Fire Prevention1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 24

RISK IS GENERICALLY DEFINED AS THE UNCERTAINTY OF LOSS.

Fire and explosion can result in catastrophic consequences, causing serious


injuries or death of workers and others, as well as significant damage to
property.

A person conducting a business or undertaking must prevent the possibility


of fire or explosion from an ignition of flammable substances associated with
a hazardous area or a hazardous atmosphere.
The goal of fire prevention is to educate the public to take precautions to prevent
potentially harmful fires, and be educated about surviving them.
The mission of the NFPA established in 1896, is to reduce the worldwide burden of
fire and other hazards on the quality of life by providing and advocating consensus
codes and standards, research, training, and education.

CODES AND STANDARDS

NFPA is responsible for 300 codes and standards that are designed to
minimize the risk and effects of fire by establishing criteria for building,
processing, design, service, and installation around the world.
PORTABLE FIRE EXTINGUISHER
NFPA 10 standard is implemented
for various type of portable fire
extinguisher.
NFPA13 is implemented for design,
installation & Testing the Sprinkler System
❖ NFPA 14 is
implemented for
design, installation
& Testing the Stand
pipes & Hose
System
❖ NFPA 24 & NFPA
291 is used for
❖ NFPA 20 standard is
used for Fire Pump to
comply in all respects.
❖ NFPA 22 is used for
Fire Water Tank
design.
❖ The design ,installation &
Testing shall comply with
NFPA 24 & NFPA 291
including referenced NFPA
publications.
❖ The system components,
pipes, fittings shall be
selected as per the
relevant provision of NFPA
13.
❖ Requirement for Inspection, Testing and Maintenance of Water Based
Fire Protection
❖ 72 ,70 & 101 recommendations shall be used for Application, Installation,
Location, Performance & Maintenance of Fire Alarm System NFPA
❖ NFPA 2001 is implemented for design, installation & Testing of the Clean
Agent System
❖ NFPA 11 - Standard for Low, Medium & High-Expansion Foam
❖ NFPA 16 - Standard for the Installation of Foam-Water Sprinkler
and Foam-Water Spray Systems
❖ NFPA 30 - Flammable and Combustible Liquids Code
❖ The design, installation & Testing
shall comply with NFPA 750 &
including referenced NFPA
publications.
❖ NFPA 17A standard is
implemented for wet chemical
Extinguishing System.
❖ The design, installation &
Testing shall comply with
following standards :
• NFPA – 92 A
• NFPA – 92 B
• NFPA – 204
❖ Establishes minimum
requirements for new &
existing buildings to protect
building occupant from Fire,
Smoke and Toxic Fumes

You might also like