Professional Documents
Culture Documents
Hydrogen in Generator
Hydrogen in Generator
Hydrogen in Generator
Hydrogen-Cooled
Cooled
Generators Lurks as Serious Operational Threat
MELISSA KOLODZIEJ
8.1.2003
By: Ed Borkey, Fluid Energy and Troy Reynolds, Progress Energy
Water contamination in hydrogen gas also contributes to lead carbonate deposits, which
form as a result of water and carbon dioxide reacting with lead and acid flux within
generators. Lead carbonate
arbonate is a conductive and porous material that can trap moisture,
leading to electrical arcing and failure of generator windings.
Hydrogen Dryers
Drying systems based on internally heated regenerative dryers are commonly used to
remove moisture from hydrogen gas. Such systems typically consist of a coalescing pre- pre
filter, a loose bed carbon adsorber, a regenerative dryer, an after filter, and a blower
(Figure 2).
A desiccant dryer is only as effective as its ability to regenerate itself. As one vessel is
drying the hydrogen gas, the other vessel regenerates itself by energizing the heaters
within each desiccant chamber and by purging a small amount of hydrogen gas across the
desiccant to carry the moisture, and potentially other contaminants, out of the system.
Depending on ambient temperature and the amount of water being removed from the
generator, varying amounts of liquid water can condense in the purge exhaust drain line.
This drain location is an excellent place to gauge the effectiveness of the hydrogen dryer. By
measuring the amount of condensate at this location over time, it is possible to accurately
calculate the amount of water contamination within a generator. Moreover, this calculation
is conservative because the purge gas carries additional water out of the system in a vapor
state that does not condense into the purge exhaust drain location.
All desiccant materials are abrasive and create dust over time. To keep desiccant fines from
being introduced into the generator, a particulate after filter is used. The final component in
the hydrogen drying system is a positive displacement, rotary lobe blower that continually
circulates about 10 actual cubic feet per minute through the dryer system. This blower is
necessary to overcome pressure drop associated with the dryer, filtration system, and
piping.
Water Entry
The water content in turbine oil has a huge effect on generator dew point. The alarm point
for many utilities is 500 ppmw of water in turbine oil. When water content in turbine oil
reaches these high limits, it also creates high dew points in generators, and it does not all
occur by oil infiltration into the generator.
Turbine oil pressure is usually kept 10 psi lower than hydrogen gas pressure to keep oil
carryover at a minimum. As hydrogen leaks out of the seals, a flow path is created for water
vapor to enter the generator. This can be explained by water vapor seeking equilibrium. In
other words, the partial pressure of water vapor in the turbine oil is greater than in the
generator. As water vapor seeks equilibrium, water vapor enters the generator, even
though the hydrogen gas is at a higher pressure. This can be further understood by
studying Fick’s Law of thermodynamics that addresses diffusion of gas molecules.
New 150 MW GE generators that have been recently supplied for gas turbine power plants
have an internal volume of 2250 ft3. One gallon of water removed from this generator each
day equates to 8.3 lb of water. With a specific volume of water of 21.06 ft3/lb at standard
conditions, 8.3 lb of water consumes 174.8 ft3 of space in the generator. If this is the only
contaminant, the purity is 92.2 percent by volume.
Continuing with this example, 8.3 pounds of water equals 58,100 grains of water. Spread
uniformly through this same generator, this corresponds to 25.8 grains/ft3. The resulting
dew point would be approximately 106 F. This would undoubtedly create a saturated
environment including liquid water in the generator. However, based on extensive analysis
of more than 80 hydrogen drying systems, the authors have observed a generator dew
point of greater than 100 F on only one occasion. In that case, the excessive dew point was
primarily due to a cooler leak on a water-cooled generator. Therefore, when more than one
gallon of water is removed from a generator in a given day, water must be continually
added to the generator through the seals as described above.
If the carbon dioxide has been thoroughly purged from the generator prior to operation, the
likely contaminants then include air, water, and oil vapor. Many hydrogen purity analyzers
also include dryers upstream to remove water and oil vapor prior to entering the hydrogen
4 Source: Power-eng.com | https://www.power-eng.com/coal/water-contamination-in-hydrogen-
cooled-generators-lurks-as-serious-operational-threat/#gref
purity analyzer. In these instances, it is more likely that the impurities measured by the
analyzer are indeed air.
As an example, dew point measurements taken at many gas turbine sites over the last
several years revealed high purity readings on the purity analyzers that did not coincide
with the measured dew points. Typical dew points ranged from +20°F to +70°F, while the
purity analyzers usually showed 99 percent and higher. Further investigation of the purity
analyzers, and discovery of the upstream dryers, explained the discrepancy.
This can be a particular problem on generators used for peak load conditions. Some
generators are equipped with internal electric heaters to keep relative humidity of the
hydrogen coolant low, but many utilities are reluctant to operate these heaters for safety
reasons.
Generators that are not running and exposed to ambient temperatures are more susceptible
to high humidity environments than generators in operation. For example, if a stand-by
generator has a hydrogen coolant dew point of 40 F and the ambient temperature is 80 F,
the relative humidity is 25 percent within the generator. As ambient temperature drops at
night or during cooler seasons, relative humidity increases. In this example, if ambient
temperature falls to 40 F, saturated conditions prevail. As cooling continues below 40 F,
liquid water condenses into a liquid and may potentially freeze if temperatures fall below 32
F.
Possible Solutions
One alternative to installing a hydrogen drying and circulation system is to continue the
common practice of “bleed and feed” of hydrogen gas into generators. When hydrogen
The “bleed and feed” approach could also be used if dew point or humidity were known
within the generators. However, utilities rarely have hygrometers installed on generators,
and are often reluctant
tant to install hygrometers because of the potential for sensor
contamination. When operators question
the accuracy of instruments, action is
rarely taken based on the output
provided.