Professional Documents
Culture Documents
Bni Iol-712-000-K023 - en - Bni00041
Bni Iol-712-000-K023 - en - Bni00041
BNI IOL-714-000-K023
User’s Guide
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
2 Safety
2.1 Intended use 3
2.2 General safety notes 3
2.3 Meaning of the warnings 3
3 Getting started
3.1 Connection overview 4
3.2 Mechanical connection 4
3.3 Electrical connection 4
3.3.1 IO-Link interface 4
3.3.2 Sensor interface 5
4 IO-Link interface
4.1 IO-Link data 6
4.2 Process data / Input data 6
4.3 Parameter data / Request data 7
4.4 Errors 7
4.5 Events 7
5 Technical data
5.1 Dimensions 8
5.2 Mechanical data 8
5.3 Electrical data 8
5.4 Operating conditions 8
5.5 LED indicators 9
Appendix
Product ordering code 10
Order information 10
Scope of delivery 10
www.balluff.com 1
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
1.1 About this guide This guide describes the Balluff Network Interface BNI IOL-712/714-000-K023 for the
application as peripheral input module to connect analogue sensors. Hereby it is about an
IO-Link device which communicates by means of IO-Link protocol with the superordinate IO-
Link master assembly.
1.2 Structure of the The guide is organized so that the sections build on one another.
guide Section 2: Basic safety information.
Section 3: The main steps for installing the device.
Section 4: IO-Link, parameter and process data for the device.
Section 5: Technical data for the device.
1.3 Typographical
conventions
The following typographical conventions are used in this guide.
1.3.1 Enumerations Enumerations are shown in list form with bullet points:
- Entry 1,
- Entry 2.
1.3.2 Actions Action instructions are indicated by a preceding triangle. The result of an action is indicated
by an arrow.
Action Instruction 1,
Action result.
Action instruction 2.
1.3.4 Cross Cross references indicate where additional information on the topic can be found (see
references Section 5 „Technical data”).
Note!
This symbol indicates a security notice which must be observed.
www.balluff.com 2
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
2 Safety
2.1 Intended use This guide describes the Balluff Network Interface BNI IOL-712/714-000-K023 for the
application as peripheral input module to connect analogue sensors. Hereby it is about an
IO-Link device which communicates by means of IO-Link protocol with the superordinate IO-
Link master assembly.
www.balluff.com 3
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
3 Getting started
3.1 Connection
overview
1
4
3.2 Mechanical The BNI IOL-712/714-000-K023 modules are directly attached to an IO-Link Master or to the
connection analogue sensor, threaded in with M12 male. No further mechanical attachment is required.
3.3 Electrical The BNI IOL-712/714-000-K023 modules require no separate supply voltage connection.
connection Power is provided through the IO-Link interface by the superordinate IO-Link Master
Assembly.
Connecting the Connect the BNI IOL-…-K023 either to an IO-Link Master directly or to an analogue
module sensor.
Connect the male plugs unconnected by using cables.
Note:
A standard 3 wire sensor cable is used for connection to the host IO-Link master.
Note:
A standard 4 wire sensor cable is used for connection to the analogue sensor.
Module versions
Module versions Analogue port
BNI IOL-712-000-K023 Current input (4-20mA)
BNI IOL-714-000-K023 Voltage input (0-10V)
www.balluff.com 4
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
3 Getting started
Pin Signal
1 +24V, 100mA
1)
2 Current input 4-20mA
3 GND
2)
4 Voltage input 0-10V
www.balluff.com 5
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
4 IO-Link interface
BNI IOL-714-000-K023
BNI IOL-712-000-K023
Byte 0 Byte 1
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Error:
0 - current > 4mA
1 – current < 4mA
Error
Analogue Input Current Value -
BNI IOL-714-000-K023
Byte 0 Byte 1
7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0
www.balluff.com 6
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
4 IO-Link interface
0x0B
0x10 0 Vendor name 7 Byte BALLUFF
0x11 0 Vendor text 15 Byte read only www.balluff.com
BNI IOL-712-000-K023
0x12 0 Product name 20 Byte
BNI IOL-714-000-K023
BNI 0041
0x13 0 Product ID 7 Byte
BNI 0042
Hobbit current input
0x14 0 Product text 22 Byte
Hobbit voltage input
0x16 0 Hardware Revision 1 Byte 1.2
0x17 0 Firmware Revision 23 Byte 1.0
Parameter
Data
www.balluff.com 7
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
5 Technical data
5.1 Dimensions
www.balluff.com 8
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
5 Technical data
LED 1: Communication
LED 2: Supply
www.balluff.com 9
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
Appendix
IO-Link interface
Functions
712 = Current input 4-20mA
714 = Voltage input 0-10V
Versions
000 = Standard design
Mechanical design
K023 = Plastic housing, Hotmelt
Bus connection and voltage supply 1xM12, male, 4 poles, external thread
Analogue port: 1xM12, female, 4 poles, internal thread
www.balluff.com 10
Balluff Network Interface / IO-Link BNI IOL-712/714-000-K023
www.balluff.com
Balluff GmbH
Schurwaldstrasse 9
73765 Neuhausen a.d.F.
Germany
Tel. +49 7158 173-0
Fax +49 7158 5010