SCHEDULE OF CIRCUIT DETAILS & INSPECTION & TEST RESULTS– STR 17

Issue 6 June 2012

SCHEDULE OF CIRCUIT DETAILS


SITE NAME: Bridge of Weir JOB NUMBER(NIMs): CHANGE CONTROL REFERENCE:
Site Address : Lintwhite Crescent, Bridge Of Weir, Renfrewshire, Scotland, PA11 3LJ
DB/SW Description: Sandaster DB Number of ways: 4 Supplied from DB/SW Ref: G/21
DB/SW Ref: G/28 Way No: 1L1 DB/SW Location: Engine Room
DB/SW Rating : 30 Amps DB/SW PFC: 1.4kA DB/SW Zs: 0.18Ω
Location : Engine room
Nominal Voltage: 230 V Circuit Design Current : 0.5 Amps Essential : Y Non-Essential : N
Circuit description Apps room lights & em lights          
Circuit Location APP room

Current (mA)
Circuit length
Fault Protection

RCD Operate
Cable C.S.A.

Allowed ()
Temp. (C)
C.P.C. Protective Device Method

Reference

Grouping

Diversity
Ambient
BS / Type Rating S/C Max. Other

Max. Zs
method
(mm2)

(mm2)
C.S.A.
Type*

factor
BS EN (A) Cap. Discon. (State)
Way

Line

(M)
(kA) Time
Type of Cable (Seconds)
1 L1 PVC Singles 1.5 40.0 B C *20 30.0 1 1.0 88 2 6 80 0 8.52 0.4

L2
L3
*C.P.C. Type T for Trunking, C for conduit, SWA for Steel wire armour, AWA for Aluminium wire armour, Cu for copper conductor, Al for aluminium conductor
# Make reference to installation methods detailed in Table 4A2 of BS7671
Number of Rectifiers/phase L1 0 L2 L3 Rectifier Type: , ,
Design: I/We being the person(s) responsible for the design of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, have exercised reasonable skill and care
when carrying out the design hereby CERTIFY that the said work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS7671:2008:
Details of departures from BS7671:2008 as amended (Regs 120.3, 120.4):
The extent of liability of the signatory or signatories is limited to the work described above as the subject of this certificate.
Designer Name: Digital Signature: Date:
Company Name :
Address:
Construction: I/We being the person(s) responsible for the construction of the electrical installation (as indicated by my/our signatures below), particulars of which are described above, have exercised reasonable skill
and care when carrying out the construction hereby CERTIFY that the construction work for which I/we have been responsible is to the best of my/our knowledge and belief in accordance with BS7671:2008

Details of departures from BS7671:2008 as amended (Regs 120.3, 120.4):


The extent of liability of the signatory or signatories is limited to the work described above as the subject of this certificate.
Constructor Name: Digital Signature: Date:
Company Name :
Address:

SCHEDULE OF INSPECTIONS

This form is based on model forms shown in Appendix 6 BS 7671:2008 © Copyright British Telecommunications plc. Registeredoffice: 81 Newgate Street, London, EC1AJ 7AJ.
Registered in England No. 1800000
1 of 3
SCHEDULE OF CIRCUIT DETAILS & INSPECTION & TEST RESULTS– STR 17
Issue 6 June 2012

SITE NAME:Bridge of Weir JOB NUMBER(NIMs): CHANGE CONTROL REFERENCE:


DB/SW Ref: G/28 G/28 Way No: 1L1 1L1
Y/N/NA/LIM METHODS OF PROTECTION AGAINST ELECTRIC SHOCK Y/N/NA/LIM Prevention of mutual detrimental influence
Both basic and fault protection Y Proximity of non-electrical services & influences
Y SELV Y Segregation of Band I & II cables or the use of Band II insulation
Y Limitation of discharge of energy Y Segregation of safety circuits
Y Double insulation Identification
Y Reinforced insulation Y Presence of diagrams, instructions, circuit charts and similar information
Basic protection Y Presence of danger notices & other warning notices
Y Insulation of live parts Y Labelling of protective devices, switches and terminals
Y Barriers or enclosures Y Identifications of conductors
Y Obstacles Cables & Conductors
Y Placing out of reach Y Selection of conductors for current capacity and volt drop
Y Erection methods
Fault Protection Y Routing of cables in prescribed zones
Automatic disconnection of supply: Y Cables incorporating earthed armour or sheath, or run within an earthed wiring
system, or otherwise adequately protected against nails, screws etc.
Y  Presence of earthing conductor Y Additional protection provided by 30mA RCD for cables in concealed walls (where
required in premises not under the supervision of a skilled or instructed person)
Y  Presence of circuit protective conductors Y Connection of conductors
Y  Presence of protective bonding conductors Y Presence of fire barriers and protection against thermal effects
Y  Presence of earthing arrangements for combined protective General
and functional purposes
Y  Presence of adequate arrangements for alternative source(s) Y Presence & correct location of appropriate devices for isolating & switching
where applicable
Y  FELV Y Adequacy of access to switchgear and other equipment
Y  Choice and setting of protective & monitoring devices (for Y Particular protective measures for special installations and locations
fault and or overcurrent protection)
Non conducting location: Y Connection of single-pole devices for protection/ switching in line conductors only
Y Absence of protective conductors Y Correct connection of accessories and equipment
Earth-free local equipotential bonding: Y Presence of undervoltage protective devices
Y Presence of earth-free local equipotential bonding conductors Y Selection of equipment and protective measures appropriate to external influences
Electrical separation: Y Selection of appropriate functional switching devices
Y Provided for one item of current-using equipment
Y Provided for more than one item of current-using equipment Y – Indicates an inspection has been carried out and is satisfactory. N – Indicates an inspection has been
Additional Protection: carried out and is unsatisfactory (periodic inspections only). NA – Indicates the inspection is not
Y Presence of residual current device(s) applicable to a particular item. LIM – Indicates a limitation prevented the inspection being carried out
Y Presence of supplementary bonding conductors (periodic inspections only)
SCHEDULE OF TEST RESULTS

This form is based on model forms shown in Appendix 6 BS 7671:2008 © Copyright British Telecommunications plc. Registeredoffice: 81 Newgate Street, London, EC1AJ 7AJ.
Registered in England No. 1800000
2 of 3
SCHEDULE OF CIRCUIT DETAILS & INSPECTION & TEST RESULTS– STR 17
Issue 6 June 2012

SITE NAME: Bridge of Weir Error: Reference source not found JOB NUMBER(NIMs): CHANGE CONTROL REFERENCE:
DB/SW Ref: G/28 G/28 Way No: 1L1

Insulation Resistance RDC Operating

RCD Rated Current


Polarity (Pass/Fail)
Continuity ()

Functional test of
(Record lowest value) (M) times

Max. Measured

test – Yes / No
Part of Sample
All other
Ring circuits

EFLI Zs ()
Circuits* Comments
Neutr In 5In mS
Line/ Lines/ Lines/
Bonding

al/ (mS) (30mA


Line Neutral Earth

(mA)
r1 rn r2 r1+r2 r2 Earth (All) only)
Way

RCD
Line

1 0.18 0.18 500 500 500 1.57


L1 Y

L2
L3
* Record r1+r2 or r2

Comments on existing installation (in the case of an alteration or addition. See section 633):

TEST INSTRUMENTS All test instruments must have an associated valid calibration certificate at the time of test
Type Insulation Tester Continuity E.L.I. Tester R.C.D. Tester Other Other Other

Manufacturer/Model Fluke Fluke Fluke Fluke


No.
Serial Number 8572031 8572031 8572031 8572031
Obtain permission from the Manager responsible for the electrical installation before working on this equipment
Inspector Name: Stephen Grant
Inspector Digital Signature: Yes
Date: 10/07/2013
Company: British Telecommunications PLC

This form is based on model forms shown in Appendix 6 BS 7671:2008 © Copyright British Telecommunications plc. Registeredoffice: 81 Newgate Street, London, EC1AJ 7AJ.
Registered in England No. 1800000