Professional Documents
Culture Documents
A6V101025339 en
A6V101025339 en
A6V101025339 en
Revision 1.40.xxx.1
User Guide
3
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2.3.6 Deleting a PTEC Point ...........................................................................40
2.4 Using the Point Editor .......................................................................................... 40
2.4.1 Point User Interface ...............................................................................40
2.4.2 Discovering Points .................................................................................41
2.4.3 Adding Points ........................................................................................42
2.4.4 Adding Points to the N4 Database .........................................................43
2.4.5 Using the Point Editor Application ..........................................................43
2.4.6 Editing Points in PX Controllers..............................................................43
2.4.7 Modifying a Point in Another Tool...........................................................44
2.4.8 Deleting a Point .....................................................................................44
2.5 Troubleshooting................................................................................................... 46
2.5.1 Running Sie Update Db does not cause Point and PPCL Editors to appear
..............................................................................................................46
Uninstalling Siemens Workbench ................................................................... 49
4
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
How to Use This Manual
Document Conventions
The following table lists conventions to help you use this manual in a quick and
efficient manner.
Convention Examples
Numbered Lists (1, 2, 3…) indicate a 1. Turn OFF power to the field panel.
procedure with sequential steps. 2. Turn ON power to the field panel.
3. Contact the local Siemens Solution Partner, Authorized
TALON Dealer.
Conditions that must be completed or met ⊳Composer software is properly installed.
before beginning a task are designated with a ⊳A Valid license is available.
⊳. 1. Select Start > Programs > Siemens > GMS >
Intermediate results (what will happen Composer.
following the execution of a step), are
⇨The Project Management window displays.
designated with a ⇨.
2. Open an existing project or create a new one.
Results, which inform the user that a task was
completed successfully, are designated with a ⇨The project window displays.
⇨.
Actions that should be performed are specified Type F for Field panels.
in boldface font. Click OK to save changes and close the dialog box.
Error and system messages are displayed in The message Report Definition successfully
Courier New font. renamed displays in the status bar.
New terms appearing for the first time are The field panel continuously executes a user-defined set
italicized. of instructions called the control program.
This symbol signifies Notes. Notes provide additional
information or helpful hints.
Cross references to other information are For more information on creating flowcharts, see
indicated with an arrow and the page number, Flowcharts [→92].
enclosed in brackets: [→92]
Placeholders indicate text that can vary based Type A C D H [username] [field panel #].
on your selection. Placeholders are specified
in bold print, and enclosed with brackets [ ].
5
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
How to Use This Manual
Safety Symbols
The following table lists the safety symbols used in this manual to draw attention to
important information.
How to Contact Us
Your feedback is important to us. If you have comments about this document, please
submit them to the following email address:
SBT_technical.editor.us.sbt@siemens.com.
6
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Overview
Network and System Requirements
Overview
The Siemens TALON N4 Appliance has been designed to allow point and PPCL
editing for Siemens Programmable TECs and TC BACnet field panels using the
Niagara 4 platform.
Hardware
l Compatible with the TNM-800.
l Compatible with Talon N4 Supervisor.
l Compatible with Talon PX versions 3.3 and above.
System Recommendations
For optimized system performance, Siemens recommends the following tuning
policies:
7
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Overview
N4 Appliance Compatibility
N4 Appliance Compatibility
Version 1.40.101.1 of the N4 Appliance is compatible with Niagara N4 Version
4.8.110.32.
8
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing Siemens Workbench
1
1 Installation
Use the following workflow to install Siemens Workbench and set up system-related
parameters:
Installation Step
1 Installing Siemens Workbench [➙ 9] and Obtaining a License [➙ 10]
2 Installing and Configuring a Siemens N4 Appliance Station and Platform [➙ 12]
l Installing the N4 Appliance [➙ 12]
l Installing a New Station [➙ 15]
l Adding a BACnet network and Siemens utilities to the station [➙ 18]
3 Identifying and Configuring the Station Communication Links
l Configuring a Niagara Supervisor BACnet/IP Links [➙ 22]
l Configuring N4 JACE station BACnet/IP Links [➙ 19]
l Configuring N4 JACE station BACnet MS/TP Links [➙ 21]
4 Configuring the Required Networks [➙ 26]
l Configuring the BACnet Local Device [➙ 24]
l Configuring a BACnet/IP Network [➙ 26]
l Configuring a BACnet MS/TP Network [➙ 27]
9
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing Siemens Workbench
– 10 characters
– One lowercase character
– One uppercase character
– One digit
8. If desired, select one or both check boxes to create Start Menu or Desktop
shortcuts and click Next.
a A progress bar displays during the installation.
a A confirmation message displays with the following options selected:
– Launch Workbench.
– Install and Start Platform Daemon.
– Copy Niagara Daemon Data From Prior Version (only displays if a prior version
exists).
9. Clear the check box(es) for any options that should not run and click Finish.
NOTICE
If a previous version of Siemens Workbench was installed and you are connected to
the Internet, you will automatically receive a new license.
In this case, start Siemens Workbench and skip to the procedure Installing and
Configuring a Siemens N4 Appliance Station and Platform.
2. Call the Siemens number listed in the dialog box and provide the information
displayed, or download/email the license from your Niagara Central licensing
portal.
3. Once you receive the license *.zip file, save it to your computer and extract its
contents.
10
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing Siemens Workbench
1
4. Navigate to the location where Siemens Workbench is installed and open the
security folder.
a The default location is C:\Siemens\SiemensWorkbench-4.8 .x.x.
5. Copy the *.license file(s) into the target host’s licenses folder.
Note: You can rename any license file without affecting it. For example, you can
change the name from Tridium.license to MyHost2.license to keep from overwriting
an existing license file with the same name.
6. Copy any *.certificate files into the certificates folder. These files come with the
License file.
7. Start Siemens Workbench.
11
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
NOTE:
Since TNM Niagara stations may connect to devices using both BACnet/IP and
BACnet MS/TP ports, in some cases, more than one example in this section may
apply.
The devices outlined in this section are examples only. They are provided to illustrate
the types of devices that could be included on various types of networks.
12
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
1
Niagara Supervisor
A Niagara Supervisor typically has a single BACnet/IP link, as shown in the following
figure.
For this type of network layout, follow the instructions in the section Configuring a
Niagara Supervisor BACnet/IP Links [➙ 22].
13
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
For this type of network layout, follow the instructions in the section Configuring TNM
BACnet/IP Links.
14
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
1
For this type of network layout, follow the instructions in the section Configuring TNM
BACnet MS/TP Links.
1. From the Windows Start menu, select Programs > Siemens Workbench 4.8 .x.x >
Install Platform Daemon.
a The Platform Daemon runs and Siemens Workbench detects any new
module(s).
15
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
4. If any stations are currently running on the host, open Application Director, stop the
station(s) and disable the Auto-Start function.
16
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
1
17
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
3. Click Finish to start the transfer and click Close when the station transfer is
complete.
4. If prompted, select Yes to start Application Director. Otherwise, manually navigate
to Application Director and start the station.
5. In the Nav pane, right-click on My host and select Open Station to start the
Siemens TALON N4 Appliance station in Siemens N4 Workbench.
6. Enter the station credentials to logon.
– Enter admin for the user name.
– Use the password selected when the station was created.
a Installation is of Niagara Supervisor is complete.
– In the Palette pane, click Open and type bacnet in the filter field.
– Select the bacnet module and click OK.
– Drag-and-drop BacnetNetwork from the Palette pane onto Drivers in the Nav
pane and click OK.
4. Do the following to add the Siemens Utilities Service:
– In the Palette pane, click Open and type sie in the filter field.
– Select the SieUtilities module and click OK.
– Drag-and-drop SieUtilitiesService from the Palette pane onto Services in the
Nav pane and click OK.
18
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
1
l In the Nav pane, right-click on the station and select Save station.
a The configuration is complete and saved.
Parameter Notes
Network Number The number of the BACnet network to which the station’s IP port is
connected.
Adapter The IP network port used to connect to the BACnet network.
19
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
Parameter Notes
l Select dm0 for the port marked Pri on the TNM enclosure.
l Select dm1 for the port marked Sec on the TNM enclosure.
If an expected port is missing from the drop-down list, use
Platform/TCP/IP Configuration to setup network ports.
Enabled Enables or disables the communication link.
Routing_Enabled l If the TNM will have BACnet MS/TP devices connected to any of
its MS/TP ports (see the figure TNM with BACnet MS/TP Link(s))
and communication between BACnet/IP devices and the
connected BACnet MS/TP devices is required, set
Routing_Enabled to true. When set to true, the TNM routes
messages between the BACnet/IP port and the MS/TP port(s).
l If the TNM will not have BACnet MS/TP devices connected to any
of its MS/TP ports (see the figure TNM with BACnet MS/tP Link(s))
or communication between BACnet/IP devices and the connected
BACnet MS/TP devices is prohibited, set Routing_Enabled to
false.
Maintain_Routing_Enabled l When set to false, the station automatically disables routing in the
presence of routing errors, such as router loops.
l When set to true, the station continues to attempt to route
messages even when routing errors are detected.
20
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
1
Parameter Notes
Network Number The number of the BACnet network to which the station’s IP port is
connected.
Port Name The MS/TP network port used to connect to the BACnet network. Enter
COM1 or COM2, based on the port markings on the TNM enclosure.
Baud Rate The bit rate of the MS/TP network.
21
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
Parameter Notes
Mstp Address The MS/TP network MAC address for the TNM on the connected
MS/TP network. Zero (0) is usually a safe choice for this.
Enabled Enables or disables the communication link.
Routing_Enabled l If BACnet MS/TP devices will be connected to more than one
MS/TP port of the TNM (see the figure TNM with BACnet MS/TP
Link(s)), and communication between BACnet MS/TP devices on
different ports is required, set Routing_Enabled to true. When set
to true, the TNM routes messages between the BACnet MS/TP
ports.
l If the TNM will have BACnet MS/TP devices connected to only a
single MS/TP port (see the figure TNM with BACnet MS/TP
Link(s)) use the Routing_Enabled setting determined in the section
Configuring TNM BACnet/IP Links.
Maintain_Routing_Enabled l False
The station automatically disables routing in the presence of
routing errors, such as router loops.
l True
The station continues to attempt to route messages even when
routing errors are detected.
Parameter Notes
Network Number The number of the BACnet network to which the Niagara Supervisor is
connected.
Link > Adapter The network adapter used to connect to the BACnet network. If an
adapter is missing from the drop-down list, right-click on Link and select
22
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
1
Parameter Notes
Actions > Query for Adapters to refresh the list (see the following
Figure Refreshing the Network Adapter List).
Enabled Enables or disables the communication link.
Routing Enabled If the will have BACnet MS/TP devices connected to any of its MS/TP
ports (see the figure with BACnet MS/TP Link(s)) and communication
between BACnet/IP devices and the connected BACnet MS/TP devices
is required, set Routing_Enabled to true. When set to true, the routes
messages between the BACnet/IP port and the MS/TP port(s).
If the will not have BACnet MS/TP devices connected to any of its
MS/TP ports (see the figure with BACnet MS/tP Link(s)) or
communication between BACnet/IP devices and the connected BACnet
MS/TP devices is prohibited, set Routing_Enabled to false.
Maintain Routing Enabled When set to false, the station automatically disables routing in the
presence of routing errors, such as router loops.
When set to true, the station continues to attempt to route messages
even when routing errors are detected.
23
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
24
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Installing and Configuring a Siemens N4 Appliance Station and Platform
1
25
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Configuring the Required Networks
26
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Installation
Configuring the Required Networks
1
NOTE:
Only complete this procedure if the configuration does not use a Siemens field panel.
That is, if Siemens MS/TP devices are connected directly to MS/TP ports of the TNM
controller.
Configure an MS/TP port for each TNM controller. Each network number must be
unique on the network.
w You have connected to the Siemens TALON N4 Appliance station using the admin
account.
1. In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > Bacnet
Comm.
2. Double-click Network to display the Property Sheet.
3. In the Property Sheet, expand MstpPort > Link.
27
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
1 Installation
Configuring the Required Networks
5. Click Save.
6. In the Nav pane, expand Network, right-click MstpPort and select Actions > Enable.
28
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Discovering and Adding Devices
2
Installation Step
1 Discovering BACnet Devices on the Network [➙ 29]
2 Adding Controllers [➙ 30]
3 Adding the PPCL and Point Editor Functions [➙ 31] to Siemens Devices.
29
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Discovering and Adding Devices
30
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the PPCL Editor
2
1. Select a device in the Discovered list and click Add at the bottom of the pane. You
can also use multiselect to expedite this procees.
a The Add dialog box displays.
2. Click OK.
a The device is added to the database.
NOTICE
Any time you add a new device or points to Siemens Workbench, do the following to
update the database:
Right-click on SieUtilitiesService and select Actions > Sie Update Db.
31
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Using the PPCL Editor
5
6
① Command Bar
Contains the following functions:
l Syntax Check
32
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the PPCL Editor
2
Performs a basic syntax check. Select this function if you need to check the syntax of a PPCL
program after it is modified or imported.
l Enable or Disable
These buttons are disabled if the program contains unsaved changes.
– TC Series: A range of line numbers can be enabled or disabled. The line number fields
default to asterisks (*), which can be used for wildcarding.
– PTEC devices: The whole program is enabled or disabled.
l Clear Trace
Clears the trace bits of program lines. This button is disabled if the program contains unsaved
changes.
l Import
Loads a PPCL program file from the local computer or from a network share.
l Export
Saves the PPCL Editor content to a text file on the local computer or to a network share.
② Program Name (TC only)
Enter a name for the PPCL program. Limited to 30 alpha-numeric characters.
③ Line Increment
The line increment for adding a new line at the end of a program. Default is 10.
If a line is added and the next line number does not allow the desired increment setting, the line
number increments by 1.
④ Program Priority
The PPCL command priority. All commands within the program will be issued using that command
priority.
l TC Series: Priority can be selected when creating or importing a new program. The priority
cannot be changed through the N4 Appliance once a program is saved. Default is 16.
l PTEC devices: The priority is fixed at 15.
⑤ Line Status pane
Displays the status of each PPCL line. The following flags may display:
E or D - The line is enabled or disabled.
T - The line has been traced (executed) since the last time the trace bit was cleared.
U - The line references a point that does not exist in the device.
F - The line contains a syntax error.
⑥ PPCL Text Edit pane
A multi-line text field with automatic line numbering and all basic editing features.
⑦ Status pane
Displays the results of a Syntax Check, Enable, Disable, Clear Trace or Save operation.
⑧ Save button
Saves new or modified contents to the device. New or modified lines are saved as disabled.
33
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Using the PPCL Editor
34
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the PPCL Editor
2
Figure 5: Location of PPCL programs in the Nav pane (AlarmHorn: Damper; SilenceAlarm).
PTEC
1. In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [PTEC
device].
2. Double-click siePtecPpclProgram.
a PPCL Editor opens in the right pane. If the PTEC device already contains a
program, it is displayed.
3. In the PPCL Editor, click Import.
a The File Chooser opens.
4. Navigate to the file location on your computer and click Open.
Hint: Click to display display recently used file paths.
a The imported program displays in the PPCL Text Edit pane.
5. Click Syntax Check to check the PPCL syntax.
35
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Using the PPCL Editor
1. Double-click the program name in the Nav pane to display it in the PPCL Editor.
2. In the PPCL Editor, click Export.
a The File Chooser opens with PpclFile.pcl as the File name.
3. If desired, enter a new File name.
4. Select the network location for saving the file and click Save.
PTEC
1. In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [PTEC
device].
36
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the PPCL Editor
2
2. Double-click siePtecPpclProgram.
3. The PTEC program is displayed in the PPCL Editor.
4. In the PPCL Editor, click Export.
a The File Chooser opens with PpclFile.pcl as the File name.
5. If desired, enter a new File name.
6. Select the network location for saving the file and click Save.
TC Series.
l In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [TC device]
l Right-click on the program you want to delete and select Views > SiePxPpclEditor.
a The program is removed from the N4 database and left in the device.
NOTE: You cannot delete using Sie Remove Px PPCL Program if the name contains a
special character, such as “$.”
To delete a program from the N4 database and leave the program in the device,
complete the following:
1. In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [TC
Device].
2. Right click on the program you want to delete and select Delete.
37
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Using the PTEC Point Editor
PTEC
To delete a program from the device and the N4 database, complete the following
steps:
1. Double click siePtecPpclProgram to open the editor.
2. Remove entire content in the editing pane and click Save (you are saving an empty
program).
NOTICE
You can only save an empty program. You cannot delete a PPCL program in PTEC.
① Point Name
Displays the point name. Maximum of 12 characters.
Type
Drop-down list for the point type (AO or BO).
38
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the PTEC Point Editor
2
Instance #
Displays the instance number (1,000 or higher).
Engineering Units
Drop-down list for the standard BACnet engineering units. This column is disabled for BO points.
State Text
Drop-down list for the state text used to indicate point value. This column is disabled for AO points.
Inactive Text
The value displayed when the point is in the inactive (0) state. This column is disabled for AO
points.
Active Text
The value displayed when the point is in the active (1) state. This column is disabled for AO points.
Default Value
Displays the default point value. This is a numeric field for AO points and a drop-down list for BO
points.
② Analog Output (AO) Point
③ Binary Output (BO) Point
④ Status pane
Displays the results of a Syntax Check or Save operation.
⑤
⑥ Syntax Check
Performs a basic syntax check.
⑦ Save button
Saves new or modified contents to the device.
When you select a PTEC device, the object list indicates the ability to select the
Custom Point Table. After selecting the Custom Point Table from the object list, the
PTEC Point Editor table displays, showing the custom application point objects:
All information is editable.
39
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Using the Point Editor
a A new row displays in the PTEC Point Editor table. The new row is configured
for an AO type point by default:
40
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the Point Editor
2
1. Point Type
2. Point values
3. Save button
All points added to a PX controller using the N4 PX point editor are automatically
added to the N4 database.
41
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Using the Point Editor
To add a point:
1. Navigate to Station > Config > Drivers > BacnetNetwork > [TC Device] > Points.
2. Double click on Points.
3. Click Discover.
4. Find and click to highlight the desired point.
5. Click Add.
6. Navigate to Station > Config > Services > SieUtilitiesService.
7. Right-click on SieUtilitiesService and select Actions > SieUpdateDb.
NOTE: Run SieUpdateDb again if:
l You add points using N4 Discovery.
l You add panels or PTECs.
l Fill in the appropriate properties. Reference the BACnet Field Panel User’s Manual
for more information.
NOTE: The N4 Appliance TC point editor currently does not have a slope-intercept
calculator. The following slope-intercept calculators can be found at the following
location:
https://extranet.w3.siemens.com/buildingtechnologies/partner/CPSUSEN/AutomationP
roducts/Pages/Commissioning-Tool-Apogee.aspx
l Launch Pad or FP Web UI through APOGEE ALN Tools Installation (requires
ability to connect directly to field panel using http connection).
l Commisioning Tool Point Editor
l Slope intercept calculator installed as a stand alone application using
Commissioning Tool (use MEC as panel type for calculating slope intercept for TC
s).
42
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the Point Editor
2
NOTE: If you have two or more panels on two or more Automation-Level Networks
(ALNs), the N4 Appliance will learn the state text from the first panel it communicates
with. See below for a workaround:
l Delete all panels from the N4 database except the panel with the unique state text
table.
l Navigate to Station > Config > Drivers > Bacnet Nework and Delete
SiePxStateTextTable.
l Run Sie Update Db.
l The point you created will be added to the Points folder. To continue to view or
modify the point, double click on the new point (The one with the name you just
assigned it).
NOTE: When adding a point that exists at the panel and using N4 Point Discovery, if
the slope is greater than 20, an error message will display. If you discover a point
greater than 20, delete the existing point from the panel and add it via the N4
Appliance TC Point Editor.
43
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Using the Point Editor
1. In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [device]
and then double-click Points.
2. Double click on the desired point.
a The editor displays in a pop-up window.
3. Make the necessary modifications and click Save.
44
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Using the Point Editor
2
Figure 6:
45
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Troubleshooting
1. In the Nav pane, expand Station > Config > Drivers > BacnetNetwork > [device] >
Points.
a The points in the N4 database are displayed.
2. Right-click on the point you want to delete and select Delete.
a The point is removed from the N4 database.
NOTE: If you want to delete a point from the device that is not in the N4 database,
complete the following:
1. Discover the point
2. Run Sie Update Db
3. Delete the point (Views > Sie Delete Px Point)
2.5 Troubleshooting
2.5.1 Running Sie Update Db does not cause Point and PPCL
Editors to appear
One of the causes of the Sie Update Db not being able to create the objects for the
Point and PPCL Editors is if the station cannot bind to the webserver.
To determine if this is happening, navigate to Platform > Application Director and
search for an error message similar to the following:
INFO [08:32:30 01-Aug-16 CDT][javax.baja.web.BWebServer]
Scheduling restart in 5 seconds.
INFO [08:32:30 01-Aug-16 CDT][fox] FOX server started on port
[1911]
INFO [08:32:30 01-Aug-16 CDT][fox] FOXS server started on port
[4911]
INFO [08:32:30 01-Aug-16 CDT][sys] Niagara Runtime Environment:
4.1.27.20
INFO [08:32:30 01-Aug-16 CDT][sys] *** Station Started (1295ms)
[6948ms total] ***
niagara>INFO [08:32:31 01-Aug-16 CDT][history.db] Starting async
warmup of history config index...
INFO [08:32:31 01-Aug-16 CDT][history.db] Async history config
index warmup completed in 16 ms.
INFO [08:32:35 01-Aug-16 CDT][web] Jetty stopped.
SEVERE [08:32:35 01-Aug-16 CDT][javax.baja.web.BWebServer]
failed: java.net.BindException: Failed to bind to https port
[443], http port [80], or both
java.net.BindException: Failed to bind to https port [443], http
port [80], or both
at
com.tridium.jetty.BJettyWebServer.doStartWebServer(BJettyWebServ
er.java:618)
at
javax.baja.web.BWebServer.startWebServer(BWebServer.java:228)
at javax.baja.web.BWebServer.doRestart(BWebServer.java:291)
at auto.com_tridium_jetty_BJettyWebServer.invoke(AutoGenerated)
at
46
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Using the Siemens N4 Appliance
Troubleshooting
2
com.tridium.sys.schema.ComponentSlotMap.invoke(ComponentSlotMap.
java:1871)
at
com.tridium.sys.engine.EngineUtil.doInvoke(EngineUtil.java:61)
at javax.baja.sys.BComponent.doInvoke(BComponent.java:1206)
at javax.baja.util.Invocation.run(Invocation.java:46)
at
java.util.concurrent.Executors$RunnableAdapter.call(Executors.ja
va:511)
at java.util.concurrent.FutureTask.run(FutureTask.java:266)
at
java.util.concurrent.ThreadPoolExecutor.runWorker(ThreadPoolExec
utor.java:1142)
at
java.util.concurrent.ThreadPoolExecutor$Worker.run(ThreadPoolExe
cutor.java:617)
at java.lang.Thread.run(Thread.java:745)
To address this, open the Station and navigate to Station > Config > Services >
WebService and set the Http Port and Https port to different port numbers. For
example try setting the Http Port to 81 and the Https port to 500.
If you need to troubleshoot further to determine if a specific port is in use and which
program is using it, use the following procedure:
1. Run a command prompt as an Administrator.
2. Create and select a location to store a text file. For example, C:\N4_TS
3. Type the following commands and press Enter:
4. Netstat –a –n –p tcp –b > C:\N4_TS\tcpport01.txt
5. Netstat –ano > C:\N4_TS\tcpport_PID02.txt
Both text files will give you list of ports used for example in the line from tcpport01.txt
TCP 0.0.0.0:443 0.0.0.0:0 LISTENING
[vmware-hostd.exe]
47
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
2 Using the Siemens N4 Appliance
Troubleshooting
If you need to use a specific port that has a conflict, you will need to either stop the
program that is using the port or reconfigure that program to use a different port.
48
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Uninstalling Siemens Workbench
1. From the Windows Start menu, select All Programs > Siemens Workbench 4.x.x.x
folder > Uninstall.
49
Siemens Industry, Inc. Siemens TALON N4 Appliance A6V101025337
Confidential 2019-01-14
Issued by © Siemens Industry, Inc., 2018
Siemens Industry, Inc. Technical specifications and availability subject to change without notice.
Smart Infrastructure
1000 Deerfield Pkwy
Buffalo Grove IL 60089
Tel. +1 847-215-1000