Professional Documents
Culture Documents
49-55 3m811 - ENG72dpi
49-55 3m811 - ENG72dpi
The railway
connection
Frequency converters for railway power supply
Gerhard Linhofer, Philippe Maibach, Niklaus Umbricht
Converters
∼ ∼
was adopted. 50 kV, 50 Hz AC converter 132 kV, 16.7 Hz of GTOs (gate turn-off thyris-
tors), that self-commutated
Railways operated with low- =
converter
= voltage source converters
frequency single-phase alter- could be built.
nating current can be found
Converters
The interconnection of a three-phase act as a voltage and reactive power semiconductors. This technology was
and a single-phase grid places higher source, but must also be able to han- eventually applied to a railway con-
demands on both rotary converters dle – without interruption – the transi- verter station in Karlsfeld (Germany)
and power-electronic converters than tion from interconnected system oper- with a rating of 2 × 50 MW/67 MVA put
the interconnection of two three- ation to island operation in case of into service in 1999.
phase grids. One principle reason for disturbances in the grid. Furthermore,
this is the fact that the power in the it must be capable of acting as the The next step was the development of
single-phase grid oscillates at twice sole power supply to one isolated sec- a new semiconductor element, the in-
the grid frequency. In the case of tion of railway, and be able to re-syn- tegrated gate-commutated thyristor
rotary converters, these torque and chronize with the rest of the railway- (IGCT).1) This was a development of
power fluctuations are absorbed and side grid after a disturbance has been the GTO and featured much better
damped by the rotating masses. The cleared 1 . switching capabilities, lower losses,
resulting vibrations must however be and the low-inductance gate unit as
absorbed by their mechanical anchor- Examples of frequency converters an integrated “component.” The com-
ing and its foundations. This leads to Static converter technology has a long pact design finally led to the develop-
additional complexity in the design of tradition at ABB. The first railway ment of standardized converter mod-
both the machine and its foundations. power supply converters were taken ules and permitted converters of dif-
into operation in Sweden. However, ferent power classes to be built. To-
the technology deployed was not very day, 21 converters in the 15 to 20 MW
Only after the emergence suitable for use in central Europe range are in operation and performing
of powerful turn-off semi- where the structure of the railway to the customers’ fullest satisfaction.
conductors in the form of power grid was considerably different Due to the modular design, other
and the requirements on the voltage power classes can be implemented
GTOs (gate turn-off thyris- quality higher. The first two modern very easily, most appropriately in
tors), could self-commu- frequency converters, rated at 25 MVA steps of 15 MW. These are achieved by
each, were put into operation in 1994 connecting the converter modules and
tated voltage source con- in Giubiasco (Switzerland). Following the converters based on them in par-
verters be built. the success of this project, GTO tech- allel.
nology was developed further, and in
Where voltage converters are used in 1996 a 100 MVA converter went into This converter generation sets new
this application, the oscillation is fil- service in Bremen (Germany). This standards in terms of performance,
tered using a capacitor bank and an converter was equipped with “hard- footprint and short erection/commis-
inductance, tuned to double the oper- driven” GTOs. These were GTOs with sioning times. The positive feedback
ating frequency of the single-phase a concentric gate and a gate unit feed-
grid. ing the control signal to the gate via Footnote
an extremely low-inductance lead. 1)
For more background on IGCTs, see “A tiny dot can
Another challenge lies in the fact that The result was a substantially im- change the world” on pages 15–18 of this edition of
such a system does not only have to proved switching performance for the ABB Review.
Converters
from customers shows that the stan- should not be too low because of the (a water-glycol mixture) is fed via
dardized railway converter from ABB harmonics generated. Hence, there is hose connections to the heat sinks.
is well suited to cover their needs. an optimization potential between The mechanical structure of the dou-
losses and harmonics. An elegant way ble stack allows a very compact de-
The base module to partially overcome this dilemma is sign. This helps achieve the required
The “heart” of the converter module, to choose a multi-level topology. This low stray inductance values within the
the IGCT, is shown in 2 . The IGCT allows the converter to be operated stack allowing the semiconductors to
combines the advantages of the GTO with a relatively low switching fre- be utilized to the optimum. Neverthe-
and the IGBT (insulated-gate bipolar quency and at the same time achieve less, access to all semiconductors in
transistor), ie, robustness, low switch- good harmonic performance. the stack is still possible permitting
ing and conduction losses as well as a easy replacement. Each semiconductor
fast switching capability. The proper- can be replaced with the help of a
ties of this semiconductor element re-
The IGCT combines the simple tool without interrupting the
main unsurpassed for the application advantages of the GTO cooling circuit. 4 shows an example of
discussed here (high power, medium and the IGBT, ie, robust- such a double stack.
voltage). An IGBT for the same appli-
cation (high-voltage IGBT, IEGT), for ness, low switching and Example: 15–20 MW class converter
example, exhibits comparable switch- conduction losses as 5 shows the schematic of a complete
Converters
can be used to form a single-phase the DC side by a common bus bar third and fifth harmonics of the rail-
H-bridge. A double-phase module carrying the connections for the indi- way grid 5f
consists of the same elements as vidual converter modules – for the
described above for the 50 Hz con- directly coupled DC link capacitors as Both DC link filters – together with
verter. well as for the DC link filter banks the directly-coupled capacitors – also
Circuitry and control method: The and for voltage measurements. serve as energy storage. This is re-
16.7 Hz converter is implemented in quired for control reasons. The capac-
an eight-step configuration. The The DC link forms the connection ity of the energy storage is sufficient
converter output voltage levels are between the 50 Hz and 16.7 Hz con- to face an unexpected load shedding
summed up by means of series con- verters. The DC link consists of the of P = 100 percent fast enough to
nection of the line side transformer following main components: keep the DC-link voltage within speci-
windings of the four offset-pulsed Directly coupled capacitor bank fied limits.
three-level H-bridges. The individu- used as energy storage
al H-bridges are operated in three- 33.4 Hz filter to absorb the power 33.4 Hz filter
pulse mode using a conventional fluctuation from the railway grid 5e The purpose of the 33.4 Hz notch fil-
PWM (pulse-width modulation) High-pass filter to absorb the higher ter is to absorb the power pulsations
technique. frequency harmonics from the rail- from the railway grid 5e . Despite the
way grid, in particular the distinct high quality factor of approximately
A multi-level topology
allows the converter to be 5 Schematic diagram of a converter station
b
2
Voltage limiter 3
Should the DC link voltage exceed an
b
upper threshold, it is discharged via a a
Converters
200 (ie, low damping), the filter ex- harmonic of the fundamental frequen- Converter container
hibits a relatively broad-banded char- cy of the railway grid. This is due to The converter and the associated con-
acteristic around its center frequency the distinctive third and fifth harmon- trol system come fully wired and test-
due to its high capacitive perfor- ics of the railway grid voltage which ed in a weatherproof container. The
mance. This allows specified railway are reflected as second, fourth and cooling system is supplied in a sepa-
frequency deviations to be absorbed. sixth in the DC link. The higher-fre- rate container. Both containers are
In addition, filter losses are relatively quency harmonics from the three- mounted onto a common support
low as the capacitors generally exhibit phase grid and the railway grid as base. 6 shows a cross-sectional view
significantly lower losses than the well as those caused by the pulsing of the converter container.
reactors. are partially absorbed by this filter as
well but mainly by the directly cou-
High-pass filter pled capacitors of the converter.
Compared with the typical
The high-pass filter absorbs the lower- Hence, the expected harmonics in frequency spectrum of
frequency harmonics originating main- these grids are also being taken into machines, the frequency
ly from the railway grid 5f . The filter account in the dimensioning of these
is set up as damped second-order ab- components. spectrum of the output
sorption circuit tuned below the fifth voltage formed by the
individual levels exhibits
7 The three-phase voltages on the connection point of the 50 Hz grid
only very low harmonics in
50 uac50 L1
the low frequency range.
40 uac50 L2
30 uac50 L3
20 Converter transformers
10 Voltages
50 Hz transformer: The 50 Hz trans-
kV
0
-10 former of the 50 Hz converter feeds
-20 the two IGCT-based three-phase
-30
-40
-50 (ms)
Factbox Advantages of static (power
-46.9 -40.0 -30.0 -20.0 -10.0 0.0 10.0 20.0 30.0 40.0 46.9
electronic) frequency converters in
comparison with rotary converters
c f
f
f Availability
f g
e
e
e
g
g Due to longer maintenance downtimes
d g
g
g and repair times, the availability of rotary
g
converters is considerably lower.
a
b Operational behavior
Due to the absence of rotating masses in
a Space cooler g Valve-based electronics m Event printer
static converters, the response times are
b Cooling air h Auxiliary power n UPS considerably shorter. Potential stability
c C bank / DC bus bar i Open-loop control o HMI (Human Machine Interface) problems in case of grid disturbances due
d Voltage limiter j Closed-loop control to rotor oscillations do not exist.
e 50 Hz converter k Measurement
f 16.7 Hz converter l Protection
Converters
bridges. A three-phase transformer tertiary windings or to the railway 8 shows a converter group in a sub-
consists either of a three-limb core grid. station with four converters of the
in double-tier design with interme- 15–20 MW class.
diate yoke or of two three-limb Line filter
cores contained in one tank. Each On the 16.7 Hz side, a filter is used to Outlook
(part-) limb carries a high-voltage reduce the very low harmonic distor- ABB’s relatively large market share for
winding and a valve-side winding. tion caused by the converter to even this type of system shows that the tar-
The two high-voltage part-windings lower values. On the 50 Hz side, this geted development of the converter
are connected in series. The high- is required in some cases as well. technology was in accordance with
voltage winding is Y-connected. The the customers’ requirements. In addi-
two valve-side windings are electri- The output voltages of the IGCT con- tion, the modular approach allows
cally offset by 30° (Y/D connection) verters form rectangular pulses with a a flexible response to various perfor-
to allow a 12-pulse operation of the controllable width. Compared with the mance requirements. Converter units
converters. typical frequency spectrum of ma- rated at 30 MW and higher are cur-
The resulting connection is: chines, the frequency spectrum of the rently under construction, and huge
YN y0 d11 output voltage formed by the individ- efforts are being made by ABB to
16.7 Hz transformer: The 16.7 Hz ual levels exhibits only very low har- remain successful on the market with
transformer of the 16.7 Hz converter monics in the low frequency range. this highly demanding technology.
serves to add up the four partial With regard to the grid, the converter
voltages to a nearly sinusoidal sin- represents a harmonic voltage source.
gle-phase voltage with a rated fre- The inductance of the transformer has
quency of 16.7 Hz. The transformer a damping effect that is particularly
consists of four single-phase units. marked for the higher current har-
The rectangular partial voltages are monics. This in turn positively affects
generated from a DC voltage source the quality of the grid voltage. To fur-
(DC link) with the help of four sin- ther enhance the effect of the trans-
gle-phase IGCT converter bridges former inductance, a filter is provided,
using the pulse width modulation which further reduces the harmonic
method and fed to the four valve- voltages. The resulting harmonic dis-
side windings of the transformer. tortions remain below the required
The adding-up and adaptation to values. 7 illustrates the good quality Gerhard Linhofer
the railway grid voltage is done in of the voltage on the grid connection Philippe Maibach
the high-voltage winding. A filter is point of a converter (oscillogram Niklaus Umbricht
connected to the series-connected recorded during commissioning). ABB Automation Products
Turgi, Switzerland
gerhard.o.linhofer@ch.abb.com
philippe.maibach@ch.abb.com
8 15-20 MW class frequency converter station for the power exchange between the 50 Hz
niklaus.umbricht@ch.abb.com
national grid and the single-phase 16.7 Hz railway grid. On the left the 50 Hz transformer with
three-phase AC filters mounted on the gantry above, in the middle the converter container,
and on the right the single-phase low-frequency transformer. References
[1] Gaupp, O., Linhofer, G., Lochner, G., Zanini, P.
Powerful static frequency converters for transal-
pine rail routes. ABB Review 5/95, 4–10.
[2] Lönard, D., Northe, J., Wensky, D. Statische
Bahnstromrichter – Systemübersicht ausgeführter
Anlagen. Elektrische Bahnen 6/95, 179–190.
[3] Mathis, P. Statischer Umrichter Giubiasco der
Schweizerischen Bundesbahnen. Elektrische
Bahnen 6/95, 194–200.
[4] Steimer, P., Grüning, H., Werninger, J., Dähler,
P., Linhofer, G., Boeck, R. Series connection of
GTO thyristors for high-power static frequency
converters. ABB Review 5/96, 14–20.
[5] Steimer, P., Grüning, H.P., Werninger, J.,
Carroll, E., Klaka, S., Linder, S. IGCT – a new,
emerging technology for high-power, low-cost
inverters. ABB Review 5/1998, 34–42.
[6] Meyer, M., Thoma, M. Netzkompatibilitätsstudie
und -messungen für die Umrichteranlage Wimmis.
Elektrische Bahnen 12/2006, 567–574.
[7] Jampen, U., Thoma, M. Statische Frequenz-
umrichteranlage Wimmis. Elektrische Bahnen
12/2006, 576–583.