DALIRE-ABE14 Requirments

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 21

4.

82m
14.75m
Laundry Area 4.25m
WT
3.00m 5.75m
2.75m
WM
5.00m
CR
Dining/Kitchen Area
4.90m
Bedroom3
0.91m
Hallway 2.51m 12.50m
3.00m 3.00m
CR
5.85m

Bedroom1
Bedroom2 5.00m

ACU

Heater
Porch 1.00m
3.80m 4.10m
5.10m 13.00m
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE FLOORPLAN JOHN PAUL D. GALVAN 1
Student (RESIDENTIAL) Subject Teacher 4
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE RESIDENTIAL LIGHTING OUTLET LAYOUT JOHN PAUL D. GALVAN 2
Student Subject Teacher 4
GFCI OUTLET
GFCI
CKT#4
GR
GAS RANGE OUTLET
GR
HEATER OUTLET
HEATER
CKT#3
ACU ACU OUTLET
CKT#1
CONVENIENCE OUTLET
CKT#2
PANEL BOARD
CKT#6 CIRCUIT HOMERUN
CKT#5
HEATER
ACU
GFCI
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE RESIDENTIAL CONVENIENCE OUTLET LAYOUT JOHN PAUL D. GALVAN 3
Student Subject Teacher 4
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE COMBINATION JOHN PAUL D. GALVAN 4
Student (LIGHTING AND CONVENIENCE LAYOUT) Subject Teacher 4
8.94m 7.62m
30.11m
CR 1

CR 2

CR 3

4.11m
3.94m
3.00m
3.84m
Office
5.91m Area
Storage 6.00m 7.86m
Area 15.00m
6.00m
9.11m
Receiving Area
3.00m
7.00m Tools and
3.87m 3.94m
Equipment
5.87m
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE
FLOORPLAN
(WAREHOUSE STORAGE FOR JOHN PAUL D. GALVAN 1
Student GRAIN-BAGGED) Subject Teacher 4
S1
S1
S1

CKT #4
S1
S1 S1
S2
CKT #5 S1
CKT #8
CKT #7
CKT #6 S1 S1
LEGEND
FLUORESCENT
LED LIGHT BULB
CIRCUIT HOMERUN
ONE WAY SWITCH S1
TWO WAY SWITCH S2
PANEL BOARD
LIGHT SWITCH CONNECTION
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE
LIGHTING OUTLET LAYOUT
(WAREHOUSE STORAGE FOR JOHN PAUL D. GALVAN 2
Student GRAIN-BAGGED) Subject Teacher 4
CKT #2
LEGEND
CKT #1
CONVENIENCE
OUTLET
HOMERUN CIRCUIT
PANEL BOARD
BRANCH CIRCUIT LINE
CKT #3
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE
CONVENIENCE OUTLET LAYOUT
(WAREHOUSE STORAGE FOR JOHN PAUL D. GALVAN 3
Student GRAIN-BAGGED) Subject Teacher 4
S1
S1
S1

CKT #2
CKT #4
S1
CKT #1
S1 S1
S2
S1
CKT #5
CKT #8
CKT #7
CKT #6 S1 S1
CKT #3 LEGEND
FLUORESCENT
LED LIGHT BULB
CIRCUIT HOMERUN
ONE WAY SWITCH S1
TWO WAY SWITCH S2
PANEL BOARD
LIGHT SWITCH CONNECTION
CONVENIENCE OUTLET
BRANCH CIRCUIT LINE
Prepared by: Sheet Title: Reviewed by: Sheet No:
OLIVIA P. DALIRE
COMBINATION
(LIGHTING AND CONVENIENCE JOHN PAUL D. GALVAN 4
Student OUTLET) Subject Teacher 4
RESIDETIAL

Length(m) Width(m) Area (𝒎𝟐 )


Porch 3.80 1 3.8
Laundry 4.82 3 14.46
Kitchen/Dining Area 5.75 4.90 28.175
Bedroom 1a 2.60 3 7.8
Bedroom 1b 4.61 2.60 11.986
Bedroom 2 4.6 3.6 16.56
Bedroom 3 4.58 3.63 16.63
Living Room 4.75 3.80 18.01
Hallway 1a 2.85 2.5 7.125
Hallway 1b 3.91 2.54 9.93
CR 1 2.75 1.60 4.4
CR 2 2.85 1.85 5.27

(Lighting Requirements)x (Floor Area)


No. of Lamps= (Lumen per Lamps)

(150 lumen/m2)x (3.8 m2)


A. Porch = (1200 lumen/lamp)

=0.475
≈ 1 lamp
(150 lumen/m2)x (18.1m2)
B. Living Area = (5400lumen/lamp)

= 0.50

≈1 lamp
(150 lumen/m2)x (28.175 m2)
C. Kitchen/Dining Area = (2400 lumen/lamp)

=1.76

≈2 lamps
(150 lumen/m2)x (7.2m2)
D. Bedroom 1a = (5400 lumen/lamp)

=0.2

≈1 lamp
(150 lumen/m2)x (11.986m2)
E. Bedroom 1b = (5400 lumen/lamp)
=0.33

≈1 lamp
(150 lumen/m2)x (16.56m2)
F. Bedroom 2 = (5400 lumen/lamp)

=0.46

≈1 lamp
(150 lumen/m2)x (16.63 m2)
G. Bedroom 3 = (4300 lumen/lamp)

=0.46

≈1 lamp
(150 lumen/m2)x (4.4 m2)
H. Comfort Room 1 = (1200 lumen/lamp)

=0.55

≈1 lamp
(150 lumen/m2)x (5.27 m2)
I. Comfort Room 2 = (1200 lumen/lamp)

=0.66

≈1 lamp
(150 lumen/m2)x (14.46 m2)
J. Laundry Area = (2400 lumen/lamp)

=0.90

≈1 lamp
(150 lumen/m2)x (7.125 m2)
K. Hallway 1a = (600 lumen/lamp)

=1.78

≈2 lamps
(150 lumen/m2)x (7.125 m2)
L. Hallway 1b = (600 lumen/lamp)

=2.48

≈3 lamps

Floor Lighting Lamp Requirement


Area Requirements Type of Watt Lumens Quantity
(m2) (lumens/m )2
Lamp
Porch 3.8 150 Fluorescent 20 1200 1
Helical
Living Area 18.05 150 Fan-blade 45 5400 1
LED light
bulb
Kitchen/Dining 28.175 150 LED 25 2400 2
Area
Bedroom 1a 7.8 150 Fan-blade 45 4500 1
LED light
bulb
Bedroom 1b 11.986 150 Fan-blade 45 4500 1
LED light
bulb
Bedroom 2 16.56 150 Fan-blade 45 4500 1
LED light
bulb
Bedroom 3 16.63 150 Fan-blade 45 4500 1
LED light
bulb
C-Room 1 4.4 150 Fluorescent 20 1200 1
Helical
C-Room 2 5.27 150 Fluorescent 20 1200 1
Helical
Laundry Area 14.46 150 LED 24 2400 1
Hallway 1a 7.125 150 Recessed 5 400 2
LED
Hallway 1b 9.93 150 Recessed 5 400 3
LED
TOTAL 16
A. Circuit 1: Lighting Outlets (8 outlets)

1. Total Estimation = (8 outlets x 100 watts)


= 800 watts

800 watts
Current Load= 230 volts

= 3.48 Amperes
2. Branch Circuit Wire = Use 14 AWG THW 75℃

3. Rating of Overcurrent Protection = Use 15 amperes trip breaker

4. Size of Conduit Pipe = Use 13 mm conduit pipe.

B. Circuit 2: Lighting Outlets (8 outlets)

1. Total Estimation = 8 outlets x 100 watts


= 800 watts

800 watts
Current Load = 230 volts

= 3.48 Amperes
2. Branch Circuit Wire = Use 14 AWG THW 75℃

3. Rating of Overcurrent Protection = Use 15 amperes trip breaker

4. Size of Conduit Pipe = Use 13 mm conduit pipe.

C. Circuit 3: Convenience Outlets (8 outlets)

1. Total Estimation = 8 outlets x2 gang per outlet x 180 watts


= 2880 watts

2880 watts
Current Load= 230 volts

= 12.52 Amperes

2. Branch Circuit Wire = Use 12 AWG THW 75℃


3. Rating of Overcurrent Protection = Use 20 amperes trip breaker.

4. Size of Conduit Pipe = Use 13 mm conduit pipe.

D. Circuit 4: Convenience Outlets (9 outlets)

1. Estimation = 9 outlets x2 gang per outlet x 180 watts


= 3240 watts
3240 watts
Current Load= 230 volts

= 14.09 Amperes

2. Branch Circuit Wire = Use 12 AWG THW 75℃

3. Rating of Overcurrent Protection = Use 20 amperes trip breaker.

4. Size of Conduit Pipe = Use 13 mm conduit pipe.

E. Circuit 5: Convenience Outlets (8 outlets)

1. Total Estimation = 8 outlets x 2 gang per outlet x 180 watts


= 2880watts
2880watts
Current Load= 230 volts

= 12.52 Amperes

2. Branch Circuit Wire = Use 12 AWG THW 75℃

3. Rating of Overcurrent Protection = Use 20 amperes trip breaker.

4. Size of Conduit Pipe = Use 13 mm conduit pipe

F. Circuit 6: Air Conditioning (1 unit)

1. Air Conditioning Unit Load (appliance rating) = 1000 watts


1000watts
Current Load= 230 volts

= 4.35 Amperes
2. Branch Circuit Wire = Use 12 AWG THW 75℃

3. Rating of Overcurrent Protection = Use 20 Amperes trip breaker.

4. Size of Conduit Pipe = 13 mm conduit pipe.

G. Circuit 7: Heater (1 unit)


1. Total Estimation = 1500 watts

Current Load = (1500 watts)/(230 volts)

= 6.52 Amperes

2. Branch Circuit Wire = Use 12 AWG THW 75℃

3. Rating of Overcurrent Protection = Use 20 amperes trip breaker.

4. Size of Conduit Pipe = Use 13 mm conduit pipe.

H. Circuit 8: Gas Range (1 unit)

1. Demand Load=8kW+(14kW-12kW)(0.4)

= 8.8 kW
8800 watts
Current Load= 230 volts

= 38.26 Amperes

2. Branch Circuit Wire = Use 8 AWG THW 75℃

3. Rating of Overcurrent Protection = Use 45 amperes trip breaker.

4. Size of Conduit Pipe = Use 20 mm conduit pipe


Branch Load Current
Circuit Quantity Description Size, A Conductors Circuit Conduit,
No. Breaker (mm)
Size Insulator Ampacity Frame Trip
(AWG) Type (A) (A)
1 8 LO 3.48 14 THW. 75 15 50 15 13
DEGREES
2 8 LO 3.48 14 THW. 75 15 50 15 13
DEGREES
3 8 CO 12.52 12 THW. 75 20 50 20 13
DEGREES
4 9 CO 14.09 12 THW. 75 20 50 20 13
DEGREES
5 8 CO 12.52 12 THW. 75 20 50 20 13
DEGREES
6 1 ACU 4.35 12 THW. 75 20 50 20 13
DEGREES
7 1 HEATER 6.52 12 THW. 75 20 50 20 13
DEGREES
8 1 GAS 38.26 8 THW. 75 20 50 45 20
RANGE DEGREES

Sizing of Service Entrance

General Lighting and general-purpose outlet = (3.48+3.48+12.52+14.09+12.52) x 230

General lighting and general-purpose outlet = 10,600.7 VA

Applying the demand system:

3,000 VA x 100% = 3000 VA

10,600.7 – 3,000 VA x 35%= 9,550.7 VA

Total demand load = 3,000 VA + 9,550.7

=12,550.7 VA
FARM STRUCTURE
(Warehouse Storage for Grain-Bagged)

Length(m) Width(m) Area (𝒎𝟐 )


Storage Area 30.11 15 451.65
Receiving Area 9.11 7 63.77
Office Area 8.94 5.91 52.84
CR 1 4.11 3.08 12.66
CR 2 4.11 1.50 6.125
CR 3 4.11 2.89 11.28
Hallway 5.91 3.84 22.69
Tools and 5.87 3.87 22.72
Equipment Room

(3 W/m2)x (451.65 m2)


A. Storage= (54W)

=25.09

≈25 lamps
(3W/m2)x (63.77m2)
B. Receiving Area= (40)

=4.78

≈ 5 lamps
(3W/m2)x (52.84m2)
C. Office Area= (40W)

=3.96

≈ 4 lamps
(3W/m2)x (12.66m2)
D. CR 1 =
(40W)

=0.95

≈ 1 lamp
(3W/m2)x (6.125m2)
E. CR 2 = (40 W)

=0.46

≈ 1 lamp

(3W/m2)x (11.28 m2)


F. CR 3 = (40W)

=0.87

≈ 1 lamp

(3W/m2)x (22.69m2)
G. Hallway = (40W)

=1.7

≈ 2 lamps
(3 W/m2)x (22.72 m2)
H. Tools and Equipment = (40 W)

=1.7

≈ 2 lamps

ROOM AREA(m2) TYPE OF WATT QUANTITY


LAMP
Storage Area 451.65 Fluorescent 54 25
Receiving Area 63.77 Fluorescent 40 5
Office Area 52.84 LED 40 4
CR 1 12.66 LED 40 1
CR 2 6.165 LED 40 1
CR 3 11.88 LED 40 1
Hallway 22.69 Fluorescent 40 2
TOTAL 39

A. Circuit 1: Convenience Outlet (8 outlets)


1. Total Estimation = 7 outlets x 2gang per outlet x 180 watts
= 2520 W
2520 watts
2. Current Load= 230 volts
= 10.97 Amperes

3. Branch Circuit Wire = Use 12 AWG THW 75℃

4. Rating of Overcurrent Protection = Use 20 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

B. Circuit 2: Convenience Outlets (7 outlets)


1. Total Estimation = 7outlets x 2 gang per outlet x 180 watts
= 2520 watts
2520 watts
2. Current Load= 230 volts
= 10.97 Amperes

3. Branch Circuit Wire = Use 12 AWG THW 75℃

4. Rating of Overcurrent Protection = Use 20 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

C. Circuit 3: Convenience Outlet (7 outlets)


1. Total Estimation = 7 outlets x 2 gang per outlet x 180 watts
= 2520 watts
2520 watts
2. Current Load= 230 volts
= 10.97 Amperes

3. Branch Circuit Wire = Use 12 AWG THW 75℃

4. Rating of Overcurrent Protection = Use 20 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

D. Circuit 4: Lighting Outlet (9 outlets)

1. Total Estimation = 10 outlets x 180 watts


= 1800 watts
1800 watts
2. Current Load= 230 volts
= 7.83 Amperes
3. Branch Circuit Wire = Use 14 AWG THW 75℃

4. Rating of Overcurrent Protection = Use 15 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

E. Circuit 5: Lighting Outlet (7 outlets)


1. Total Estimation = 7 outlets x 180 watts
= 1260 watts
1260 watts
2. Current Load= 230 volts
=5.48 Amperes

3. Branch Circuit Wire = Use 14 AWG THW 75℃

4. Rating of Overcurrent Protection = Use 15 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

F. Circuit 6: Lighting Outlet (8 outlets)


1. Total Estimation = 10outlets x 180 watts
= 1800watts
1800 watts
2. Current Load= 230 volts
=7.83 Amperes

3. Branch Circuit Wire = Use 14 AWG THW 75℃

4. Rating of Overcurrent Protection = Use 15 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

G. Circuit 7: Lighting Outlet (9 outlets)


1. Total Estimation = 10 outlets x 180 watts
= 1800 watts
1800 watts
2. 𝐶𝑢𝑟𝑟𝑒𝑛𝑡 𝐿oad= 230 volts
= 7.83 Amperes

3. Branch Circuit Wire = Use 14 AWG THW 75℃


4. Rating of Overcurrent Protection = Use 15 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

H. Circuit 8: Lighting Outlet (8 outlets)


1. Total Estimation = 5 outlets x 180 watts
= 900 watts
900watts
2. Current Load= 230 volts
= 3.91 Amperes

3. Branch Circuit Wire = Use 14 AWG THW 75℃

4. Rating of Overcurrent Protection = Use 15 amperes trip breaker.

5. Size of Conduit Pipe = Use 50 mm conduit pipe.

Branch Load Current


Circuit Quantity Description Size, A Conductors Circuit Conduit,
No. Breaker (mm)
Size Insulator Ampacity Frame Trip
(AWG) Type (A) (A)
1 7 CO 10.97 12 THW. 75 20 50 20 50
DEGREES
2 7 CO 10.97 12 THW. 75 20 50 20 50
DEGREES
3 7 CO 10.97 12 THW. 75 20 50 20 50
DEGREES
4 9 LO 7.04 14 THW. 75 15 50 15 50
DEGREES
5 7 LO 5.48 14 THW. 75 15 50 15 50
DEGREES
6 8 LO 7.83 14 THW. 75 15 50 15 50
DEGREES
7 9 LO 7.83 14 THW. 75 15 50 15 50
DEGREES
8 8 LO 3.91 14 THW. 75 15 50 15 50
DEGREES
Sizing of Service Entrance

General Lighting and general-purpose outlet

= (10.97+10.97+10.97+7.04+5.48+7.83+7.83+3.91) x 230

General lighting and general-purpose outlet = 14,950 VA

Applying the demand system:

3,000 VA x 100% = 3000 VA

14,950 – 3,000 VA x 35%= 13,900 VA

Total demand load = 3,000 VA + 13,900 VA

= 16,900 VA