Dear Sir/Mdm,
SCDF would like to issue the 8th batch of amendments to the Code of Practice for Fire
Precautions in Buildings 2018 (Fire Code 2018). The amendments which were deliberated and
accepted by the Fire Code Review Committee are attached as Annex A of this circular.
2. Amendments stipulated in this Annex shall take effect from the dates specified therein.
For those amendments that are to take effect at future dates as specified in Annex A, Qualified
Persons are encouraged to comply with the requirements before the effective dates. Any
proposed plans of fire safety works for new buildings or existing buildings that are submitted
to SCDF for approval on or after the effective dates shall be subjected to the amendments made
to the Fire Code.
3. Please convey the contents of this circular to members of your Board/ Institution/
Association. This circular is also available in CORENET’s e-Info:
http://www.corenet.gov.sg/einfo.
Yours faithfully
Distribution list
CEO, BCA
CEO, URA
CEO, HDB
CEO, JTC
CE, LTA
CE, Enterprise Singapore
President, REDAS
President, IFE
President, SISV
President, FSMAS
President, SCAL
Honorary Secretary, SPM
Manager (Fire Safety & Building Control Unit), DSTA
SCDF Fire Safety Standing Committee
Fire Code Review Committee
Amendment Effective
S/N Clause No Clause Status Clause Before Amendment Clause After Amendment
Date Date
1 1.1.2 01/03/2021 01/03/2021 Clarification Fire safety requirements for laboratories Fire safety requirements for laboratories
handling hazardous chemicals handling hazardous chemicals
For laboratory storing and using For laboratory Laboratories storing and using
chemicals/HazMat shall be in compliance chemicals/HazMat shall be in compliance
with NFPA 45, except for the Maximum comply with SS 641NFPA 45, except for the
Allowable Quantity (MAQ) which shall Maximum Allowable Quantity (MAQ)
comply with the figures released by SCDF. which shall comply with the figures released
by SCDF.
2 1.1.6 01/03/2021 01/03/2021 Clarification Nil Fire safety requirements for open plant
processing structure
3 1.1.7 01/03/2021 01/03/2021 Clarification Nil Fire safety requirements for pipeline service
corridors
4 1.1.8 01/03/2021 01/03/2021 Clarification Nil Fire safety requirement for storage of
flammable liquids
The safe storage of flammable liquids shall
comply with SS 532.
…………………..
6 2.3.3c.(5) 01/03/2021 01/03/2021 Clarification (4) There shall be no unprotected (4) There shall be no unprotected
openings of occupancy area or openings of occupancy area or
combustible material/construction combustible material/construction
within 3m from discharge point of within 3m from discharge point of the
the exit staircase (both internal and exit staircase (both internal and
external). This distance can be external). This distance can be
reduced to 1.5m if the unprotected reduced to 1.5m if the unprotected
openings are along the same plane openings are along the same plane of
of the staircase exit. the staircase exit.
7 3.8.6c. 01/03/2021 01/09/2021 Revised/ Nil Any door fitted to an opening in protecting
Clarification structure of a shaft containing services, such
as electrical and telecommunication cables,
pipes (including gas pipe in separate shaft),
ducts etc., is not required to comply with the
requirements in Cl.2.3.9d.(2) if it is fitted
with a self-closing device. Rising mains and
hose reel doors shall not be fitted with self-
closing device and shall comply with the
stipulated corridor width when the door is in
its fully opened position. Areas within the
swing paths of the rising mains and hose reel
doors shall be clear of any
obstruction/storage at all times.
Exception
11 7.4.4d.(15) 01/03/2021 01/03/2021 Reinstatement Nil (15) There shall be at least one viable
of past approach route (i.e. where acceptance
requirement criteria for firefighters are in
accordance with Cl.7.4.4g. and
Diagram 7.4.4e.(4)-2) for the
firefighters to any possible fire
location up to a distance of 5m from
that fire. As such, information as to
the viable approach route shall be
displayed at the main fire alarm
panel. This can be achieved by
arranging the sprinkler control zone
to correspond with that of the smoke
control zone. Upon detection of the
fire within a particular smoke control
zone / sprinkler zone, reference can
be made to the display showing the
viable approach route for that
particular smoke control zone.
12 7.4.4.g.(1) 01/03/2021 01/03/2021 Reinstatement Exhaust fan design Exhaust fan design
of past
requirement (1) The car park shall be provided with at (1) The car park shall be provided with at
least 12 air changes per hour during a least 12 air changes per hour during a
fire. fire. A lower air change not less than 9
air changes can be permitted provided
(2) ……………….. the acceptance criteria stipulated in
the Cl.7.4.4g.(1)(b) can be achieved
through fire modelling:
* Smoke temperature
shall not exceed
250C at a height of
1.7m from floor level.
* Visibility shall not be
less than 5m at a
height of 1.7m from
floor level.
Where :
B = distance/width/height from
actual test profile
A sensitivity study is to
be carried out to show
the impact of 1 group of
jet fan failure nearest the
fire on the overall
effectiveness of the jet
fans system. This study
is applicable to both fire
modelling and hot smoke
test. Notwithstanding the
failure of 1 group of jet
fans, the acceptance
criteria must still be
maintained.
15 8.1.7f. 01/03/2021 01/03/2021 Clarification Self-illuminating signs Self-illuminating signs Self-luminous sign
(1) All door closers (regardless if (1) All door closers (regardless if
concealed or surface-mounted) concealed, or surface-mounted or
shall have their own CoCs. floor-mounted) shall have their own
CoCs.
(2) For concealed door closers, these (2) For concealed door closers, these
shall be tested together with the shall be tested together with the
specific type of fire-rated door (i.e. specific type of fire-rated door (i.e.
brand, model, fire performance), brand, model, fire performance),
and their CoC numbers and and their CoC numbers and
specifications shall be included in specifications The door closer
the appendix for that related fire specifications and CoC
door. number/CoC holder company name
shall be included in the appendix for
(3) Uninsulated surface-mounted door that related fire door.
closers shall only be used on
uninsulated doors. Insulated (3) Uninsulated surface-mounted door
surface-mounted door closers may closers shall only be used on
be used on either insulated or uninsulated doors. Insulated
uninsulated doors. surface-mounted door closers may
be used on either insulated or
(4) The 6-digit coding system uninsulated doors.
indicating the performance of the
door closer, as stipulated in SS (3) The 6-digit coding system
332 Cl 6 Annex C or EN 1154, indicating the performance of the
shall be stored within the QR code door closer, as stipulated in SS 332
on the serial label for the door Cl 6 Annex C or EN 1154, shall be
closer. stored within the QR code on the
serial label for imprinted on the
(5) The following statement shall be door closer.
included in the appendix of the
CoC:
“For surface-mounted door (4) The following statement shall be
closers, the selected door closer included in the appendix of the
shall meet the performance CoC:
requirements needed for the
respective fire-rated door, in “For surface-mounted door closers,
accordance with SS 332 Cl 6 Annex the selected door closer shall meet
C. the performance requirements
needed for the respective fire-rated
Surface-mounted door closers door, in accordance with SS 332 Cl
tested with uninsulated fire-rated 6 Annex C.
doors can be installed on insulated
or uninsulated fire-rated doors
Surface-mounted door closers tested
(subject to the maximum fire-rating
with uninsulated fire-rated doors can
attained by the door closer in a fire
be installed on insulated or
test). Surface-mounted door closers
uninsulated fire-rated doors (subject
tested with insulated fire-rated
to the maximum fire-rating attained
doors can only be installed on
by the door closer in a fire test).
insulated fire-rated doors.”
Surface-mounted door closers tested
with insulated fire-rated doors can
only be installed on insulated fire-
rated doors.”