
Drawings
value)
Outline
0 (press to switch between the PU and
(initial Can be switched to
external operation mode. PU operation
value) 0 NET operation mode external, PU or NET
At power on, the inverter is placed in the mode
operation mode∗1
Terminal Specification
external operation mode.
Terminal Connection
Fixed to PU operation
Explanation
1 PU operation mode
Diagram
mode
1 Fixed to PU operation mode
Switching between the
External external and NET
operation mode is
Operation panel
FR Configurator
operation mode
Parameter unit
Fixed to external operation mode 2 NET operation mode
enabled
Operation can be performed by switching
2 Switching to PU
between the external and Net operation NET operation
mode operation mode disabled
mode.
External/PU combined Operation mode
1 3, 4
Parameter
operation mode switching disabled
External/PU combined operation mode 1
List
Switching among the
Frequency command Start command
external, PU, and NET
Operation panel and 6 NET operation mode
operation mode is
PU (FR-PU04/FR-
Explanations
External signal
Parameters
PU07) setting or enabled while running.
3
external signal input input Can be switched to
of
(multi-speed setting, X12 (MRS) signal ON
(terminal STF, external, PU or NET
across terminals 4-5 .. NET operation mode
STR) operation mode∗1
(valid when AU signal
turns on)). 7 Fixed to external
X12 (MRS) signal ON
Protective
Functions
External/PU combined operation mode 2 operation mode (forcibly
.. External operation
Frequency command Start command switched to external
mode
Input from the operation mode)
External signal input operation panel Switching between the
4
(terminal 2, 4, JOG, and the PU (FR- 0 NET operation mode PU and Net operation
Options
multi-speed selection, PU04/FR-PU07)
mode is enabled∗2
etc.) Fixed to PU operation
( ) 1 PU operation mode
mode
PU operation
mode Fixed to NET operation
Instructions
2 NET operation mode
mode
Switchover mode External/PU
External Operation mode
Switch among PU operation, external operation mode 3, 4 combined operation
6 10 switching disabled
operation, and NET operation while mode
keeping the same operating status. Switching between the
Motor
NET operation
PU and NET operation
mode 6 NET operation mode
mode is enabled while
running∗2
External operation mode (PU operation PU operation Fixed to external
Compatibility
interlock) mode
X12 signal ON External operation operation mode (forcibly
7
Operation mode can be switched to the mode switched to external
7 PU operation mode.
External operation mode)
(output stop during external operation)
X12 signal OFF operation mode ∗1 Operation mode can not be directly changed between the PU
Warranty
Operation mode can not be switched to operation mode and network operation mode
the PU operation mode. ∗2 Operation mode can be changed between the PU operation mode and
network operation mode with key of the operation panel and X65
signal.
Inquiry
When setting parameters, refer to the instruction manual (applied) and understand instructions. 38
Pr. 80, 81, 89, 800 Pr. 82 to 84, 90 to 94, 96, 298, 859
Selection of control method and control Offline auto tuning
mode AD MFVC GP MFVC Pr. 82 Motor excitation current
Pr. 84 Rated motor frequency
Pr. 83 Rated motor voltage
Pr. 90 Motor constant (R1)
Pr. 80 Motor capacity Pr. 81 Number of motor poles Pr. 91 Motor constant (R2) Pr. 92 Motor constant (L1)
Pr. 89 Speed control gain (Advanced magnetic flux Pr. 93 Motor constant (L2) Pr. 94 Motor constant (X)
Pr. 800 Control method selection
vector) Pr. 96 Auto tuning setting/status Pr. 298 Frequency search gain
Advanced magnetic flux vector control and general-purpose Pr. 859 Torque current
magnetic flux vector control can be selected by setting the motor Offline auto tuning operation for automatic calculation of motor
capacity, number of poles in Pr. 80 and Pr. 81. Selection of constants can be executed when using advanced magnetic flux
advanced magnetic flux vector control or general-purpose vector control and general-purpose magnetic flux vector control.
magnetic flux vector control can be made by Pr. 800. When offline auto tuning is performed under V/F control, Pr. 298
Frequency search gain necessary for frequency search for automatic
Parameter Setting
Description restart after instantaneous power failure is set as well as the motor
Number Range
constants (R1).
0.1 to 15kW Set the applied motor capacity.
80 9999 Parameter Setting
V/F control Description
(initial value) Number Range
2, 4, 6, 8, 10 Set the number of motor poles. 0
81 9999 (initial Without offline auto tuning
V/F control
(initial value) value)
20 Offline auto tuning for advanced magnetic
Advanced magnetic flux vector control ∗ 1
(initial value) flux vector control
800
General-purpose magnetic flux vector 96 Offline auto tuning for general-purpose
30
control ∗ 11 magnetic flux vector control
∗ Set a value other than "9999" in Pr. 80 and Pr. 81. (compatible with FR-E500 series)
z The motor speed fluctuation at load fluctuation can be adjusted Offline auto tuning for V/F control
using Pr. 89. 21 (automatic restart after instantaneous power
failure (with frequency search))
z You can copy the offline auto tuning data (motor constants) to
another inverter with the PU (FR-PU07).
z Even when motors (other manufacturer's motor, SF-JRC, etc.) other
than Mitsubishi standard motor (SF-JR SF-HR 0.2kW or more) and
Mitsubishi constant-torque motor (SF-JRCA 4P SF-HRCA 0.2kW to
15kW) are used or the wiring length is long, using the offline auto
tuning function runs the motor with the optimum operating
characteristics.
z Offline auto tuning conditions
y A motor should be connected.
y The motor capacity is equal to or one rank lower than the inverter
capacity.
(note that the capacity should be 0.1kW or more)
y The maximum frequency is 120Hz.
y A high-slip motor, high-speed motor and special motor cannot be
tuned.
z As the motor may run slightly, fix the motor securely with a
mechanical brake or make sure that there will be no problem in
safety if the motor runs.
* This instruction must be followed especially in elevator.
Note that if the motor runs slightly, tuning performance is unaffected.
39 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. Setting
Pr. 117 to 124, 342, 343, 502, 549 Number Range
Description
Features
occurrence output removal
Pr. 117 PU communication station number Pr. 118 PU communication speed 0 (initial
Pr. 119 PU communication stop bit length Pr. 120 PU communication parity check Coasts to Stop
value) E.PUE Output
Pr. 121 Number of PU communication stop. (E.PUE)
Pr. 122 PU communication check time interval 3
retries 502
Pr. 123 PU communication waiting time setting Pr. 124 PU communication CR/LF selection Decelerates After stop Output
Stop
Peripheral
1
Devices
Pr. 342 Communication EEPROM write selection Pr. 343 Communication error count to stop E.PUE after stop
(E.PUE)
Pr. 502 Stop mode selection at communication error Pr. 549 Protocol selection Automatic
Decelerates After stop Without
2 restart
(1) Initial settings and specifications of RS-485 to stop E.PUE output
functions
Specifications
communication (Pr. 117 to Pr. 124) ∗1 When making communication through Modbus-RTU protocol (Pr. 549 =
Standard
Used to perform required settings for RS-485 communication "1"), the setting range within parenthesis is applied.
between the inverter and personal computer.
z Use PU connector of the inverter for communication. (2) Communication EEPROM write selection (Pr. 342)
z You can perform parameter setting, monitoring, etc. using When parameter write is performed from the inverter PU
Dimension
Drawings
Outline
the Mitsubishi inverter protocol or Modbus-RTU protocol. connector, USB communication, and communication option,
z To make communication between the personal computer parameters storage device can be changed from EEPROM +
and inverter, initialization of the communication RAM to RAM only. Set when a frequent parameter change is
Terminal Specification
Terminal Connection
specifications must be made to the inverter. necessary.
Explanation
Diagram
Data communication cannot be made if the initial settings
are not made or there is any setting error.
(3) Modbus-RTU communication specifications (Pr.
Pr. Setting 343, Pr. 549)
Operation panel
FR Configurator
Parameter unit
Description
Number Range
Pr. Setting
Specify the inverter station number. Description
0 to 31 Number Range
Set the inverter station numbers when two or
117 (0 to 247)
more inverters are connected to one personal Displays the number of communication
∗1 343 — errors during Modbus-RTU communication.
computer.
Parameter
(Reading only)
Set the communication speed.
List
The setting value × 100 equals the 0 (initial Mitsubishi inverter (computer link
48, 96,
118 communication speed. 549 value) operation) protocol
192, 384
For example, the communication speed is 1 Modbus-RTU protocol
Explanations
Parameters
19200bps when the setting value is 192.
Stop bit length Data length
of
0 1bit
1 (initial 8bit
119 2bit
value)
Protective
Functions
10 1bit
7bit
11 2bit
0 Without parity check
1 With odd parity check
120
2 (initial
With even parity check
Options
value)
Set the permissible number of retries at
occurrence of a data receive error. If the number
0 to 10
of consecutive errors exceeds the permissible
121
value, the inverter will come to trip.
Instructions
If a communication error occurs, the inverter will
9999
not come to trip.
RS-485 communication can be made
0 (initial Note that a communication error (E.PUE) occurs
value) as soon as the inverter is switched to the
operation mode with control source.
Motor
value)
0 Without CR/LF
1 (initial
124 With CR
value)
2 With CR/LF
Inquiry
When setting parameters, refer to the instruction manual (applied) and understand instructions. 40
Pr. 125, 126, 241, C2 (902) to C7 (905), C22 (922) to C25 (923) Pr. 127 to 134
Analog input frequency change and PID control, dancer control
adjustment (calibration) Pr. 127 PID control automatic switchover frequency Pr. 128 PID action selection
Pr. 129 PID proportional band Pr. 130 PID integral time
Pr. 125 Terminal 2 frequency setting gain frequency Pr. 126 Terminal 4 frequency setting gain frequency
Pr. 131 PID upper limit Pr. 132 PID lower limit
Pr. 241 Analog input display unit switchover C2 (Pr. 902) Terminal 2 frequency setting bias frequency
Pr. 133 PID action set point Pr. 134 PID differential time
C3 (Pr. 902) Terminal 2 frequency setting bias C4 (Pr. 903) Terminal 2 frequency setting gain
C5(Pr. 904) Terminal 4 frequency setting bias frequency C6 (Pr. 904) Terminal 4 frequency setting bias z The inverter can be used to exercise process control, e.g. flow rate,
C22 (Pr. 922) Frequency setting air volume or pressure.
C7 (Pr. 905) Terminal 4 frequency setting gain voltage bias frequency (built-in
The terminal 2 input signal or parameter setting is used as a set
potentiometer)
C23 (Pr. 922) Frequency setting C24 (Pr. 923) Frequency setting voltage point and the terminal 4 input signal used as a feedback value to
voltage bias (built-in potentiometer) gain frequency (built-in potentiometer) constitute a feedback system for PID control.
C25 (Pr. 923) Frequency setting
voltage gain (built-in potentiometer) y Pr. 128 = "20, 21" (measured value input)
You can set the magnitude (slope) of the output frequency as desired Inverter circuit
Pr. 133 Manipulated Motor
in relation to the frequency setting signal (0 to 5VDC, 0 to 10V or 4 to or terminal 2
PID operation
variable
+- 1 IM
20mA). Set point Kp 1+
Ti S
+Td S
0 to 5VDC
C22 (Pr. 922) to C25 (Pr. 923) is available when the operation panel (0 to 10VDC) Terminal 4
Feedback signal (measured value) 4 to 20mADC (0 to 5V, 0 to 10V)
(PA02) for the FR-E500 series is connected with cable. You can
Kp: Proportionality constant Ti: Integral time S: Operator Td: Differential time
calibrate the operation panel built-in potentiometer.
z Performs PID control by feedbacking the position signal of the
(1) Change the frequency at maximum analog input dancer roller, controlling the dancer roller is in the specified position.
(Pr. 125, Pr. 126) Performs dancer control by setting 40 to 43 in Pr. 128 PID action
Set Pr. 125 (Pr. 126) when changing only frequency setting selection. The main speed command is the speed command of each
(gain) of the maximum analog input voltage (current). (Other operation mode (external, PU, communication). Performs PID
calibration parameter settings need not be changed.) control by the position detection signal of the dancer roller, then the
result is added to the main speed command.
(2) Analog input bias/gain calibration
(C2 (Pr. 902) to C7 (Pr. 905))
y The "bias" and "gain" functions are designed to adjust the
relationships between the output frequency and the setting
Pr. 145
input signal, e.g. 0 to 5VDC/0 to 10VDC or 4 to 20mADC Parameter unit display language
entered from outside the inverter. selection
Pr. 145 PU display language selection
Output frequency (Hz)
Initial value
60Hz
You can switch the display language of the parameter unit (FR-
PU04/FR-PU07) to another.
Gain
Pr. 145 Setting Description
Pr. 125
Bias
0 (initial value) Japanese
C2(Pr. 902) 1 English
0 100% 2 German
0
Frequency setting signal
5V 3 French
0 10V
C3(Pr. 902) C4(Pr. 903) 4 Spanish
5 Italian
Output frequency (Hz)
Initial value
6 Swedish
60Hz 7 Finnish
41 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 150 to 153 Pr. 160, 172 to 174
Detection of output current (Y12 signal) User group function
Features
Detection of zero current (Y13 signal) Pr. 160 User group read selection Pr. 172 User group registered display/batch clear
Pr. 173 User group registration Pr. 174 User group clear
Pr. 150 Output current detection level Pr. 151 Output current detection signal delay time
Pr. 152 Zero current detection level Pr. 153 Zero current detection time z Parameter which can be read from the operation panel and
parameter unit can be restricted.
Peripheral
The output power during inverter running can be detected and
Devices
output to the output terminal. The inverter is set to display all parameters with initial setting.
Specifications
Standard
0
y The output current detection function can be used for
(initial All parameters are displayed.
excessive torque detection, etc.
value)
y If the output current remains higher than the Pr. 150 setting
1 Only the parameters registered in the user group can be displayed.
during inverter operation for longer than the time set in Pr.
Dimension
9999 Only the simple mode parameters can be displayed.
Drawings
Outline
151, the output current detection signal (Y12) is output
from the inverter's open collector or relay output terminal. z User group function (Pr. 160, Pr. 172 to Pr. 174)
y The user group function is designed to display only the
Terminal Specification
parameters necessary for setting.
Terminal Connection
Explanation
Diagram
y From among all parameters, a maximum of 16 parameters can
Pr. 150 be registered in the user group. When "1" is set in Pr. 160 , only
parameters registered in the user group can be accessed for
Output current
Operation panel
FR Configurator
Parameter unit
Pr. 151 reading and writing. (The parameters not registered in the user
group can not be read.)
Time y Set parameter numbers in Pr. 173 to register parameters in
100ms the user group.
Parameter
Output current
detection signal
OFF ON OFF y To delete a parameter from the user group, set its parameter
List
(Y12) number in Pr. 174. To batch-delete the registered parameters,
(2) Zero current detection (Y13 signal, Pr. 152, Pr. 153) set Pr. 172 to "9999".
y If the output current remains lower than the Pr. 152 setting
Explanations
Parameters
during inverter operation for longer than the time set in Pr.
Pr. 161, 295
of
153, the zero current detection (Y13) signal is output from
the inverter's open collector or relay output terminal.
Operation selection of the operation
panel
Protective
Functions
Pr. 161 Frequency setting/key lock operation
Output current
Options
Pr. 152
Pr. 152
0[A]
100ms* Time
z The key operation of the operation panel can be disabled.
OFF ON
Start signal
Pr. 161 Setting Description
Zero current
detection time OFF ON OFF ON 0 (initial value) Setting dial frequency setting mode
Instructions
(Y13) Key lock invalid
Pr. 153 Pr. 153 1 Setting dial potentiometer mode
Detection time Detection time
10 Setting dial frequency setting mode
Key lock valid
11 Setting dial potentiometer mode
Pr. 156, 157 Refer to the section about Pr. 22. z When setting the set frequency with the setting dial, the
frequency setting increments of the setting dial can be changed,
Motor
When setting parameters, refer to the instruction manual (applied) and understand instructions. 42
Pr. 178 to 184 Pr. 190 to 192
Function assignment of input terminal Terminal assignment of output terminal
Pr. 178 STF terminal function selection Pr. 179 STR terminal function selection Pr. 190 RUN terminal function selection Pr. 191 FU terminal function selection
Pr. 180 RL terminal function selection Pr. 181 RM terminal function selection Pr. 192 A,B,C terminal function selection
Pr. 182 RH terminal function selection Pr. 183 MRS terminal function selection
You can change the functions of the open collector output terminal
Pr. 184 RES terminal function selection
and relay output terminal.
Use these parameters to select/change the input terminal
Pr. 190 to Pr. 192
functions. Setting
Signal Functions
Pr. 178 to Positive Negative
Pr. 184 Signal Functions logic logic
Setting 0 100 RUN Inverter running
Pr. 59 = 0 (initial Low-speed operation 1 101 SU Up to frequency
value) command 3 103 OL Overload alarm
4 104 FU Output frequency detection
Remote setting (setting
0 RL Pr. 59 = 1, 2 *1 7 107 RBP Regenerative brake prealarm
clear)
8 108 THP Electronic thermal relay function prealarm
Stop-on contact selection
Pr. 270 = 1 *2 11 111 RY Inverter operation ready
0
12 112 Y12 Output current detection
Pr. 59 = 0 (initial Middle-speed operation 13 113 Y13 Zero current detection
value) command 14 114 FDN PID lower limit
1 RM
Remote setting 15 115 FUP PID upper limit
Pr. 59 = 1, 2 *1
(deceleration) 16 116 RL PID forward/reverse rotation output
Pr. 59 = 0 (initial High-speed operation 20 120 BOF Brake opening request
value) command 25 125 FAN Fan fault output
2 RH
Remote setting 26 126 FIN Heatsink overheat pre-alarm
Pr. 59 = 1, 2 *1 During deceleration due to instantaneous
(acceleration) 46 146 Y46
Second function selection power failure (retained until release)
3 RT 47 147 PID During PID control activated
Pr. 270 = 1 *2 Stop-on contact selection 1
4 AU Terminal 4 input selection 64 164 Y64 During retry
5 JOG Jog operation selection 90 190 Y90 Life alarm
91 191 Y91 Fault output 3 (power-off signal)
7 OH External thermal relay input*3
93 193 Y93 Current average value monitor signal
15-speed selection
8 REX 95 195 Y95 Maintenance timer signal
(combination with three speeds RL, RM, RH)
96 196 REM Remote output
Inverter operation enable signal
10 X10 98 198 LF Alarm output
(FR-HC/FR-CV connection) 99 199 ALM Fault output
12 X12 PU operation external interlock 9999 — No function
14 X14 PID control valid terminal
15 BRI Brake opening completion signal Pr. 232 to 239 Refer to the section about Pr. 4.
16 X16 PU-external operation switchover
18 X18
V/F switchover Pr. 240 Refer to the section about Pr. 72.
(V/F control is exercised when X18 is on)
24 MRS Output stop Pr. 241 Refer to the section about Pr. 125.
25 STOP Start self-holding selection
Forward rotation command
60 STF
(assigned to STF terminal (Pr. 178) only) Pr. 244
Reverse rotation command
61 STR
(assigned to STR terminal (Pr. 179) only) Increase cooling fan life
62 RES Inverter reset Pr. 244 Cooling fan operation selection
65 X65 PU/NET operation switchover You can control the operation of the cooling fan (FR-E720-1.5K or
66 X66 External/NET operation switchover
more, FR-E740-1.5K or more, FR-E720S-0.75K or more) built in
67 X67 Command source switchover
the inverter.
9999 — No function
Pr. 244 Setting Description
∗1 When Pr. 59 Remote function selection = "1 or 2", the functions of the RL,
RM and RH signals change as listed above. Operates in power-on status.
∗2 When Pr. 270 = "1", the functions of the RL and RT signals change as 0 Cooling fan on/off control invalid
listed above. (the cooling fan is always on at power on)
∗3 The OH signal turns on when the relay contact "opens".
Cooling fan on/off control valid
1 The fan is always on while the inverter is running.
(initial value) During a stop, the inverter status is monitored and
the fan switches on-off according to the temperature.
Pr. 245 Rated slip Pr. 246 Slip compensation time constant
Pr. 247 Constant-power range slip
compensation selection
The inverter output current may be used to assume motor slip to
keep the motor speed constant.
43 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 249 Pr. 251, 872
Earth (ground) fault detection at start Input/output phase failure protection
Features
Pr. 249 Earth (ground) fault detection at start selection
You can choose whether to make earth (ground) fault detection at Pr. 251 Output phase loss protection selection Pr. 872 Input phase loss protection selection
start valid or invalid. Earth (ground) fault detection is executed only You can disable the output phase failure protection function that
Peripheral
right after the start signal is input to the inverter.
Devices
stops the inverter output if one of the inverter output side (load
side) three phases (U, V, W) opens.
Pr. 249 Setting Description
Input phase failure protection, which stops inverter output when
0 (initial value) Without earth (ground) fault detection
one of three phases (R, S, T) on the inverter's input side is lost,
Specifications
1 With earth (ground) fault detection*
Standard
can be disabled.
∗ As detection is executed at starting, output is delayed for approx. 20ms
every starting. Pr.
Setting Range Description
y If an earth (ground) fault is detected with "1" set in Pr. 249, fault Number
output (E.GF) is displayed and the output is shut off. 0 Without output phase failure protection
251
Dimension
Drawings
y Protective function will not activate if an earth (ground) fault occurs 1 (initial value) With output phase failure protection
Outline
during operation. 0 Without input phase failure protection
872 *
y If the motor capacity is smaller than the inverter capacity for the 5.5K 1 (initial value) With input phase failure protection
or more, earth (ground) fault detection may not be provided. ∗ The setting is available for three-phase power input models.
Terminal Specification
Terminal Connection
Explanation
Diagram
Pr. 250 Pr. 255 to 259
Selection of motor stopping method and Display of the life of the inverter parts
Operation panel
FR Configurator
Parameter unit
start signal Pr. 255 Life alarm status display Pr. 256 Inrush current limit circuit life display
Pr. 257 Control circuit capacitor life display Pr. 258 Main circuit capacitor life display
Pr. 250 Stop selection
Pr. 259 Main circuit capacitor life measuring
Used to select the stopping method (deceleration to a stop or
Degrees of deterioration of main circuit capacitor, control circuit
Parameter
coasting) when the start signal turns off.
capacitor or inrush current limit circuit and cooling fan can be
List
Used to stop the motor with a mechanical brake, etc. together with
diagnosed by monitor.
switching off of the start signal.
When any part has approached the end of its life, an alarm can be
You can also select the operations of the start signals (STF/STR).
output by self diagnosis to prevent a fault.
Explanations
Parameters
Description (Use the life check of this function as a guideline since the life
of
Pr. 250
Start signal except the main circuit capacitor is calculated theoretically.)
Setting Stop operation
(STF/STR) Pr. Setting
STF signal: The motor is coasted to a Description
Number Range
Forward rotation start stop when the preset time
Protective
Functions
0 to 100s Displays whether the control circuit capacitor,
STR signal: elapses after the start signal
Reverse rotation start is turned off. main circuit capacitor, cooling fan, and each
The motor is coasted to a 255 (0 to 15) parts of the inrush current limit circuit has
STF signal: Start signal reached the life alarm output level or not.
1000s to 1100s STR signal: stop (Pr. 250 - 1000)s after (Reading only)
Forward/reverse signal the start signal is turned off.
Displays the deterioration degree of the inrush
Options
STF signal: 256 (0 to 100%) current limit circuit.
Forward rotation start (Reading only)
9999
STR signal: When the start signal is
Reverse rotation start turned off, the motor Displays the deterioration degree of the
decelerates to stop. 257 (0 to 100%) control circuit capacitor.
STF signal: Start signal
Instructions
(Reading only)
8888 STR signal:
Forward/reverse signal Displays the deterioration degree of the main
circuit capacitor.
When "9999 (initial value) or 8888" is set in Pr. 250 258 (0 to 100%)
(Reading only)
The value measured by Pr. 259 is displayed.
Output Deceleration starts
frequency when start signal turns OFF Setting "1" and turning the power supply off
Motor
(Hz)
starts the measurement of the main circuit
Deceleration time capacitor life.
(Time set in Pr. 8, etc.) 259 0, 1
When the Pr. 259 value is "3" after powering on
DC brake again, the measuring is completed.
Time Displays the deterioration degree in Pr. 258.
Compatibility
When a value other than "9999" (initial value) or "8888" is set in Pr. 250
Warranty
When setting parameters, refer to the instruction manual (applied) and understand instructions. 44
Pr. 261 Pr. 270, 275, 276, 6, 48
Operation at instantaneous power
Stop-on-contact control AD MFVC GP MFVC
failure
Pr. 275 Stop-on contact excitation
Pr. 261 Power failure stop selection Pr. 270 Stop-on contact control selection
current low-speed multiplying factor
When a power failure or undervoltage occurs, the inverter can be Pr. 276 PWM carrier frequency at stop-on contact Pr. 6 Multi-speed setting (low speed)
Pr. 48 Second stall prevention operation current
decelerated to a stop or can be decelerated and re-accelerated to
To ensure accurate positioning at the upper limit etc. of a lift, stop-
the set frequency.
on-contact control causes a mechanical brake to be closed while
Pr. Setting the motor is developing a holding torque to keep the load in contact
Description
Number Range with a mechanical stopper etc.
Coasts to stop. This function suppresses vibration which is liable to occur when the
0 (initial
When undervoltage or power failure occurs,
value) load is stopped upon contact in vertical motion applications,
the inverter output is shut off.
When undervoltage or a power failure occurs, ensuring steady precise positioning.
1
261 the inverter can be decelerated to a stop.
When undervoltage or a power failure occurs, Pr. 270 Setting Description
the inverter can be decelerated to a stop. 0
2 Without stop-on-contact control
If power is restored during a power failure, the (initial value)
inverter accelerates again. 1 Stop-on-contact control
power failure function (Pr. 261 = "2") * Goes into stop-on-contact control when both RL and RT switch ON.
RL and RT may be switched on in any order with any time difference.
y When power is restored during deceleration after a power (a) Acceleration time (Pr. 7 ) (b) Deceleration time (Pr. 8 )
(c) Second deceleration time (Pr. 44/Pr. 45 )
failure, acceleration is made again up to the set frequency.
Pr. Setting
Description
Pr. 261 = 2
When power is restored during deceleration
Number Range
at occurrence of power failure Sets the output frequency for stop-on-contact
IPF control
0 to
Power 6 The frequency should be as low as possible
400Hz
Output (about 2Hz). If it is set to more than 30Hz, the
frequency
operating frequency will be 30Hz.
During deceleration at Reacceleration
occurrence of power failure Time Sets the stall prevention operation level for stall
0 to
Y46 48 prevention operation level.
200%
(Pr. 22 when Pr. 48 = "9999")
Usually set a value between 130% and 180%.
0 to
Pr. 267 Refer to the section about Pr. 73. 275 300%
Set the force (holding torque) for stop-on-contact
control.
Pr. 268 Refer to the section about Pr. 52. 9999 Without compensation.
Sets a PWM carrier frequency for stop-on-
Pr. 269 Parameter for manufacturer setting. Do not set. 276
0 to 9
contact control.
9999 As set in Pr. 72 PWM frequency selection.
45 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 278 to 283, 292 Pr.
Number
Setting
Range
Description
Brake sequence function AD MFVC GP MFVC Set to the rated slip frequency of the motor +
Features
278 0 to 30Hz about 1.0Hz.
Pr. 278 Brake opening frequency Pr. 279 Brake opening current This parameter may be set only if Pr. 278 ≤ Pr. 282.
Pr. 280 Brake opening current detection time Pr. 281 Brake operation time at start Generally, set this parameter to about 50 to
Pr. 282 Brake operation frequency Pr. 283 Brake operation time at stop 90%. If the setting is too low, the load is liable
Pr. 292 Automatic acceleration/deceleration 279 0 to 200% to drop due to gravity at start.
Peripheral
Suppose that the rated inverter current is
Devices
This function is used to output from the inverter the mechanical 100%.
brake operation timing signal in vertical lift and other applications. Generally, set this parameter to about 0.1 to
280 0 to 2s
This function prevents the load from dropping with gravity at a start 0.3s.
Pr. 292 = 7: Set the mechanical delay time until
Specifications
due to the operation timing error of the mechanical brake or an
Standard
the brake is loosened.
281 0 to 5s
overcurrent alarm from occurring at a stop, ensuring secure operation. Pr. 292 = 8: Set the mechanical delay time until
the brake is loosened + about 0.1 to 0.2s.
At this frequency, the brake opening request
<Operation example> signal (BOF) is switched off. Generally, set this
282 0 to 30Hz
parameter to the Pr. 278 setting + 3 to 4Hz.
Dimension
z At start: When the start signal is input to the inverter, the inverter
Drawings
Outline
This parameter may be only set if Pr. 282 ≥ Pr. 278.
starts running. When the internal speed command reaches
Pr. 292 =7: Set the mechanical delay time until
the value set in Pr. 278 and the output current is not less the brake is closed + 0.1s.
283 0 to 5s
than the value set in Pr. 279, the inverter outputs the brake Pr. 292 =8: Set the mechanical delay time until
the brake is closed + 0.2 to 0.3s.
Terminal Specification
Terminal Connection
opening request signal (BOF) after the time set in Pr. 280
Explanation
0, 1, 7, 8, Brake sequence function is made valid when a
Diagram
has elapsed. 292
11 setting is "7" or "8".
When the time set in Pr. 281 elapses after the brake opening
completion signal (BRI) was activated*, the inverter
increases the output frequency to the set speed.
Operation panel
FR Configurator
Pr. 286, 287
Parameter unit
z At stop: When the speed has decreased to the frequency set in Pr.
282, the brake opening request signal (BOF) is turned off.
Droop control AD MFVC
When the time set in Pr. 283 elapses after the brake
Pr. 286 Droop gain Pr. 287 Droop filter time constant
operation confirmation signal (BRI) was activated*, the
Parameter
inverter output is switched off. This function is designed to balance the load in proportion to the
List
* If Pr. 292 = "8" (mechanical brake opening completion signal not input), load torque to provide the speed drooping characteristic.
this time is the time after the brake opening request signal is output.
This function is effective for balancing the load when using
multiple inverters
Explanations
1) Pr. 292 = "7" (brake opening completion signal input)
Parameters
Output frequency (Hz)
Pr. Setting
of
Description
Target Number Range
frequency
Pr. 280 0
Pr. 282 Pr.13 setting
Droop control is invalid
Pr. 278
Pr. 281 or 0.5Hz, (initial value)
Protective
Functions
whichever is lower
Pr. 13 286 Set the drooping amount at the rated torque
0.1 to 100% as a percentage with respect to the rated
Time
Pr. 283
ON
STF
motor frequency.
Pr. 279
Output I 0.00 to Set the time constant of the filter applied on
287
Brake opening request ON 1.00s the torque amount current.
Options
(BOF signal)
Instructions
Output frequency (Hz)
Frequency command
Target
frequency
Pr. 280
Pr. 282 Pr.13 setting Droop compensation
Rated frequency
Pr. 281
Pr. 278 or 0.5Hz, frequency
whichever is lower
Pr. 13 Droop
gain
Motor
Time
Pr. 283
ON
STF
(BOF signal)
When setting parameters, refer to the instruction manual (applied) and understand instructions. 46
Pr. 296, 297 Pr. 338, 339, 550, 551
Password function Start command source and frequency
Pr. 296 Password lock level Pr. 297 Password lock/unlock command source during communication
Registering 4-digit password can restrict parameter reading/ operation
writing. Pr. 338 Communication operation command source Pr. 339 Communication speed command source
z Level of reading/writing restriction by PU/NET mode operation Pr. 550 NET mode operation command source selection Pr. 551 PU mode operation command source selection
command can be selected by Pr. 296. When the RS-485 communication with the PU connector or
communication option is used, the external start command and
PU Mode NET Mode Operation Command
frequency command can be made valid. Command source in the
Pr. 296 Operation RS-485 Communication
PU operation mode can be selected.
Setting Command Communication Option
Pr. Setting
Read Write Read Write Read Write Description
Number Range
9999 { { { { { {
0 (initial
0, 100 × × × × × × Start command source communication
338 value)
1, 101 { × { × { × 1 Start command source external
2, 102 { × { { { { 0
(initial Frequency command source communication
3, 103 { { { × { × value)
4, 104 × × × × { × 339 1 Frequency command source external
5, 105 × × { { { { Frequency command source external
6, 106 { { × × { × 2 (Frequency setting from communication is valid,
frequency terminal 2 is invalid)
Only parameters registered in the user group can be read/written
99, 199 (For the parameters not registered in the user group, same The communication option is the command
0
restriction level as "4, 104" applies.) source in the NET operation mode.
{: enabled, ×: restricted PU connector is the command source in the
2
NET operation mode.
550∗
Pr. Setting Automatic communication option recognition
Description 9999
Normally, PU connector is valid. When a
Number Range (initial
communication option is mounted, the
value)
1000 to communication option is valid.
Register a 4-digit password
9998 PU connector is the command source in the PU
2
operation mode.
Displays password unlock error count.
297 USB connector is the command source in the
(0 to 5) ∗ (Reading only) 3
PU operation mode.
(Valid when Pr. 296 = "100" to "106") Operation panel is the command source in the
4
9999 ∗ No password lock 551∗ PU operation mode.
USB automatic recognition
When Pr. 296 ≠ "9999" (with password lock), note that Pr. 297 is always Normally, operation panel is the command
9999
available for setting regardless of Pr. 160 setting. source. When the parameter unit is connected
(initial
∗ "0 or 9999" can be set to Pr.297 at any time although the displayed value to the PU connector, PU is the command
value)
does not change (set value is not displayed). source. When USB is connected, USB is the
command source.
∗ Pr. 550 and Pr. 551 are always write-enabled.
Pr. 298 Refer to the section about Pr. 82. Pr. 340 Refer to the section about Pr. 79.
Pr. 299 Refer to the section about Pr. 57. Pr. 342, 343 Refer to the section about Pr. 117.
47 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 495 to 497 Pr. 503, 504
Remote output function (REM signal) Maintenance of parts
Features
Pr. 495 Remote output selection Pr. 496 Remote output data 1 Pr. 503 Maintenance timer Pr. 504 Maintenance timer alarm output set time
Pr. 497 Remote output data 2
When the cumulative energization time of the inverter reaches the
You can utilize the on/off of the inverter's output signals instead of parameter set time, the maintenance timer output signal (Y95) is
the remote output terminal of the programmable controller.
Peripheral
output. (MT) is displayed on the operation panel.
Devices
Pr. Setting This can be used as a guideline for the maintenance time of
Description
Number Range
peripheral devices.
0
Remote output data clear
(initial
Specifications
First power
at powering off Remote output ON
Standard
value) data clear at
Remote output data held inverter reset
1
495 at powering off 9998
Remote output data clear (999800h)
10 Remote output Set "0" in Pr. 503
at powering off Maintenance
data held at timer
Dimension
Drawings
Remote output data held Pr. 504
Outline
11 inverter reset (Pr. 503)
at powering off
496∗ 0 to 4095 Time
Refer to the following diagram. Y95 signal OFF ON ON
497∗ 0 to 4095
MT display
Terminal Specification
∗ The above parameters allow its setting to be changed during operation in
Terminal Connection
z The cumulative energization time of the inverter is stored into the
Explanation
any operation mode even if "0" (initial value) is set in Pr. 77 Parameter write
Diagram
selection. EEPROM every hour and indicated in Pr. 503 Maintenance timer in
<Remote output data> 100h increments. Pr. 503 is clamped at 9998 (999800h).
Pr. 496
Operation panel
FR Configurator
Parameter unit
b11 b0
Pr. 547, 548
RUN
ABC
FU
∗1
∗1
∗1
∗1
∗1
∗1
∗1
∗1
∗1
Parameter
Inverter setup with setup software (FR Configurator) can be easily
List
b11 b0
performed by USB communication.
RA3 ∗2
RA2 ∗2
RA1 ∗2
Y6 ∗2
Y5 ∗2
Y4 ∗2
Y3 ∗2
Y2 ∗2
Y1 ∗2
Y0 ∗2
∗1
∗1
Pr. Setting
Description
Explanations
Parameters
Number Range
∗1 As desired (always 0 when read)
0
of
∗2 Y0 to Y6 are available only when the extension output option (FR- (initial Set the station number of USB device (inverter)
A7AY E kit) is fitted 547 value) within the range "0 to 31".
∗3 RA1 to RA3 are available only when the relay output option (FR-A7AR
1 to 31
E kit) is fitted
Set the communication check time interval of USB
Protective
Functions
communication.
Pr. 502 Refer to the section about Pr. 117.
548
0 to 999.8 If data is not received within the time set in Pr.
548, (E.USB) is displayed.
9999
(initial Communication time interval is not checked.
Options
value)
When setting parameters, refer to the instruction manual (applied) and understand instructions. 48
Pr. 555 to 557 Pr. 653
Current average value monitor signal Reduce mechanical resonance
Pr. 555 Current average time Pr. 556 Data output mask time Pr. 653 Speed smoothing control
Pr. 557 Current average value monitor signal
output reference current Mechanical vibration produced while motor is driving (resonance)
can be reduced.
The average value of the output current during constant speed
operation and the maintenance timer value are output as a pulse Set 100% in Pr. 653 and check if the vibration will be reduced.
to the current average value monitor signal (Y93). Make adjustment gradually increasing the setting, until the
The pulse width output to the I/O module of the programmable
vibration become the smallest.
controller or the like can be used as a guideline due to abrasion of
machines and elongation of belt and for aged deterioration of
devices to know the maintenance time.
The current average value monitor signal (Y93) is output as pulse
Pr. 665, 882, 883, 885, 886
for 20s as 1 cycle and repeatedly output during constant speed Regeneration avoidance function
operation.
Pr. 665 Regeneration avoidance frequency gain Pr. 882 Regeneration avoidance operation selection
Pr. 885 Regeneration avoidance
From acceleration to constant speed operation Pr. 883 Regeneration avoidance operation level
compensation frequency limit value
Output frequency Pr. 886 Regeneration avoidance voltage gain
This function detects a regeneration status and increases the
Time frequency to avoid the regenerative status.
1 cycle (20s) Next cycle
z Possible to avoid regeneration by automatically increasing the
Y93 signal
frequency and continue operation if the fan happens to rotate faster
1) Data output mask time
When the speed has changed to
constant from acceleration/deceleration,
5) End pulse
Output as low pulse than the set speed due to the effect of another fan in the same duct.
Y93 signal is not output for Pr. 556 time. shape for 1 to 16.5s
2 ".
Regeneration avoidance
operation example for deceleration
frequency Bus voltage
Pr. 883
(VDC)
Time
Output
(Hz)
49 When setting parameters, refer to the instruction manual (applied) and understand instructions.
Pr. 888, 889 Pr. 990
Free parameter Buzzer control of the operation panel
Features
Pr. 889 Free parameter 1 Pr. 889 Free parameter 2 Pr. 990 PU buzzer control
Parameters you can use for your own purposes. You can make the buzzer "beep" when you press key of the
You can input any number within the setting range 0 to 9999. operation panel and parameter unit (FR-PU04/FR-PU07)
Peripheral
For example, the number can be used:
Devices
Pr. 990 Setting Description
y As a unit number when multiple units are used.
0 Without buzzer
y As a pattern number for each operation application when 1
multiple units are used. With buzzer
(initial value)
Specifications
Standard
y As the year and month of introduction or inspection.
Pr. 991
Pr. C0(900)
PU contrast adjustment
Dimension
Drawings
Outline
Adjustment of terminal FM output Pr. 991 PU contrast adjustment
(calibration) Contrast adjustment of the LCD of the parameter unit (FR-PU04/
C0 (Pr. 900)FM terminal calibration FR-PU07) can be performed.
Terminal Specification
Terminal Connection
By using the operation panel or parameter unit, you can calibrate Decreasing the setting value makes contrast light.
Explanation
Diagram
terminal FM to full scale deflection.
Pr. 991 Setting Description
FM terminal calibration (C0 (Pr. 900))
0: Light
Operation panel
FR Configurator
y The terminal FM is preset to output pulses. By setting the
Parameter unit
0 to 63 È
calibration parameter C0 (Pr. 900), the meter connected to the 63: Dark
inverter can be calibrated by parameter setting without use of a
calibration resistor.
y Using the pulse train output of the terminal FM, a digital display
Pr. CL, ALLC, Er.CL, CH
Parameter
can be provided by a digital counter. The monitor value is 1440
List
pulses/s output at the full-scale value of Pr. 54 FM terminal function Clear parameter, initial value change list
selection.
Pr.CL Parameter clear ALLC All parameter clear
Indicator Er.CL Fault history clear Pr.CH Initial value change list
Explanations
Parameters
1mA full-scale (Digital indicator)
1mA
analog meter
1440 pulses/s(+) (-) z Set "1" in Pr.CL parameter clear to initialize all parameters.
of
FM FM
(Calibration parameters are not cleared.) ∗
(+) (-) T1
Calibration
resistor *1
SD
8VDC
SD z Set "1" in ALLC All parameter clear to initialize all parameters.∗
T2 z Set "1" in Er.CL Faults history clear to clear faults history.∗
Pulse width T1: Adjust using calibration parameter C0
Protective
Functions
Pulse cycle T2: Set with Pr. 55 (frequency monitor)
Set with Pr. 56 (current monitor)
z Using Pr.CH Initial value change list, only the parameters changed
∗1 Not needed when the operation panel or parameter unit (FR-PU04/FR- from the initial value can be displayed.
PU07) is used for calibration. ∗ Parameters are not cleared when "1" is set in Pr. 77 Parameter write
Used when calibration must be made near the frequency meter for such selection.
a reason as a remote frequency meter.
However, the frequency meter needle may not deflect to full-scale if the
Options
calibration resistor is connected. In this case, use this resistor and
operation panel or parameter unit together.
When setting parameters, refer to the instruction manual (applied) and understand instructions. 50
Protective Functions
When a fault occurs, the inverter trips and the PU display automatically changes to any of the following fault or alarm indications.
Function Name Description Display
Operation panel lock Appears when operation was tried during operation panel lock.
Error message
Password locked Password function is active. Display and setting of parameter is restricted.
∗2
to
Parameter write error Appears when an error occurred during parameter writing.
value. If the regenerative brake duty reaches 100%, a regenerative overvoltage (E. OV_) occurs.
Electronic thermal relay function prealarm Appears when the electronic thermal O/L relay has reached 85% of the specified value.
∗3
PU stop Appears when on the operation panel was pressed during external operation.
Maintenance signal output ∗7 Appears when the cumulative energization time has exceeded the maintenance output timer set value.
Undervoltage Appears when the main circuit power became low voltage.
Alarms
Appears when the cooling fan remains stopped when operation is required or when the speed has
Fan alarm
∗4
decreased.
Overcurrent trip during acceleration Appears when an overcurrent occurred during acceleration.
Overcurrent trip during constant speed Appears when an overcurrent occurred during constant speed operation.
Overcurrent trip during deceleration
Appears when an overcurrent occurred during deceleration and at a stop.
or stop
Regenerative overvoltage trip during
Appears when an overvoltage occurred during acceleration.
acceleration
Regenerative overvoltage trip during
Appears when an overvoltage occurred during constant speed operation.
constant speed
Regenerative overvoltage trip during
Appears when an overvoltage occurred during deceleration and at a stop.
deceleration or stop
Inverter overload trip
Appears when the electronic thermal relay function for inverter element protection was activated.
(electronic thermal relay function)
Motor overload trip
Appears when the electronic thermal relay function for motor protection was activated.
(electronic thermal relay function) ∗1
Fin overheat Appears when the heatsink overheated.
May appear when one phase voltage is lost or differs greatly from others in three-phases power
Input phase loss ∗8 ∗9
supply.
Stall prevention Appears when the output frequency drops to 1Hz as a result of deceleration due to the excess motor load.
This function stops the inverter output if an alarm occurs in the brake circuit, e.g. damaged brake
Brake transistor alarm detection
transistors. In this case, the inverter must be powered off immediately.
Output side earth (ground) fault
Appears when an earth (ground) fault occurred on the inverter's output side. (detects only at a start)
overcurrent at start ∗7
If one of the three phases (U, V, W) on the inverter's output side (load side) is lost during inverter
Output phase loss operation (except during DC injection brake operation and when output frequency is under 1Hz),
inverter stops the output.
Fault
External thermal relay operation∗6 ∗7 Appears when the external thermal relay connected to the OH signal was activated.
∗5
Appears when communication option is installed during password lock (Pr. 296 Password lock level =
Option fault
"0, 100").
Communication option fault Appears when a communication error occurred in the communication option.
Appears when a contact fault or the like of the connector between the inverter and communication
Option fault
option occurs.
Parameter storage device fault Appears when operation of the element where parameters stored became abnormal. (control board)
Internal board fault When a combination of control board and main circuit board is wrong, the inverter is tripped.
Appears when a communication error between the PU and inverter occurred, the communication
PU disconnection interval exceeded the permissible time during the RS-485 communication with the PU connector, or
communication errors exceeded the number of retries during the RS-485 communication.
Retry count excess ∗7 Appears when the operation was not restarted within the set number of retries.
/
CPU fault Appears during the CPU and peripheral circuit errors occurred. /
/
Inrush current limit circuit fault Appears when the resistor of the inrush current limit circuit overheated.
Appears if voltage(current) is input to terminal 4 when the setting in Pr.267 Terminal 4 input selection
Analog input fault
and the setting of voltage/current input switch are different.
The inverter output is stopped when a sequence error occurs during use of the brake sequence to
Brake sequence error ∗7
function (Pr. 278 to Pr. 285).
USB communication fault Appears when USB communication error occurred.
Internal circuit fault Appears when an internal circuit error occurred.
∗1 Resetting the inverter initializes the internal thermal integrated data of the electronic thermal relay function.
∗2 The error message shows an operational error. The inverter output is not shut off.
∗3 Warnings are messages given before fault occur. The inverter output is not shut off.
∗4 Alarms warn the operator of failures with output signals. The inverter output is not shut off.
∗5 When faults occur, the protective functions are activated to inverter trip and output the fault signals.
∗6 The external thermal operates only when the OH signal is set in Pr. 178 to Pr. 184 (input terminal function selection).
∗7 This protective function does not function in the initial status.
∗8 Protective function activates when Pr.872 Input phase loss protection selection = "1".
∗9 Available for only three-phase power input models.
51
Option and Peripheral Devices
Option list
By fitting the following options to the inverter, the inverter is provided with more functions.
One type of plug-in option can be mounted.
Features
Applicable
Name Type Applications, Specifications, etc.
Inverter
y This input interface sets the high frequency accuracy of the inverter using an external BCD
or binary digital signal.
16-bit digital input FR-A7AX E kit y BCD code 3 digits (maximum 999) y BCD code 4 digits (maximum 9999)
Peripheral
Devices
y Binary 12 bits (maximum FFFH) y Binary 16 bits (maximum FFFFH)
y This option provides the inverter with open collector outputs selected from among the
Plug-in type
Specifications
y 20mADC or 10VDC meter can be connected. models
Standard
y This option provides the inverter with three different relay contact outputs selected from
Relay output FR-A7AR E kit among the standard output signals.
CC-Link communication FR-A7NC E kit
Communication
Dimension
Drawings
Outline
terminal
Control
Multi-drop connection is easy with the 2-port terminal block adapted for EIA-485 (RS-485) Shared among all
RS-485 2-port terminal block FR-E7TR communication terminal. models
Terminal Specification
Terminal Connection
FR-PU04 models
Explanation
This parameter unit enables parameter setting without connecting the inverter to power Shared among all
Diagram
Parameter unit with battery pack FR-PU07BB supply. models
This operation panel enables inverter operation and monitoring of frequency, etc. from the
Enclosure surface operation panel FR-PA07 enclosure surface
Cable for connection of operation panel or parameter unit
Parameter unit connection cable FR-CB20
indicates a cable length. (1m, 3m, 5m) Shared among all
Operation panel
FR Configurator
Parameter unit
Connector for amplifier Connector for personal computer models
MR-J3USBCBL3M
USB cable mini-B connector (5 pin) A connector
Cable length 3m
For installation of a FR-E700 series inverter to the installation holes of FR-A024/A044 series Compatible with
Intercompatibility attachment FR-E7AT01 to 03 inverter. the 3.7K or less
Compatible with
Parameter
DIN rail attachment FR-UDA01 to 03 Attachment for installation on DIN rail the 3.7K or less
List
For harmonic current reduction and inverter input power factor improvement (total power
AC reactor FR-HAL factor approx. 88%) According to
For harmonic current reduction and inverter input power factor improvement (total power capacities
DC reactor FR-HEL factor approx. 93%)
Stand-alone shared
Explanations
EMC Directive compliant noise filter EMC Directive (EN61800-3 C3) compliant noise filter
Parameters
FR-S5NFSA capacities
200V: According to
of
FR-A5AT03 capacities
EMC compliant EMC filter According to
FR-AAT02 For installation of the inverter to the EMC Directive compliant EMC filter (SF).
installation attachment capacities
200V: According to
FR-E5T(-02) capacities
Protective
Functions
Radio noise filter FR-BIF(H) For radio noise reduction (connect to the input side)
Shared among all
FR- BSF01,
Line noise filter For line noise reduction models
FR- BLF
Three-phase
Combination of power factor improving DC reactor, common mode choke, and capacitative power input model:
Filterpack FR-BFP2 filter compatible with
Options
0.4K or more
Brake resistor MRS type, MYS type For increasing the regenerative braking capability (permissible duty 3%ED)
High-duty brake resistor FR-ABR For increasing the regenerative braking capability (permissible duty 10%/6%ED) For the 0.4K or
Brake unit, Resistor unit, FR-BU2, FR-BR, For increasing the braking capability of the inverter (for high-inertia load or negative load) more
Discharging resistor GZG, GRZG type Brake unit, electrical-discharge resistor and resistor unit are used in combination
Instructions
Power regeneration common converter FR-CV Unit which can return motor-generated braking energy back to the power supply in common
Stand-alone reactor dedicated for the FR-CV FR-CVL converter system
According to
The high power factor converter switches the converter section on/off to reshape an input capacities
High power factor converter FR-HC current waveform into a sine wave, greatly suppressing harmonics. (Used in combination with
the standard accessory.)
400V: According to
FR-ASF capacities
Surge voltage suppression filter Filter for suppressing surge voltage on motor
400V: For the 5.5K
Motor
FR-BMF or more
Manual controller FR-AX For independent operation. With frequency meter, frequency potentiometer and start switch.
controller/speed controller
DC tach. follower FR-AL For synchronous operation (1.5VA) by external signal (0 to 5V, 0 to 10V DC)∗
Three speed selector FR-AT For three speed switching, among high, middle and low speed operation (1.5VA)∗
FR series manual
Motorized speed setter FR-FK For remote operation. Allows operation to be controlled from several places (5VA)∗
Compatibility
Ratio setter FR-FH For ratio operation. The ratios of five inverters can be set (3VA)∗
Speed detector FR-FP For tracking operation by a pilot generator (PG) signal (3VA)∗
Master controller FR-FG Master controller (5VA) for parallel operation of multiple (maximum 35) inverters.∗
Soft starter FR-FC For soft start and stop. Enables acceleration/deceleration in parallel operation (3VA)∗
Shared among all
For continuous speed control operation. Used in combination with a deviation sensor or models
Deviation detector FR-FD synchro (5VA)∗
Warranty
Calibration resistor RV24YN 10kΩ For frequency meter calibration. Carbon film type B characteristic
Shared among all
FR Configurator SW3 (VFD setup FR-SW3-
Supports an inverter startup to maintenance. models
software) SETUP-WE (Available soon)
∗ Rated power consumption. The power supply specifications of the FR series manual controllers and speed controllers are 200VAC 50Hz, 220V/220VAC 60Hz,
and 115VAC 60Hz.
52
Control terminal option
SOURCE
RES
Reset Open collector output common
SE value) to select current input (4 to
SINK
SD Sink/source common
Contact input common 24V Calibration Indicator (Frequency meter, etc.) 20mA).
24VDC power supply
(Common for external power supply transistor) PC *1 resistor + - Moving-coil type ∗4 It is recommended to use 2W1kΩ
Frequency setting signals (Analog) 3 10(+5V)
FM 1mA full-scale when the frequency setting signal is
Terminal *5
2/SG switch SD changed frequently.
Frequency setting 2
potentiometer 2 0 to 5VDC *2 *6 ∗5 It is not necessary when calibrating
1/2W1kΩ (0 to 10VDC) O SDA
*4
N
SDA
EIA-485 (RS-485) the indicator from the operation
communication signal
1 SG SDB panel.
(Analog common) SDB
RDA
From the computer ∗6 Set the switch to the right (ON)
Terminal 4 input (+) 4 4 to 20mADC or previous inverter
(Current input) (-) 0 to 5VDC *3
RDA position to pass a shielded wire
RDB
0 to 10VDC
RDB
across terminal SG.
I V ∗7 Set only the terminating resistor
Voltage/current
OPEN 100Ω To the next inverter switch of the remotest inverter to the
input switch *3 Terminating
resistor switch *7 "100Ω" position.
SOURCE
100Ω (valid/invalid can be changed with a
SINK
Terminating resistor
terminating resistor switch)
SDA SDB RDA RDB RUN FU SE
A B C
SDB (2 points) Inverter send- Inverse sending signal output terminal from the inverter.
Receive signal input terminal of the inverter.
RDA (2 points) Inverter receive+ Changing the terminating resistor switch to "100Ω" side connects the inverter to the 100Ω
terminating resistor.
Receive signal input terminal of the inverter.
RDB (2 points) Inverter receive- Changing the terminating resistor switch to "100Ω" side connects the inverter to the 100Ω
terminating resistor.
Used as power supply when connecting potentiometer for frequency setting (speed setting)
10 Frequency setting power supply from outside of the inverter. (Specifications are the same as the standard control circuit
terminal)
Inputting 0 to 5VDC (or 0 to 10V) provides the maximum output frequency at 5V (10V) and
Frequency setting
makes input and output proportional. (Specifications are the same as the standard control
circuit terminal)
Frequency setting (voltage)/
2
Common terminal
Set terminal 2/SG switch to the right position (ON) to change terminal 2 to terminal SG to
pass a shielded wire across terminal SG during RS-485 communication. In this case,
voltage at terminal 2 is 0V input.
Inputting 4 to 20mADC (or 0 to 5V, 0 to 10V) provides the maximum output frequency at
4 Frequency setting (current) 20mA and makes input and output proportional. (Specifications are the same as the standard
control circuit terminal)
RS-485 communication common, Common terminal of RS-485 communication and frequency setting signal (terminal 2 or
SG
Analog common terminal 4). Do not earth (ground).
∗ Specifications of contact input (STF, STR, RH, RM, RL, MRS, RES, SD, PC) and output signal (A. B, C, RUN, FU, SE, FM) are the same as the
standard control circuit terminal.
53
Stand-alone option
Features
Name (type) Specifications, Structure, etc.
z FR-A024/A044 series intercompatibility attachment
The FR-E700 series inverter can be installed using installation holes of the conventional
FR-A024/A044 series with this attachment. This attachment is useful for replacing the FR-E7AT Inverter
conventional model with the FR-E700 series.
(The depth increases after installation of the inverter when the attachment is used. )
12
Peripheral
Devices
Intercompatibility Mountable Models Compatible Former Models Increased Depth (mm)
Attachment Type E720 E740 A024 A044 200V class 400V class
attachment
0.1K 0.1K 26.5
FR-E7AT
0.2K 0.2K 26.5
Specifications
FR-E7AT01 — — —
0.4K 0.4K 48.5
Standard
0.75K 0.75K 39.5
FR-E7AT02 1.5K — 1.5K — 31.5 —
— 1.5K — 1.5K — 11
FR-E7AT03 2.2K 2.2K 2.2K 2.2K 21.5 11
3.7K 3.7K 3.7K 3.7K 28.5 11
Dimension
Drawings
z Attachment to enable installation of FR-E700 series on DIN rail.
Outline
Selection table
Inverter Capacity
Attachment Type
E720 E720S E710W
FR-UDA01 0.1K, 0.2K, 0.4K, 0.75K 0.1K,0.2K,0.4K 0.1K,0.2K,0.4K
FR-UDA02 1.5K,2.2K 0.75K,1.5K 0.75K
Terminal Specification
Terminal Connection
FR-UDA03 3.7K — —
Explanation
Diagram
z Approximate dimension
<FR-UDA01> <FR-UDA02> <FR-UDA03>
Operation panel
FR Configurator
Parameter unit
67 67 67
attachments 15 15 14.4
10
FR-UDA
128
128
128
Parameter
List
8.7
8.7
8.7
Explanations
Parameters
Hook 3-M4 0.7 screw Hook 4-M4 0.7 screw Hook 4-M4 0.7 screw (Unit: mm)
of
z Outline dimension
(Unit: mm)
Mass Mass
Less than D
AC reactor Inverter Type W D H (kg) Inverter Type W D H (kg)
0.4K 104 72 99 0.6 H0.4K 135 59.6 115 1.5
(for power
Protective
Functions
0.75K 104 74 99 0.8 H0.75K 135 59.6 115 1.5
coordination) 1.5K 104 77 99 1.1 H1.5K 135 59.6 115 1.5
FR-HAL-(H)
K 2.2K 115 77 115 1.5 H2.2K 135 59.6 115 1.5
200V
400V
Options
11K 160 111 164 5.2 H11K 160 91 146 6.0
W
15K 160 126 167 7.0 H15K 220 105 195 9.0
(Note) 1. Make selection according to the applied motor capacity. (When the inverter capacity is larger than
the motor capacity, make selection according to the motor capacity)
2. Power factor improving reactor (FR-BAL) can be used.
Instructions
Power factor improving effect :FR-BAL approx. 90%
FR-HAL approx. 88%
(Effect of power factor may decline slightly when using a single-phase power input model.)
3. Outline dimension drawing shown is a one of a typical model. The shape differs according to each models.
4. Install the AC reactor (FR-HAL) on horizontal or vertical plane.
z Outline dimension
(Unit: mm)
Motor
400V
(Note) 1. Be sure to remove the jumper across the inverter terminals P/+-P1. (A failure to do so will produce no power factor improving effect))
2. The wiring length between the reactor and inverter should be within 5m.
3. The size of the cables used should be equal to or larger than that of the power supply cables (R/L1, S/L2, T/L3).
4. Make selection according to the motor capacity. (When the inverter capacity is larger than the motor capacity, make selection according to
the motor capacity)
5. Power factor improving reactor (FR-BEL) can be used.
Power factor improving effect : FR-BEL approx.95%
Inquiry
FR-HEL approx.93%
(Effect of power factor may decline slightly when using a single-phase 200V power input model.)
6. Outline dimension drawing shown is a one of a typical model.
The shape differs according to each models.
7. Install the DC reactor (FR-HEL) on horizontal or vertical plane.
8. Single-phase 100V power input model is not compatible with the DC reactor.
54
Name (type) Specifications, Structure, etc.
z The EMC compliant EMC filter (EN61800-3 2nd Environment Category C3) is a filter compliant with the EU EMC Directive (EN61800-3 2nd
Environment Category C3).
H
FR-E720S-2.2K
FR-E720-5.5K, 7.5K FR-E5T-02
SF1260 222 468 80 5 440 118
FR-E720-11K FR-A5AT03
SF1261 FR-E720-15K FR-AAT02 253 600 86 9.3 71 37
EMC Directive SF1175 FR-E740-11K, 15K FR-AAT02 253 530 60 4.7 76 56
compliant EMC filter SF1320 FR-E720S-0.1K to 0.4K — 70 168 30.5 0.4 10 2.7
SF
SF1321 FR-E720S-0.75K — 110 168 36.5 0.6 10 3.8
W D
FR-E5NF-H0.75K FR-E740-0.4K, 0.75K — 140 210 46 1.1 22.6 5.5
FR-E5NF-H
K FR-E5NF-H3.7K FR-E740-1.5K to 3.7K — 140 210 46 1.2 44.5 8 (Note) Above outline dimension
(400V class) FR-E5NF-H7.5K FR-E740-5.5K, 7.5K — 220 210 47 2 68.4 15 drawing is an example.
Dimensions differ by model.
FR-S5NFSA-
K FR-S5NFSA-
FR-E710W-0.1K to 0.4K — 70 168 35 0.5 4.5 1.74
0.75K
(100V / 200V class) FR-E720S-1.5K
FR-S5NFSA-1.5K — 110 168 35 0.7 9.5 8.55
FR-E710W-0.75K
S/L2
supply T/L3
29 φ4.3 hole
41
Earth
4
T/L3
31.5
160
way as the input side.
180
4. Please use FR-BSF01 for inverters with
small capacities of 3.7K or less. Thick wires
(38mm2 or more) can not be used. In such
cases, use the FR-BLF.
55
Name (type) Specifications, Structure, etc.
z Using the option, the inverter may conform to the Japanese guideline for reduction of harmonic emission.
z The option is available for three-phase 200V/400V class inverters with 0.4K to 15K capacity.
z Specification
Features
• Three-phase 200V power input model
Type FR-BFP2-
K 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Permissible inverter output current (A) ∗1 2.5 4.2 7 10 16.5 23.8 31.8 45 58
Approximate mass (kg) 1.3 1.4 2.0 2.2 2.8 3.8 4.5 6.7 7.0
Install a DC reactor on the DC side.
Power factor improving reactor
Peripheral
(93% to 95% of power supply power factor under 100% load)
Devices
Common mode choke Install a ferrite core on the input side.
Noise filter
Capacitive filter About 4mA of capacitor leakage current ∗2
Protective structure (JEM1030) Open type (IP00)
• Three-phase 400V power input mode
Specifications
Type FR-BFP2-H
K 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Standard
Permissible inverter output current (A) ∗1 1.2 2.2 3.7 5 8.1 12 16.3 23 29.5
Approximate mass (kg) 1.6 1.7 1.9 2.3 2.6 4.5 5.0 7.0 8.2
Install a DC reactor on the DC side.
Power factor improving reactor (93% to 95% of power supply power factor under 100% load)
Common mode choke Install a ferrite core on the input side.
Noise filter
Capacitive filter About 8mA of capacitor leakage current ∗2
Dimension
Protective structure (JEM1030) Open type (IP00)
Drawings
Outline
∗1 Select a capacity for the load (inverter output) current to be equal to or less than the permissible inverter output current.
∗2 The indicated leakage current is for one phase of the three-phase three-wire star-connection power supply.
Terminal Specification
Terminal Connection
<FR-BFP2-H0.4K, H0.75K, H1.5K, H2.2K, H3.7K> <FR-BFP2-H5.5K, H7.5K, H11K, H15K>
Explanation
Diagram
2-φ4.5 hole 2-φ4.5 hole 2-fC hole 2-fC hole
H2
H2
5
5
Operation panel
FR Configurator
Parameter unit
H1
H1
H
H1
Rating
Parameter
Rating plate
H1
plate
H
List
H2
H2
C1 C1
12.5 D1 12.5 25 145 25
Explanations
Parameters
D (25) 195
220
L-bracket for inverter
of
back installation
(Enclosed with the option) ∗
5
5
4.5 4.5
D2 D1 D2 W2 W1 W2
D W
Protective
Functions
Capacity H H1 H2
D1 C C1 C2D
5.5K, 7.5K 210 198 6 75
50 4.5 4.5 5.3
200V
1.5K, 2.2K 108 55 26.5 188 178 80 55 12.5 H5.5K, H7.5K 210 198 6 75
50 4.5 4.5 4.3
Options
400V
3.7K 170 120 25 188 178 65 40 12.5 H11K 320 305 607.5 6 85
6 4.3
H0.4K, H0.75K∗ 108 55 26.5 188 178 55 30 12.5 H15K 320 305 607.5 6 85
6 6.4
H1.5K, H2.2K, H3.7K 108 55 26.5 188 178 80 55 12.5 (Unit: mm)
(Unit: mm) ∗ L-bracket is not attached when shipped from the factory but is
enclosed with the option. L-bracket is required to install the
∗ The 400V class H0.4K and H0.75K have no slit.
Instructions
option to the back of inverter.
(Note) 1. The option can be installed to the back or to the side. (The option cannot be installed to the back of FR-E720-5.5K/7.5K, FR-E740-0.4K to 3.7K.)
2. Above outline dimension drawings are examples. Dimensions differ by model.
z Outline dimension
MRS type MYS type (Unit: mm)
172 220
Round
Round
4.3
42
crimping
4.3
crimping
60
terminals terminals
1.25-4 φ4.3 hole
Compatibility
1.25-4
20
20
1.2
3.5
56
Name (type) Specifications, Structure, etc.
z Outline dimension
(Unit: mm)
Outline Dimension Outline Dimension
Resistance Value
Resistance Value
Approx. Mass
Approx. Mass
Permissible Permissible
(kg)
(kg)
(Ω)
(Ω)
Brake Resistor Type Brake Brake Resistor Type Brake
Duty W W1 D H Duty W W1 D H
FR-ABR-0.4K 10% 140 500 40 21 200 0.2 FR-ABR-H0.4K 10% 115 500 40 21 1200 0.2
FR-ABR-0.75K 10% 215 500 40 21 100 0.4 FR-ABR-H0.75K 10% 140 500 40 21 700 0.2
FR-ABR-H1.5K 10% 215 500 40 21 350 0.4
FR-ABR-2.2K*2 10% 240 500 50 26 60 0.5
FR-ABR-H2.2K 10% 240 500 50 26 250 0.5
High-duty
200V
400V
FR-ABR-3.7K 10% 215 500 61 33 40 0.8 FR-ABR-H3.7K 10% 215 500 61 33 150 0.8
brake resistor FR-ABR-5.5K 10% 335 500 61 33 25 1.3 FR-ABR-H5.5K 10% 335 500 61 33 110 1.3
FR-ABR-(H)
K FR-ABR-7.5K 10% 400 500 80 40 20 2.2 FR-ABR-H7.5K 10% 400 500 80 40 75 2.2
FR-ABR-11K 6% 400 700 100 50 13 3.5 FR-ABR-H11K 6% 400 700 100 50 52 3.2
18 2.4 18 2.4
FR-ABR-15K*3 6% 300 700 100 50 FR-ABR-H15K*4 6% 300 700 100 50
(×1/2) (×2) (×2) (×2)
(Note) 1. The regenerative brake duty setting should be less than permissible brake duty in the table
D
H above.
2. The temperature of the brake resistor becomes 300°C or more depending on the operation
frequency, care must be taken for installation and heat dissipation.
W1+20 3. MYS type resistor can be also used. Note that the permissible brake duty.
4. The brake resistor can not be used with the 0.1K and 0.2K.
0 W 5. Do not remove a jumper across terminal P/+ and P1 except when connecting a DC reactor.
z A brake unit is an option that fully enhances the regenerative braking capability of the inverter, and should be used with an electrical-
discharge resistor. Select from two discharging resistor according to the required braking torque.
z Specification
<Brake Unit>
200V * 400V
Type FR-BU2-
1.5K 3.7K 7.5K 15K 30K H7.5K H15K H30K
Applicable motor capacity Capacity of the motor to be used with differs according to the braking torque and duty (%ED)
Brake unit Connected brake resistor GRZG type, FR-BR (refer to the table below for combinations)
Up to 10 units
FR-BU2-(H)
K Multiple (parallel) operation
(note that torque generated is not more than the tolerable overcurrent amount of connected inverter)
Approximate mass (kg) 0.9 0.9 0.9 0.9 1.4 0.9 0.9 1.4
Resistor unit ∗ The option can also be connected to a single-phase 100V class inverter.
<Discharging resistor>
FR-BR-(H)
K
200V 400V
Type GRZG
GZG300W-50Ω GRZG200-10Ω GRZG300-5Ω GRZG400-2Ω GRZG200-10Ω GRZG300-5Ω GRZG400-2Ω
Discharging resistor Number of connectable devices One Three in series Four in series Six in series Six in series 8 in series 12 in series
Brake resistor total resistance value (Ω) 50 30 20 12 60 40 24
GZG type Continuous permissible power (W) 100 300 600 1200 600 1200 2400
GRZG type
<Resistor unit>
200V 400V
Type FR-BR-
15K 30K H15K H30K
Brake resistor total resistance value (Ω) 8 4 32 16
Continuous permissible power (W) 990 1990 990 1990
Approximate mass (kg) 15 30 15 30
57
Name (type) Specifications, Structure, etc.
z Selection
<When GRZG type is connected>
y The maximum temperature rise of the discharging resistors is approximately 100°C. Use heat-resistant wires and wire to avoid contact
Features
with resistors.
Power Motor (kW)
Supply 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Voltage Braking torque
50% 30s FR-BU2-1.5K FR-BU2-3.7K FR-BU2-7.5K FR-BU2-15K
200V
FR-BU2-
Peripheral
class 100% 30s FR-BU2-1.5K FR-BU2-7.5K FR-BU2-15K 2 × FR-BU2-15K*1
Devices
3.7K
400V 50% 30s —*2 FR-BU2-H7.5K FR-BU2-H15K
class 100% 30s —*2 FR-BU2-H7.5K FR-BU2-H15K FR-BU2-H30K
∗1 The number before the model name explains the number of connectable units in parallel.
∗2 The inverter for 400V class 1.5K or less can not be used in combination with a brake unit. To use in combination with a brake unit, use the inverter of
Specifications
2.2K or more.
Standard
<When FR-BR is connected>
y The temperature rise of the resistor unit is about a maximum of 100°C. Therefore, use heat-resistant wires (such as glass wires).
%ED at short-time rating when braking torque is 100% Braking torque (%) at short-time rating when 10%ED is 15s
Motor Capacity 5.5kW 7.5kW 11kW 15kW Motor Capacity 5.5kW 7.5kW 11kW 15kW
200V FR-BU2-15K 80 40 15 10 200V FR-BU2-15K Injection brake 280 200 120 100
%ED
Dimension
Drawings
class FR-BU2-30K — — 65 30 class FR-BU2-30K torque (%) — — 260 180
Outline
400V FR-BU2-H15K 80 40 15 10 400V FR-BU2-H15K Injection brake 280 200 120 100
%ED
class FR-BU2-H30K — — 65 30 class FR-BU2-H30K torque (%) — — 260 180
tb
Regeneration duty factor (operation frequency)%ED 100 tb<15s (continuous operation time)
tc
Terminal Specification
Terminal Connection
Example 1 Travel operation Example 2 Lift operation
Explanation
Diagram
Ascending
Speed
Speed
Descending
Operation panel
FR Configurator
Parameter unit
Time t Time t
tb
Brake unit tc
t1
FR-BU2-(H)
K
tc t2 t3 t4 tb=t1+t2+t3+t4
Parameter
List
FR-BR-(H)
K ON OFF
T *3
MC
MC
Discharging resistor Resistor unit or
discharging resistor
Explanations
Inverter
Parameters
MCCB MC
GZG type Three-phase U Motor
Resistor unit or
R/L1 P discharging resistor P
AC power supply
GRZG type
of
S/L2 V IM PR PR
T/L3 W
PR A PR A
Protective
Functions
P/+ P/+ B P/+ B
*2
N/- N/- C N/- C
*2 *2
RES RES
Reset
BUE *1 BUE *1
Brake permission signal SD SD
MSG MSG
Options
Signal for SD SD
master/slave MSG MSG
SD SD
∗1 A jumper is connected across BUE and SD in the
initial status. Brake unit Brake unit
∗2 Connect the inverter terminals (P/+, N/-) and FR-BU2 FR-BU2
Instructions
brake unit (FR-BU2) terminals so that their
terminal symbols match with each other. When connecting
Incorrect connection will damage the inverter. Do several brake units
not remove a jumper across terminal P/+ and P1
except when connecting a DC reactor.
∗3 When the power supply is 400V class, install a
step-down transformer.
Compatibility
H
W D H
Warranty
W W
D
58
Name (type) Specifications, Structure, etc.
z Enables 100%-torque continuous regeneration to support continuous regenerative operation for line control, etc. (Maximum torque 150% 60s)
z Eliminates the need to use a brake unit with each inverter, reducing total space and total cost.
z Saves energy since regeneration energy is used for the other inverters and excess energy is returned to the power supply.
z Heatsink protrusion type has the heat generating section outside of the enclosure, and exhaust the converter generated heat to the outside
of enclosure.
z Connection diagram
R/L1 U
S/L2 *1
T/L3 V IM
W
*5
Dedicated stand-alone FR-CV type power
reactor (FR-CVL) regeneration common converter
MCCB MC1 Inverter
R/L11 R2/L12
R2/L1
Three-phase S/L21 S2/L22
S2/L2 P/L+ P/+
AC power supply T/L31 T2/L32 *2
T2/L3 N/L- N/-
P24 PC
R/L11 SD SD
S/L21 *4
RDYA *6
T/MC1
RDYB X10 *3
400V
H H 22K/30K 150 380 322 122 22K/30K 150 380 305 105
37K/55K 400 620 250 135 37K/55K 400 620 250 135
FR-CV-(H)-AT (Unit mm)
Voltage/Capacity W H D D1 Voltage/Capacity W H D D1
W D1 D1 7.5K/11K 110 330 315 115
W 7.5K/11K/15K 130 330 320 120
200V
400V
D
15K 130 330 320 120
D
22K/30K 160 410 350 150 22K/30K 160 410 350 150
<FR-CVL>
FR-CVL (Unit mm)
D Voltage/Capacity W H D Voltage/Capacity W H D
7.5K/11K/15K 165 130 155 7.5K/11K 220 135 200
22K 165 140 155 15K 220 135 205
200V
H
37K 220 320 200 30K 245 185 220
55K 250 335 225 37K 245 230 265
55K 290 230 280
W
z Substantially suppresses power harmonics to realize the z Has the power regeneration function as standard.
equivalent capacity conversion coefficient K5=0 in the "Harmonic z Connects multiple inverters to enable common converter system
suppression guideline for consumers who receive high voltage or operation.
special high voltage".
z Specifications
200V 400V ∗1 The applicable capacity to the high power
Type FR-HC
7.5K 15K 30K 55K H7.5K H15K H30K H55K factor converter is the total capacity of the
Applicable inverter 3.7K to 7.5K to 15K to 30K to 3.7K to 7.5K to 15 to 30K to inverters.
capacity (*1) 7.5K 15K 30K 55K 7.5K 15K 30K 55K ∗2 The output voltage varies with the input voltage
Rated input voltage/ Three-phase 200V to 220V 50Hz Three-phase 380V to 460V 50/ value.
frequency 200V to 230V 60Hz 60Hz ∗3 Reactor 1 FR-HCL01, reactor 2 FR-HCL02 and
High power factor Rated input current (A) 33 61 115 215 17 31 57 110 outside box FR-HCB are supplied with a high
converter Rated output voltage (V) (*2) 293V to 335VDC 558V to 670VDC power factor converter (FR-HC)
30K 340 550 195 220 230 170 340 320 180
270 450 203
(FR-HCB)
(FR-HCL01) (FR-HCL02)
FR-HC
55K 480 700 250 210 260 225 430 470 360
H7.5K 220 300 190 160 150 100 240 220 160
Provided appliances
H15K 250 400 190 190 195 130 260 260 170 190 320 165
400V
H30K 340 550 195 220 215 140 340 310 180
H55K 480 700 250 280 255 190 400 380 285 270 450 203
High power factor converter Outside box Reactor 1, Reactor 2
H
H
H
59
Name (type) Specifications, Structure, etc.
z When driving the 400V class motor by the inverter, this filter suppresses the surge voltage generates at the motor terminal.
z This can be applied to FR-E740-5.5K to 15K.
z This can be applied to the non insulation-enhanced motor.
Features
z Specifications z Connection diagram
Type FR-BMF-H
K 7.5 15
Applicable motor within 100m
5.5 7.5 11 15
capacity (kW) ∗1 MCCB MC Inverter FR-BMF
Peripheral
Rated current (A) 17 31 Three-phase Motor
Devices
R U X
AC power S V Y IM
Overload current 150 60s, 200% 0.5s T W Z
rating∗2
supply
(inverse-time characteristics)
Rated input AC T* TH0
Three phase 380 to 480V
voltage∗2
Specifications
Permissible AC TH1
Standard
323 to 528V MC
voltage fluctuation∗2 ON OFF
Maximum frequency∗2 120Hz
PWM carrier frequency 2kHz or less∗3
MC
Protective structure
Open type (IP00) * Install a step-down transformer.
(JEM 1030)
Dimension
Drawings
Outline
Cooling system Self-cooling
Maximum wiring
100m or less
length
Approximate mass
5.5 9.5
Terminal Specification
(kg)
Terminal Connection
Explanation
Surrounding air
Diagram
-10°C to +50°C(non-freezing)
temperature
Environment
Operation panel
FR Configurator
Parameter unit
Maximum 1,000m above sea level, 5.9m/s2 or
Altitude/vibration less at 10 to 55Hz (directions of X, Y, Z
axes) ∗4
∗1 The applied motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
Surge voltage ∗2 The capacity depends on the specifications of the inverter (400V class) connected.
Parameter
∗3 The setting of Pr.72 PWM frequency selection should be 2kHz or less.
suppression filter ∗4 When using with the filter pack installed on the rear panel, do not install this combination on moving objects or places that have vibrations
List
(exceeding 1.96m/s2).
FR-BMF-H
K
z Outline dimension
Explanations
FR-BMF-H7.5K FR-BMF-H15K
Parameters
230 2- φ 6 hole 260 2- φ 10 hole
230
of
208
75 195 100
195
4-M5 4-M8 180 50 31
150 45 13.5
4-M4
Protective
Functions
6-M5
138
245
285
245
380
325
340
325
Options
480
500
457
Terminal layout
X Y Z TH0 TH1
149.5
Rating
Rating
plate
Instructions
7.5
370
6 6
80
7.5
33
420
Main terminal block (M4) Red White Blue Crimping terminal: 8-6
(U) (V) (W)
2.3 Control terminal block (M3) Isolation cap color
Compatibility
2.3
(Unit: mm)
Warranty
Inquiry
60
Peripheral devices/cable size list
FR-E720-0.75K 0.75 30AF 10A 30AF 10A S-N10 S-N10 2 2 0.75K 0.75K
FR-E720-1.5K 1.5 30AF 15A 30AF 15A S-N10 S-N10 2 2 1.5K 1.5K
FR-E720-2.2K 2.2 30AF 20A 30AF 15A S-N10 S-N10 2 2 2.2K 2.2K
FR-E720-3.7K 3.7 30AF 30A 30AF 30A S-N20, S-N21 S-N10 3.5 3.5 3.7K 3.7K
FR-E720-5.5K 5.5 50AF 50A 50AF 40A S-N25 S-N20, S-N21 5.5 5.5 5.5K 5.5K
FR-E720-7.5K 7.5 100AF 60A 50AF 50A S-N25 S-N25 14 8 7.5K 7.5K
FR-E720-11K 11 100AF 75A 100AF 75A S-N35 S-N35 14 14 11K 11K
FR-E720-15K 15 225AF 125A 100AF 100A S-N50 S-N50 22 22 15K 15K
FR-E740-0.4K 0.4 30AF 5A 30AF 5A S-N10 S-N10 2 2 H0.4K H0.4K
FR-E740-0.75K 0.75 30AF 5A 30AF 5A S-N10 S-N10 2 2 H0.75K H0.75K
Three-phase 400V
FR-E740-1.5K 1.5 30AF 10A 30AF 10A S-N10 S-N10 2 2 H1.5K H1.5K
FR-E740-2.2K 2.2 30AF 15A 30AF 10A S-N10 S-N10 2 2 H2.2K H2.2K
FR-E740-3.7K 3.7 30AF 20A 30AF 15A S-N10 S-N10 2 2 H3.7K H3.7K
FR-E740-5.5K 5.5 30AF 30A 30AF 20A S-N20, S-N21 S-N11, S-N12 3.5 2 H5.5K H5.5K
FR-E740-7.5K 7.5 30AF 30A 30AF 30A S-N20, S-N21 S-N20, S-N21 3.5 3.5 H7.5K H7.5K
FR-E740-11K 11 50AF 50A 50AF 40A S-N20, S-N21 S-N20, S-N21 5.5 5.5 H11K H11K
FR-E740-15K 15 100AF 60A 50AF 50A S-N25 S-N20, S-N21 8 8 H15K H15K
FR-E720S-0.1K 0.1 30AF 5A 30AF 5A S-N10 S-N10 2 2 0.4K*7 0.4K*7
Single-Phase 100V Single-Phase 200V
FR-E710W-0.2K 0.2 30AF 10A 30AF 10A S-N10 S-N10 2 2 1.5K*6, *7 −−− *8
FR-E710W-0.4K 0.4 30AF 15A 30AF 15A S-N10 S-N10 2 2 2.2K*6, *7 −−− *8
FR-E710W-0.75K 0.75 30AF 30A 30AF 20A S-N10 S-N10 2 2 3.7K*6, *7 −−− *8
Note
y When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to
the inverter type and cable and reactor according to the motor output.
y When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts
of the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
61
Selecting the rated sensitivity current for the earth leakage current breaker
Features
When using the earth leakage current breaker with the inverter Example
circuit, select its rated sensitivity current as follows,
independently of the PWM carrier frequency. 5.5mm2 5m 5.5mm2 50m
y Breaker designed for harmonic and surge suppression
Peripheral
ELB Noise
Devices
Rated sensitivity current IΔn≥10×(Ig1+Ign+Igi+Ig2+Igm) filter 3φ
y Standard breaker Inverter IM 200V2.2kW
Rated sensitivity current IΔn≥10×{Ig1+Ign+Igi+3X(Ig2+Igm)}
Ig1, Ig2: Leakage currents in wire path during commercial power supply Ig1 Ign Ig2 Igm
operation
Specifications
Igi
Standard
Ign : Leakage current of inverter input side noise filter
(Note) 1 Install the earth leakage breaker (ELB) on the input side of the inverter.
Igm : Leakage current of motor during commercial power supply operation
Igi : Leakage current of inverter unit 2 In the connection earthed-neutral system, the sensitivity current is blunt
against an earth (ground) fault in the inverter output side. Earthing (Grounding)
Example of leakage current of Example of leakage current must conform to the requirements of national and local safety regulations and
cable path per 1km during the of three-phase induction motor electrical codes. (NEC section 250, IEC 536 class 1 and other applicable
Dimension
Drawings
commercial power supply operation during the commercial standards)
Outline
when the CV cable is routed in power supply operation
metal conduit (200V 60Hz)
(200V 60Hz) zSelection example (in the case of the above figure)
Leakage currents (mA)
Leakage currents (mA)
120 1.0
0.7 Breaker Designed for
Terminal Specification
Terminal Connection
0.5
100 Harmonic and Surge Standard Breaker
Explanation
0.3
Diagram
80 0.2 Suppression
60 0.1 Leakage current 5m
33 × = 0.17
40
0.07
0.05
Ig1 (mA) 1,000m
0.03 Leakage current
20 0 (without noise filter)
Operation panel
FR Configurator
0.02
Parameter unit
Ign (mA)
0
2 3.5 8 142238 80150 0.1 0.2 0.75 2.2 5.5 11 20 Leakage current
1
5.5 30 60 100 0.4 1.5 3.7 7.5 15 Igi (mA)
Cable size (mm2) Motor capacity (kW) Leakage current 50m
33 × = 1.65
Ig2 (mA) 1,000m
Example of leakage current per 1km during Example of leakage current of three-
Motor leakage
0.18
Parameter
the commercial power supply operation phase induction motor during the
when the CV cable is routed in metal conduit commercial power supply operation current Igm (mA)
List
(Three-phase three-wire delta (Totally-enclosed fan-cooled Total leakage
3.00 6.66
connection 400V60Hz) type motor 400V60Hz) current (mA)
Rated sensitivity
2. 0 current (mA) 30 100
leakage currents (mA)
120
Explanations
(≥Ig×10)
Parameters
100 1. 0
of
80 0. 7
0. 5
60
0. 3
40
0. 2
20
Protective
Functions
0 0. 1
2 3.5 8 142238 80150 1.5 3.7 7.5 15
5.5 30 60100 2.2 5.5 11 20
Cable size (mm2) Motor capacity (kW)
For " " connection, the amount of leakage current is appox.1/3 of the above value.
Options
Instructions
Motor
Compatibility
Warranty
Inquiry
62
Precautions for Operation/Selection
Wiring
z Application of power to the output terminals (U, V, W) of the
inverter will damage the inverter. Therefore, fully check the
wiring and sequence to ensure that wiring is correct, etc. before
powering on.
z The terminals P/+, PR, P1, N/- are provided for connection of a
dedicated option. Connect only a dedicated option. Do not short
the frequency setting power supply terminal 10 and common
terminal 5 or the terminal PC and terminal SD.
Power supply
z When the inverter is connected
under a large-capacity power
transformer (500kVA or more Power
1500
Range
requiring
supply
transformer) or when a power system 1000 installation
of the reactor
capacity
capacitor is to be switched over, (kVA)
500
an excessive peak current may
0
flow in the power input circuit, Wiring length (m) 10
63
Precautions for selection Power transfer mechanism (reduction
gear, belt, chain, etc.)
Features
z When an oil-lubricated gear box, speed change/reduction gear
or similar device is used in the power transfer system, note that
z When operating a special motor or more than one motor in
continuous operation at low speed only may deteriorate oil
parallel with a single inverter, select the inverter capacity so that
lubrication, causing seizure. When performing fast operation at
1.1 times the total rated motor current is less than the rated
Peripheral
Devices
higher than 60Hz, fully note that such operation will cause
output current of the inverter.
strength shortage due to the noise, life or centrifugal force of the
z Setting 2kHz or more in Pr. 72 PWM frequency selection to perform
power transfer mechanism.
low acoustic noise operation with the surrounding air
Specifications
temperature exceeding 40°C (totally-enclosed structure is Instructions for overload operation
Standard
30°C), decrease the output current according to the rating table
z When performing operation of frequent start/stop of the inverter,
on page 7 . (Also change the Pr. 9 Electronic thermal O/L relay
rise/fall in the temperature of the transistor element of the
setting.)
inverter will repeat due to a repeated flow of large current,
Dimension
Drawings
Outline
Starting torque of the motor shortening the life from thermal fatigue. Since thermal fatigue is
related to the amount of current, the life can be increased by
z The start and acceleration characteristics of the motor driven by
reducing current at locked condition, starting current, etc.
the inverter are restricted by the overload current rating of that
Terminal Specification
Terminal Connection
Decreasing current may increase the life. However, decreasing
inverter. Generally the torque characteristic is less than when
Explanation
Diagram
current will result in insufficient torque and the inverter may not
the motor is started by a commercial power supply. If torque
start. Therefore, choose the inverter which has enough
boost adjustment, Advanced magnetic flux vector control, or
allowance for current.
General-purpose magnetic flux vector control cannot provide
Operation panel
FR Configurator
Parameter unit
enough torque when a large starting torque is necessary, select
the inverter of one rank higher capacity or increase the
capacities of both the motor and inverter.
Parameter
Acceleration/deceleration times
List
z The acceleration/deceleration time of the motor depends on the
motor-generated torque, load torque and moment of inertia of
Explanations
Parameters
the load (J).
z When the torque limit function or stall prevention function is
of
activated during acceleration/deceleration, increase the
acceleration/deceleration time as the actual time may become
Protective
Functions
longer.
z To decrease the acceleration/deceleration time, increase the
torque boost value (setting of a too large value may activate the
stall prevention function at a start, longer the acceleration time),
use the advanced magnetic flux vector control or general-
Options
purpose magnetic flux vector control or increase the inverter
and motor capacities. To decrease the deceleration time, it is
necessary to add optional brake resistor MRS type, MYS type,
Instructions
or FR-ABR (for the 0.4K or more), the brake unit (FR-BU2),
power regeneration common converter (FR-CV), or a similar
device to absorb braking energy.
Motor
Compatibility
Warranty
Inquiry
64
Precautions for Peripheral Device Selection
65
Earth (Ground) Leakage currents
When the inverter is run in the low acoustic noise mode, more Capacitances exist between the inverter I/O cables, other cables
Features
leakage currents occur than in the non-low acoustic noise mode and earth and in the motor, through which a leakage current flows.
due to high-speed switching operation. Be sure to earth (ground) Since its value depends on the static capacitances, carrier
the inverter and motor before use. In addition, always use the frequency, etc., low acoustic noise operation at the increased
earth (ground) terminal of the inverter to earth (ground) the carrier frequency of the inverter will increase the leakage current.
Peripheral
Devices
inverter. (Do not use the case and chassis) Therefore, take the following measures. Select the earth leakage
current breaker according to its rated sensitivity current,
Noise independently of the carrier frequency setting. (Refer to page 62)
Specifications
When performing low-noise operation at higher carrier frequency, To-earth (ground) leakage currents
Standard
electromagnetic noise tends to increase. Therefore, refer to the Type Influence and Measures
following measure example and consider taking the measures. y Leakage currents may flow not only into the inverter's
Depending on the installation condition, the inverter may be own line but also into the other line through the earth
Dimension
affected by noise in a non-low noise (initial) status. (ground) cable, etc. These leakage currents may
Drawings
Outline
z The noise level can be reduced by decreasing the carrier operate earth (ground) leakage circuit breakers and
earth leakage relays unnecessarily.
frequency (Pr. 72).
z Countermeasures
z As measures against AM radio broadcasting noise, radio noise
Terminal Specification
Influence and y If the carrier frequency setting is high, decrease the Pr.
Terminal Connection
filter FR-BIF produces an effect.
Explanation
measures 72 PWM frequency selection setting.
Diagram
z As measures against sensor malfunction, line noise filter FR- Note that motor noise increases. Select Pr. 240 Soft-
BSF01, FR-BLF produces an effect. PWM operation selection to make the sound inoffensive.
z As measures against induction noise from the power cable of y By using earth leakage circuit breakers designed for
Operation panel
FR Configurator
Parameter unit
the inverter, an effect is produced by putting a distance of 30cm harmonic and surge suppression in the inverter's own
line and other line, operation can be performed with the
(at least 10cm) or more and using a twisted pair shielded cable
carrier frequency kept high (with low noise).
as a signal cable. Do not earth (ground) shield but connect it to
signal common cable. Inverter
Parameter
Power NV1 Motor
Noise reduction examples
List
supply C
FR- BLF FR- BLF
Undesirable Leakage
Install common mode filter Decrease Install common mode filter breaker
FR- BSF01 FR- BSF01 C
on inverter input side. Enclosure carrier frequency
on inverter output side. current path
NV2 Motor
Inverter
FR- FR-
Explanations
power C
Parameters
supply BSF01 Inverter BSF01 IM Motor Leakage
breaker
Install capacitor type FR-BIF filter Use 4-core cable for motor
FR-
of
on inverter input side. power cable and use one
BIF
Separate inverter and power
line by more than 30cm (at
cable as earth (ground) cable.
Line leakage current
Use a twisted pair shielded cable
least 10cm) from sensor circuit.
Control
power
Power
supply
Sensor
Type Influence and Measures
supply for sensor
• This leakage current flows via a static capacitance
Protective
Functions
Do not earth (ground) Do not earth (ground) shield but
enclosure directly. connect it to signal common cable.
Do not earth (ground) control cable. between the inverter output cables.
• The external thermal relay may be operated
unnecessarily by the harmonics of the leakage current.
When the wiring length is long (50m or more) for the
Options
400V class small capacity model (7.5kW or less), the
external thermal relay is likely to operate unnecessarily
because the ratio of the leakage current to the rated
motor current increases.
Influence and
Instructions
z Countermeasures
measures
• Use Pr.9 Electronic thermal O/L relay.
• If the carrier frequency setting is high, decrease the Pr.
72 PWM frequency selection setting.
Note that motor noise increases. Select Pr. 240 Soft-PWM
Motor
temperature.
Line-to-line static
capacitances
Line-to-line leakage currents path
Inquiry
66
zHarmonic suppression guideline For compliance to "Harmonic suppression guideline of the
transistorized inverter (input current of 20A or less) for consumers
Harmonic currents flow from the inverter to a power receiving point other than specific consumers" published by JEMA.
via a power transformer. The harmonic suppression guideline was
established to protect other consumers from these outgoing Input
Target
harmonic currents. Power Countermeasures
Capacity
The three-phase 200V input specifications 3.7kW or less (single- Supply
Connect the AC reactor or DC reactor
phase 200V power input model 2.2kW or less, single-phase 100V Single-phase
0.75kW or less recommended in a catalog or an
power input model 0.75kW) are previously covered by "Harmonic 100V
instruction manual.
suppression guideline for household appliances and general- Reference materials
Single-phase
purpose products" and other models are covered by "Harmonic 2.2kW or less
200V y "Harmonic suppression guideline of
suppression guideline for consumers who receive high voltage or the general-purpose inverter (input
special high voltage". However, the transistorized inverter has current of 20A or less)"
Three-phase JEM-TR226 (revised in Dec. 2003):
been excluded from the target products covered by "Harmonic 3.7kW or less
200V Japan Electrical Manufacturer's
suppression guideline for household appliances and general-
Association
purpose products" in January 2004 and "Harmonic suppression
zCalculation of outgoing harmonic current
guideline for household appliances and general-purpose products"
was repealed on September 6, 2004. Outgoing harmonic current = fundamental wave current (value converted
All capacity and all models of general-purpose inverter used by from received power voltage) × operation ratio × harmonic content
yOperation ratio: Operation ratio = actual load factor operation
specific consumers are covered by "Harmonic suppression
time ratio during 30 minutes
guideline for consumers who receive high voltage or special high
yHarmonic content: Found in Table.
voltage".
y "Harmonic suppression guideline for consumers who receive high
voltage or special high voltage" Table 1: Harmonic Contents (Values at the fundamental current of 100%)
This guideline sets forth the maximum values of harmonic currents
Reactor 5th 7th 11th 13th 17th 19th 23rd 25th
outgoing from a high-voltage or especially high-voltage consumer Not used 65 41 8.5 7.7 4.3 3.1 2.6 1.8
who will install, add or renew harmonic generating equipment. If any Used
Three-phase 38 14.5 7.4 3.4 3.2 1.9 1.7 1.3
of the maximum values is exceeded, this guideline requires that (AC side)
bridge
consumer to take certain suppression measures. (Capacitor
Used
30 13 8.4 5.0 4.7 3.2 3.0 2.2
Users who use models other than the target models are not covered (DC side)
smoothing)
by the guideline. However, we ask to connect an AC reactor or a DC Used
28 9.1 7.2 4.1 3.2 2.4 1.6 1.4
(AC, DC sides)
reactor as before to the users who are not covered by the guideline.
Single-phase
For compliance to the harmonic suppression guideline for Not used 50 24 5.1 4.0 1.5 1.4 - -
bridge
consumers who receive high voltage or special high voltage (Capacitor Used
6.0 3.9 1.6 1.2 0.6 0.1 - -
smoothing) (AC side) *
Input ∗ The harmonic contents for "single-phase bridge/with reactor" in the table 4 are
Target
Power Countermeasures values when the reactor value is 20%. Since a 20% reactor is large and considered
Capacity to be not practical, harmonic contents when a 5% reactor is used is written in the
Supply technical data JEM-TR201 of The Japan Electrical Manufacturers' Association and
Make a judgment based on "Harmonic this value is recommended for calculation for the actual practice.
suppression guideline for consumers who
Table 2: Rated Capacities and Outgoing Harmonic Currents for Three-phase
receive high voltage or special high voltage"
Inverter Drive
issued by the Japanese Ministry of Economy,
Trade and Industry (formerly Ministry of Outgoing Harmonic Current Converted from
Converted from 6.6kV (mA)
Fundamental Wave Current
Rated
6.6kV (mA)
International Trade and Industry) in Current [A]
(No reactor, 100% operation ratio)
Motor kW
Applied
Three-phase Jan. 2004 Japan Electrical Manufacturer's 1.5 5.50 2.75 167 1.95 108.6 68.47 14.20 12.86 7.181 5.177 4.342 3.006
2.2 7.93 3.96 240 2.81 156.0 98.40 20.40 18.48 10.32 7.440 6.240 4.320
400V Association
3.7 13.0 6.50 394 4.61 257.1 161.5 33.49 30.34 16.94 12.21 10.24 7.092
y "Calculation method of harmonic current of 5.5 19.1 9.55 579 6.77 376.1 237.4 49.22 44.58 24.90 17.95 15.05 10.42
the general-purpose inverter used by 7.5 25.6 12.8 776 9.07 504.4 318.2 65.96 59.75 33.37 24.06 20.18 13.97
specific consumers" 11 36.9 18.5 1121 13.1 728.7 459.6 95.29 86.32 48.20 34.75 29.15 20.18
15 49.8 24.9 1509 17.6 980.9 618.7 128.3 116.2 64.89 46.78 39.24 27.16
JEM-TR201 (revised in Dec. 2003): Japan
Electrical Manufacturer's Association
Japan Electrical Manufacturer's Association
67
Application to Motor
Features
The motor operated by the inverter has a limit on the continuous The machine-installed motor operated by the inverter may be slightly
operating torque since it is slightly higher in temperature rise than the greater in vibration than the one driven by the commercial power supply.
one operated by a commercial power supply. At a low speed, reduce The possible causes of vibration are as follows.
Peripheral
Devices
the output torque of the motor since the cooling effect decreases. 1. Vibration due to imbalance of the rotator itself including the machine
When 100% torque is needed continuously at low speed, consider 2. Resonance due to the natural oscillation of the mechanical system.
using a constant-torque motor. (Refer to page 69) Caution is required especially when the machine used at constant
speed is operated at variable speed. The frequency jump function
Specifications
Torque characteristic
Standard
allows resonance points to be avoided during operation.(During
The motor operated by the inverter may be less in motor torque acceleration/deceleration, the frequency within the set area is
(especially starting torque) than the one driven by the commercial passed through.) An effect is also produced if Pr. 72 PWM frequency
power supply. It is necessary to fully check the load torque selection is changed. When a two-pole motor is operated at higher
Dimension
than 60Hz, caution should be taken since such operation may cause
Drawings
characteristic of the machine.
Outline
abnormal vibration.
Motor torque
Terminal Specification
Terminal Connection
When the Mitsubishi standard squirrel-cage motor (SF-JR, 4-pole) and inverter of the same capacity are used, the torque characteristics are as shown
Explanation
Diagram
below.
Operation panel
FR Configurator
Parameter unit
Advanced magnetic flux vector control
200 130
Parameter
Maximum torque for short time 220V
(5.5K to 15K)
List
150 85
Output torque (%)
200V
100 80
95
85 70
80 65
Explanations
Parameters
70 60 Continuous operation torque *1
63 Continuous operation torque *1 53 (0.1K to 3.7K)
of
(0.1K to 3.7K)
50
45 Continuous operation torque *1 (5.5K)
Continuous operation torque *1 (5.5K) 38
Continuous operation torque *1 (7.5K to 15K) Continuous operation torque *1 (7.5K to 15K)
0 0
Protective
Functions
0.5 3 6 20 30 40 60 Output frequency (Hz) 120 0.5 3 6 20 30 40 50 Output frequency (Hz) 120
Options
When boost is increased
Maximum torque at initial setting (boost setting)
220V
150 Maximum torque When boost is increased
Instructions
V/F control ∗4
140 for short time Maximum torque at initial setting (boost setting)
Output torque (%)
200V 130
120 Maximum torque
Continuous operation torque *1 Continuous operation
100 torque *1 for short time
90 85
80 75
70 70
Motor
65
50 45
35 38
30 30
25
Compatibility
3 6 20 30 60 120 3 6 20 30 50 120
Output frequency (Hz) Output frequency (Hz)
∗1 Continuous operation torque is for checking the limit of permissible load torque when using the motor within the permissible ambient temperature, and is not
the motor output torque itself. Maximum torque for short time is the amount of torque a motor can output.
Warranty
Continuous operation torque of a single-phase 100V power input model is 90% of the continuous operation torque indicated above.
∗2 Depending on the motor capacity or the number of motor poles, the operation at 60Hz or more may not be performed. Make sure to check the permissible
maximum operating frequency of the motor.
∗3 A 60Hz torque reference indicates that the rated torque of the motor run at 60Hz is 100%, and a 50Hz torque reference indicates that the rated torque of the
Inquiry
68
Application to constant-torque motors
SF-HRCA type Standard specifications
(Advanced magnetic flux vector (indoor type)
control)
z Continuous operation with 100% torque even at low speed of 3Hz is Output Number Frequency
Common Specifications
possible (kW) of Poles Range
Load torque is not need to be reduced even at a low speed and 0.2 Standard frequency 60Hz
constant torque (100% torque) continuous operation is possible
0.4 z rotation direction (CCW) is
within the range of speed ratio 1/20 (3 to 60Hz). (The characteristic
0.75 counterclockwise when
of motor running at 60Hz or more is that output torque is constant.)
1.5 viewed from the motor end
Continuous operation torque of a single-phase 100V power input 3 to 120Hz
2.2 zLead wire
model is 90% of the indicated value.
z Installation size is the same as that of the standard motor 3.7 4 3.7kW or less ..... 3 wires
Note that operation characteristic in the chart below can not be 5.5 5.5kW or more ... 6 or 12
obtained if V/F control is employed. 7.5 wires
11 zSurrounding air temperature:
3 to 100Hz 40°C maximum
15
Protective structure is IP44
z Torque characteristic (during advanced magnetic flux vector control, and initial value for other parameters)
Maximum torque for short time Maximum torque for short time
Output torque (%) (60 Hz is standard)
150 150
220V 220V
0 0
0.5 3 60 120 0.5 3 60 100
Output frequency (Hz)
Output frequency (Hz)
* Please contact us separately when 150% or more of maximum torque for short time is necessary.
y When rapid acceleration/deceleration is needed, the inverter capacity may need to be one rank higher.
y When two or more motors are operated in parallel, torque imbalance is likely to occur as motor slip is smaller than that of the standard motor.
69
Application to geared motor
GM-S, GM-D, GM-SY, GM-HY2 series Standard specifications
Features
z Wide constant torque range even with the standard type(when using
Available
advanced magnetic flux vector control)
Frequency Range Constant Torque
Load torque is not need to be reduced even at a low speed and (base frequency
Inverter Output Number Range When Using
Peripheral
Devices
constant torque (100% torque) continuous operation is possible Type (kW) of Poles 60Hz) Advanced Magnetic
within the range of speed ratio 1/20 (3 to 60Hz). (0.1K to 0.75K) Grease Oil Flux Vector Control
z Wide speed control range Lubrication Lubrication
The motor can be used in the wide speed deviation range of 3 to 3 to 60Hz
Specifications
GM-S
Standard
120Hz 0.1 to 3 to (0.1kW to 0.75kW)
GM-SY
The characteristic of motor running at 60Hz or more is that output 2.2 120Hz 6 to 60Hz
GM-HY2
torque is constant. (0.1K to 0.75K) (1.5kW, 2.2kW)
Note that operation characteristic in the chart below can not be 0.4 to
4 3 to
obtained if V/F control is employed.
Dimension
2.2 25 to 3 to 60Hz
Drawings
Outline
120Hz
3.7 120Hz (0.4kW, 0.75kW)
GM-D
5.5 6 to 60Hz
25 to (1.5kW, 7.5kW)
7.5
Terminal Specification
Terminal Connection
115Hz
Explanation
Diagram
zTorque characteristic (range during advanced magnetic flux vector control)
Operation panel
FR Configurator
Parameter unit
250.0 250.0
Output torque (%) (60 Hz is standard)
1.5kW to 3.7kW
Maximum torque
200.0
Parameter
Maximum torque 200.0
for short time
List
for short time 5.5kW, 7.5kW
170.0
150.0 150.0
Explanations
Parameters
100.0 100.0
of
70.0 70.0
50.0 50.0 50.0 1.5kW to 3.7kW 50.0
30.0 5.5kW, 7.5kW Continuous operation
Continuous operation torque
torque
Protective
Functions
0.0 0.0
0 36 20 40 60 80 100 120 0 3610 20 40 60 80 100 120
Output frequency (Hz)
Output frequency (Hz)
Options
Instructions
Motor
Compatibility
Warranty
Inquiry
70
Inverter-driven 400V class motor
When driving a 400V class motor by the inverter, surge voltages attributable to the wiring constants may occur at the motor terminals, deteriorating the
insulation of the motor. In such a case, consider taking the following measures.
(1) Rectifying the motor insulation
1. Use a "400V class inverter driven insulation-enhanced motor".
Note: The four poles of the Mitsubishi standard motor (SF-JR, SB-JR) have the 400V class inverter driving insulation enhanced feature.
2. For the dedicated motor such as the constant-torque motor and low-vibration motor, use the "inverter-driven, dedicated motor".
(2) Suppressing the surge voltage on the inverter side
Connect a filter on the secondary side of the inverter to suppress a surge voltage so that the terminal voltage of the motor is 850V or less. When
driving by the Mitsubishi inverter, connect an optional surge voltage suppression filter (FR-ASF-H/FR-BMF-H) on the inverter output side.
71
Main Differences and Compatibilities with the FR-E500 series
Features
V/F control General-purpose magnetic flux vector control
Control method
General-purpose magnetic flux vector control Advanced magnetic flux vector control
Optimum excitation control
Torque boost (Pr. 0) initial value FR-E720-1.5K to 3.7K: 4%
FR-E520-1.5K to 7.5K: 6% FR-E720-5.5K, 7.5K: 3%
Peripheral
Devices
FR-E540-1.5K to 3.7K: 6% FR-E740-1.5K to 3.7K: 4%
FR-E540-5.5K, 7.5K: 4% FR-E740-5.5K, 7.5K: 3%
DC injection brake operation voltage (Pr. 12) initial value
0.4K to 7.5K: 6% 0.4K to 7.5K: 4%
Specifications
Parameter number change
Standard
Frequency at 5V (10V) input (Pr. 38 ) (Pr. 125 Terminal 2 frequency setting gain frequency)
Frequency at 20mA input frequency (Pr. 39 ) (Pr. 126 Terminal 4 frequency setting gain frequency)
Second electronic thermal O/L relay (Pr. 48 ) (Pr. 51 Second electronic thermal O/L relay)
Shortest acceleration/deceleration mode (Pr. 60 ) (Pr. 60 Energy saving control selection)
(Pr. 292 Automatic acceleration/deceleration)
Dimension
Drawings
Outline
Reverse rotation from the inverter operation panel After setting "1" in Pr. 40 RUN key rotation direction
Press . selection , press .
FM terminal function selection (Pr. 54) setting
Terminal Specification
Terminal Connection
0: Output frequency (initial value), 1: Output frequency (initial value),
Explanation
Diagram
1: Output current, 2: Output current,
2: Output voltage 3: Output voltage
Second applied motor
Pr. 450 Second applied motor
Pr. 71 = 100 to 123
Operation panel
FR Configurator
Parameter unit
Terminal 2 0 to 5V, 0 to 10V selection (Pr. 73 ) setting Pr. 73 Analog input selection
Changed/cleared 0: 0 to 5V (initial value), 0: 0 to 10V
functions 1: 0 to 10V 1: 0 to 5V (initial value)
Operation mode selection (Pr. 79 )
Initial value 1: PU operation mode Initial value 0: External operation mode is selected at
Parameter
power ON
List
Setting 8: Operation mode switching by external signal Setting 8: deleted (X16 signal is used instead)
Setting General-purpose magnetic flux vector
Pr. 80 ≠ 9999 Pr. 80 ≠ 9999, Pr. 81 ≠ 9999, Pr. 800 = 30
User group 1 (16), user group 2 (16) User group (16) only, setting methods were partially changed
Explanations
Parameters
(Pr. 160, Pr. 173 to Pr. 175 ) (Pr. 160, Pr. 172, Pr. 173 )
Input terminal function selection (Pr. 180 to Pr. 183 ) setting Pr. 178 to Pr. 184 Input terminal function selection setting
of
5: MRS signal (output stop) 5: JOG signal (Jog operation selection)
6: STOP signal (start self-holding selection) 6: None
24: MRS signal (output stop)
Protective
Functions
25: STOP signal (start self-holding selection)
Long wiring mode Setting is unnecessary
(Pr. 240 setting 10, 11) (Pr. 240 setting 0, 11 are deleted)
Cooling fan operation selection (Pr. 244 ) initial setting
0: Cooling fan operates in power-on status. 1: Cooling fan on/off control valid
Stop selection (Pr. 250 ) setting increments
Options
1s 0.1s
RS-485 communication control source from the PU connector Network operation mode (PU operation mode as FR-
PU operation mode E500 when Pr. 551 = 2)
Earth (ground) fault detection
Instructions
400V class: Detects always 400V class: Detects only at a start
Inrush current limit circuit Provided for the 200V class 2.2K or more and 400V class Provided for the all capacity
Fixed terminal block (can not be removed) Removable terminal block
Control terminal block
(Phillips screw M2.5) (Flathead screw M2 (M3 for terminal A, B, and C)
Operation panel Removable operation panel (PA02) Integrated operation panel (can not be removed)
FR-PU07
Motor
72
Warranty
[Coverage]
(1) Diagnosis of failure
As a general rule, diagnosis of failure is done on site by the customer.
However, Mitsubishi or Mitsubishi service network can perform this service for an agreed upon fee upon the customer's
request.
There will be no charges if the cause of the breakdown is found to be the fault of Mitsubishi.
(2) Breakdown repairs
There will be a charge for breakdown repairs, exchange replacements and on site visits for the following four conditions
even in gratis warranty period, otherwise there will be no charge.
1)Breakdowns due to improper storage, handling, careless accident, software or hardware design by the customer.
2)Breakdowns due to modifications of the product without the consent of the manufacturer.
3)Breakdowns resulting from using the product outside the specified specifications of the product.
4)Breakdowns that are outside the terms of warranty.
Since the above services are limited to Japan, diagnosis of failures, etc. are not performed abroad.
If you desire the after service abroad, please register with Mitsubishi. For details, consult us in advance.
4. Terms of delivery
In regard to the standard product, Mitsubishi shall deliver the standard product without application settings or adjustments
to the customer and Mitsubishi is not liable for on site adjustment or test run of the product.
73
International FA Center
Features
Peripheral
Devices
UK FA Center
European FA Center
Central and Eastern Europe
FA Center Korean North American FA Center
Specifications
FA Center
Standard
Beijing FA Center
Tianjin FA Center
Shanghai FA Center
Guangzhou FA Center Taiwan FA Center
Hong Kong FA Center
Dimension
Drawings
Outline
Thailand FA Center
ASEAN FA Center
Terminal Specification
Terminal Connection
Explanation
Diagram
Operation panel
FR Configurator
Parameter unit
Parameter
List
zNorth American FA Center zASEAN FA Center
Explanations
MITSUBISHI ELECTRIC AUTOMATION, INC. MITSUBISHI ELECTRIC ASIA PTE, LTD.
Parameters
500 Corporate Woods Parkway, Vernon Hills, IL 60061 U.S.A 307 Alexandra Road #05-01/02, Mitsubishi Electric Building,
of
TEL. +1-847-478-2100 FAX. +1-847-478-0327 Singapore 159943
TEL. +65-6470-2480 FAX. +65-6476-7439
zTaiwan FA Center
SETSUYO ENTERPRISE CO., LTD. zHong Kong FA Center
Protective
Functions
6F No.105, Wu Kung 3rd RD, Wu-Ku Hsiang Taipei Hsien, MITSUBISHI ELECTRIC AUTOMATION (Hong Kong) LTD.
248, Taiwan 10th Floor, Manulife Tower, 169 Electric Road, North Point, Hong Kong
TEL. +886-2-2299-2499 FAX. +886-2-2299-2509 TEL.+852-2887-8870 FAX. +852-2887-7984
Options
MITSUBISHI ELECTRIC AUTOMATION KOREA CO., LTD. MITSUBISHI ELECTRIC EUROPE B. V. GERMAN BRANCH
B1F,2F, 1480-6, Gayang-Dong, Gangseo-Gu, Seoul, 157-200, Gothaer Strasse 8, D-40880 Ratingen, Germany
Korea TEL. +49-2102-486-0 FAX. +49-2102-486-1120
Instructions
TEL. +82-2-3660-9607 FAX. +82-2-3664-0475
zUK FA Center
zBeijing FA Center MITSUBISHI ELECTRIC EUROPE B. V. UK BRANCH
MITSUBISHI ELECTRIC AUTOMATION (SHANGHAI) LTD. Travellers Lane, Hatfield, Hertfordshire, AL10 8XB, U.K.