Un [V] 13200

Ik LLL [kA] 5.4


Un [V] 13200 P [kW] 15315.7
Ik LLL [kA] 5.4 Q [kvar] 12504.3
P [kW] 15315.7
Q [kvar] 12504.3

SUBESTACIÓN DE ENTRADA: SUB 0

-QF1 -QS4 -QS6 -QS8 -QS11 -QS13 -QF1


1VCF338113R1322 GSEC 17.06.21 GSEC 17.06.21 GSEC 17.06.21 GSEC 17.06.21 GSEC 17.06.21 1VCF338113R1322
VD4/R 17.12.16 P230 Acometida Sub 1 Alm Acometida Sub 2 Arroz-Maiz Ik max = 5.3 kA Acometida Sub 4 Galciar Acometida Sub Saceites VD4/R 17.12.16 P230
TA 1000A Ik max = 5.3 kA Ik max = 5.3 kA 3I0 = 0.1 kA Ik max = 5.3 kA Ik max = 5.3 kA TA 1000A
REF601 CEI 0-16 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA REF601 CEI 0-16
IB = 864.0 A IB = 864.0 A
Cosphi = 0.77 Cosphi = 0.77
Ik max = 5.3 kA Ik max = 5.3 kA
3I0 = 0.05 [kA] 3I0 = 0.05 [kA]

-QS2 -QF2 -QF3 -QF4 -QF5 -QF6 -QS2


Acometida General 1VCF338213R1112 1VCF338213R1112 1VCF338213R1112 1VCF338213R1112 1VCF338213R1112 Acometida General
IB = 864.0 A VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 IB = 864.0 A
Cosphi = 0.77 KECA250B1 (80A) KECA250B1 (250A) KECA250B1 (250A) KECA250B1 (250A) KECA250B1 (80A) Cosphi = 0.77
Ik max = 5.3 kA REF601 CEI 0-16 REF601 CEI 0-16 REF601 CEI 0-16 REF601 CEI 0-16 REF601 CEI 0-16 Ik max = 5.3 kA
3I0 = 0.1 kA IB = 140.4 A IB = 262.5 A IB = 461.1 A IB = 335.9 A IB = 125.2 A 3I0 = 0.1 kA
Cosphi = 0.78 Cosphi = 0.77 Cosphi = 0.77 Cosphi = 0.77 Cosphi = 0.78
Ik max = 5.3 kA Ik max = 5.3 kA Ik max = 5.3 kA Ik max = 5.3 kA Ik max = 5.3 kA
3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA]

-QE1 -QE3 -QE5 -QE9 -QE10 -QE12 -QE1


24 kV 25 Ka 24 kV 25 Ka 24 kV 25 Ka 24 kV 25 Ka 24 kV 25 Ka 24 kV 25 Ka 24 kV 25 Ka
Acometida General Acometida Sub 1 Alm Acometida Sub 2 Arroz-Maiz Ik max = 5.3 kA Acometida Sub 4 Galciar Acometida Sub Saceites Acometida General
Ik max = 5.3 kA Ik max = 5.3 kA Ik max = 5.3 kA 3I0 = 0.1 kA Ik max = 5.3 kA Ik max = 5.3 kA Ik max = 5.3 kA
3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA

-WC1 -WC2 -WC3 -WC4 -WC5 -WC1


Acometida General Acometida Sub 1 Alm Acometida Sub 2 Arroz-Maiz Acometida Sub 4 Galciar Acometida Sub Saceites Acometida General
3x(1x630)/16 3x(1x50)/16 3x(1x70)/16 3x(1x95)/16 3x(1x50)/16 3x(1x630)/16
Ib = 864.0 A IB = 140.4 A IB = 262.5 A IB = 335.9 A IB = 125.2 A Ib = 864.0 A
Iz = 917.8 A Iz = 229.9 A Iz = 302.5 A Iz = 339.6 A Iz = 278.4 A Iz = 917.8 A
dV = 0.27 % du = 0.02 du = 0.29 du = 0.33 du = 0.51 dV = 0.27 %
L = 160 m L = 20 m L = 250 m L = 266 m L = 654 m L = 160 m

SUBESTACIÓN ALMACENAMIENTO: SUB 1 SUBESTACIÓN ARROZ: SUB 2 SUBESTACIÓN GLACIAR: SUB 3 SUBESTACIÓN SACEITES: SUB 4

-QF7 -QS17 -QS19 -QF10 -QS23 -QS25 -QS41 -QF13 -QS29 -QS31 -QS33 -QF17 -QS37 -QS39
1VCF338213R1112 GSEC 17.06.21 GSEC 17.06.21 1VCF338213R1112 GSEC 17.06.21 GSEC 17.06.21 GSEC 17.06.21 1VCF338213R1112 GSEC 17.06.21 GSEC 17.06.21 GSEC 17.06.21 1VCF338213R1112 GSEC 17.06.21 GSEC 17.06.21
VD4/R-SEC 17.06.12P230 Acometida Alm Sub 1 Aco Trafo 1 Sub Alm VD4/R-SEC 17.06.12P230 Aco Trafo 1 Sub Arroz Aco Trafo 2 Sub Arroz Aco TRafo 3 Sub Arroz VD4/R-SEC 17.06.12P230 Trafo 1 sub glaciar Trafo 2 Sub Glaciar Trafo 3 Sub Glaciar VD4/R-SEC 17.06.12P230 Trafo 1 Sub Saceites Tarfo 2 Sub Saceites
KECA250B1 (80A) Ik max = 5.3 kA Ik max = 5.3 kA KECA250B1 (250A) Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA KECA250B1 (250A) Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA KECA250B1 (80A) Ik max = 4.7 kA Ik max = 4.7 kA
REF601 CEI 0-16 3I0 = 0.1 kA 3I0 = 0.1 kA REF601 CEI 0-16 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA REF601 CEI 0-16 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA REF601 CEI 0-16 3I0 = 0.1 kA 3I0 = 0.1 kA
IB = 140.4 A IB = 262.5 A IB = 335.9 A IB = 125.2 A
Cosphi = 0.78 Cosphi = 0.77 Cosphi = 0.77 Cosphi = 0.78
Ik max = 5.3 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 4.7 kA
3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA]

-QS15 -QF8 -QF9 -QS21 -QF11 -QF12 -QF38 -QS27 -QF14 -QF15 -QF16 -QS35 -QF18 -QF19
IB = 140.4 A 1VCF338213R1112 1VCF338213R1112 IB = 262.5 A 1VCF338213R1112 1VCF338213R1112 1VCF338213R1112 IB = 335.9 A 1VCF338213R1112 1VCF338213R1112 1VCF338213R1112 IB = 125.2 A 1VCF338213R1112 1VCF338213R1112
Cosphi = 0.78 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 Cosphi = 0.77 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 Cosphi = 0.77 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230 Cosphi = 0.78 VD4/R-SEC 17.06.12P230 VD4/R-SEC 17.06.12P230
Ik max = 5.3 kA KECA250B1 (80A) KECA250B1 (80A) Ik max = 5.2 kA KECA250B1 (80A) KECA250B1 (80A) KECA250B1 (80A) Ik max = 5.2 kA KECA250B1 (80A) KECA250B1 (80A) KECA250B1 (80A) Ik max = 4.7 kA KECA250B1 (80A) KECA250B1 (80A)
3I0 = 0.1 kA REF601 CEI 0-16 REF601 CEI 0-16 3I0 = 0.1 kA REF601 CEI 0-16 REF601 CEI 0-16 REF601 CEI 0-16 3I0 = 0.1 kA REF601 CEI 0-16 REF601 CEI 0-16 REF601 CEI 0-16 3I0 = 0.1 kA REF601 CEI 0-16 REF601 CEI 0-16
IB = 76.9 A IB = 63.5 A IB = 95.0 A IB = 39.5 A IB = 128.0 A IB = 75.9 A IB = 130.0 A IB = 130.0 A IB = 49.9 A IB = 75.3 A
Cosphi = 0.78 Cosphi = 0.78 Cosphi = 0.78 Cosphi = 0.78 Cosphi = 0.77 Cosphi = 0.78 Cosphi = 0.77 Cosphi = 0.77 Cosphi = 0.78 Cosphi = 0.78
Ik max = 5.3 kA Ik max = 5.3 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 4.7 kA Ik max = 4.7 kA
3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA] 3I0 = 0.05 [kA]

-QE14 -QE16 -QE18 -QE20 -QE22 -QE24 -QE40 -QE26 -QE28 -QE30 -QE32 -QE34 -QE36 -QE38
Ik max = 5.3 kA 24 kV 25 Ka 24 kV 25 Ka Ik max = 5.2 kA 24 kV 25 Ka 24 kV 25 Ka 24 kV 25 Ka Ik max = 5.2 kA 24 kV 25 Ka 24 kV 25 Ka 24 kV 25 Ka Ik max = 4.7 kA 24 kV 25 Ka 24 kV 25 Ka
3I0 = 0.1 kA Acometida Alm Sub 1 Aco Trafo 1 Sub Alm 3I0 = 0.1 kA Aco Trafo 1 Sub Arroz Aco Trafo 2 Sub Arroz Aco TRafo 3 Sub Arroz 3I0 = 0.1 kA Trafo 1 sub glaciar Trafo 2 Sub Glaciar Trafo 3 Sub Glaciar 3I0 = 0.1 kA Trafo 1 Sub Saceites Tarfo 2 Sub Saceites
Ik max = 5.3 kA Ik max = 5.3 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 5.2 kA Ik max = 4.7 kA Ik max = 4.7 kA
3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA 3I0 = 0.1 kA

-WC7 -WC8 -WC10 -WC11 -WC19 -WC13 -WC14 -WC15 -WC17 -WC18
Acometida Alm Sub 1 Aco Trafo 1 Sub Alm Aco Trafo 1 Sub Arroz Aco Trafo 2 Sub Arroz Aco TRafo 3 Sub Arroz Trafo 1 sub glaciar Trafo 2 Sub Glaciar Trafo 3 Sub Glaciar Trafo 1 Sub Saceites Tarfo 2 Sub Saceites
3x(1x50)/16 3x(1x50)/16 3x(1x50)/16 3x(1x50)/16 3x(1x50)/16 3x(1x50)/16 3x(1x50)/16 3x(1x50)/16 3x(1x50)/16 3x(1x50)/16
IB = 76.9 A IB = 63.5 A IB = 95.0 A IB = 39.5 A IB = 128.0 A IB = 75.9 A IB = 130.0 A IB = 130.0 A IB = 49.9 A IB = 75.3 A
Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A Iz = 236.0 A
du = 0.01 du = 0.00 du = 0.01 du = 0.00 du = 0.01 du = 0.01 du = 0.01 du = 0.01 du = 0.00 du = 0.01
L = 15 m L = 15 m L = 15 m L = 15 m L = 20 m L = 15 m L = 15 m L = 20 m L = 15 m L = 15 m

-TM11 -TM12 -TM13 -TM14 -TM15 -TM16 -TM17 -TM18 -TM19 -TM20
Un2 = 480 V Un2 = 480 V Un2 = 480 V Un2 = 480 V Un2 = 480 V Un2 = 480 V Un2 = 480 V Un2 = 480 V Un2 = 480 V Un2 = 480 V
Sn = 2000 kVA Sn = 1500 kVA Sn = 2500 kVA Sn = 1000 kVA Sn = 3000 kVA Sn = 2000 kVA Sn = 3000 kVA Sn = 3000 kVA Sn = 1250 kVA Sn = 2000 kVA
Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C Sec.: LLLN / TN-C

-BW21 -BW22 -BW23 -BW24 -BW25 -BW26 -BW27 -BW28 -BW29 -BW30
2500A Cu Busway 2500A Cu Busway 4000A Cu Busway 1250A Cu Busway 5000A Cu Busway 2500A Cu Busway 5000A Cu Busway 5000A Cu Busway 2000A Cu Busway 2500A Cu Busway
L = 10 m L = 10 m L = 10 m L = 10 m L = 10 m L = 10 m L = 10 m L = 10 m L = 10 m L = 10 m
du = 0.21 du = 0.16 du = 0.16 du = 0.21 du = 0.16 du = 0.21 du = 0.16 du = 0.16 du = 0.16 du = 0.21
IB = 2114.9 A IB = 1745.0 A IB = 2612.5 A IB = 1086.5 A IB = 3520.6 A IB = 2087.8 A IB = 3574.8 A IB = 3574.8 A IB = 1372.1 A IB = 2071.2 A
Iz = 2650.0 A Iz = 2650.0 A Iz = 4240.0 A Iz = 1325.0 A Iz = 5300.0 A Iz = 2650.0 A Iz = 5300.0 A Iz = 5300.0 A Iz = 2120.0 A Iz = 2650.0 A

-B1 -B2 -B3 -B4 -B5 -B6 -B7 -B8 -B9 -B10
U=459.1 V U=457.3 V U=457.8 V U=456.6 V U=452.6 V U=457.9 V U=452.0 V U=452.0 V U=456.1 V U=457.2 V
IB = 2114.9 A IB = 1745.0 A IB = 2612.5 A IB = 1086.5 A IB = 3520.6 A IB = 2087.8 A IB = 3574.8 A IB = 3574.8 A IB = 1372.1 A IB = 2071.2 A
Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80 Cosphi = 0.80
Ik max = 33.9 kA Ik max = 26.9 kA Ik max = 40.5 kA Ik max = 18.5 kA Ik max = 42.8 kA Ik max = 33.8 kA Ik max = 42.8 kA Ik max = 42.8 kA Ik max = 22.4 kA Ik max = 33.2 kA
Ik LLL = 33.1 kA Ik LLL = 26.4 kA Ik LLL = 38.9 kA Ik LLL = 18.5 kA Ik LLL = 40.0 kA Ik LLL = 32.9 kA Ik LLL = 40.0 kA Ik LLL = 40.0 kA Ik LLL = 22.2 kA Ik LLL = 32.1 kA
-QF20 -QF21 -QF22 -QF23 -QF24 -QF25 -QF26 -QF27 -QF40 -QF39 -QF28 -QF29 -QF30 -QF31 -QF32 -QF33 -QF34 -QF35 -QF36 -QF37
T8L 2500 PR332-LI 2500A XT1H 160 TMF 16-450 T8L 2000 PR332-LI 2000A A3S 400 TMF 320-3200 T8L 3200 PR332-LI 3200A XT1H 160 TMF 16-450 T7S 1250 PR231-LS/I 1250A A2N 250 TMF 125-1250 E4.2N 4000 Ekip Dip LI 4000 XT1H 160 TMF 16-450 T8L 2500 PR332-LI 2500A XT1H 160 TMF 16-450 E4.2N 4000 Ekip Dip LI 4000 XT1H 160 TMF 16-450 E4.2N 4000 Ekip Dip LI 4000 XT1H 160 TMF 16-450 T7S 1600 PR231-LS/I 1600A A2N 250 TMF 125-1250 T8L 2500 PR332-LI 2500A A3S 400 TMF 320-3200
Trafo 1 Sub Alm Bco Condesadores Trafo 2 Sub Alm Bco Condesadores Trafo 1 Sub Arroz Bco Condesadores Trafo 2 Sub Arroz Bco Condesadores Trafo 3 Sub Arroz Bco Condesadores Trafo 1 Sub Glaciar Bco Condesadores Trafo 2 Sub Glaciar Bco Condesadores Trafo 3 Sub Glaciar Bco Condesadores Trafo 1 Sub Saceites Bco Condesadores Trafo 2 Sub Saceites Bco Condesadores

-L1 -L2 -L3 -L4 -L10 -L5 -L6 -L7 -L8 -L9
Trafo 1 Sub Alm Trafo 2 Sub Alm Trafo 1 Sub Arroz Trafo 2 Sub Arroz Trafo 3 Sub Arroz Trafo 1 Sub Glaciar Trafo 2 Sub Glaciar Trafo 3 Sub Glaciar Trafo 1 Sub Saceites Trafo 2 Sub Saceites
Sn = 1761.25 [kVA] Sn = 1453.75 [kVA] Sn = 2175.00 [kVA] Sn = 906.25 [kVA] Sn = 2930.00 [kVA] Sn = 1738.75 [kVA] Sn = 2975.00 [kVA] Sn = 2975.00 [kVA] Sn = 1143.75 [kVA] Sn = 1725.00 [kVA]
Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80 Cosphi (nominal) = 0.80
In = 2118.5 [A] In = 1748.6 [A] In = 2616.1 [A] In = 1090.0 [A] In = 3524.2 [A] In = 2091.4 [A] In = 3578.4 [A] In = 3578.4 [A] In = 1375.7 [A] In = 2074.9 [A]
U = 459.1 [V] U = 457.3 [V] U = 457.8 [V] U = 456.6 [V] U = 452.6 [V] U = 457.9 [V] U = 452.0 [V] U = 452.0 [V] U = 456.1 [V] U = 457.2 [V]
dU = 4.35 % dU = 4.73 % dU = 4.62 % dU = 4.88 % dU = 5.71 % dU = 4.61 % dU = 5.82 % dU = 5.83 % dU = 4.97 % dU = 4.76 %
P = 1353.91 [kW] -C1 P = 1112.71 [kW] -C2 P = 1670.98 [kW] -C3 P = 695.03 [kW] -C4 P = 2225.37 [kW] -C10 P = 1337.31 [kW] -C5 P = 2257.65 [kW] -C6 P = 2257.65 [kW] -C7 P = 877.78 [kW] -C8 P = 1327.16 [kW] -C9
Q = 1015.43 [kvar] Sn = 5.00 kVA Q = 834.53 [kvar] Sn = 5.00 kVA Q = 1253.24 [kvar] Sn = 5.00 kVA Q = 521.27 [kvar] Sn = 5.00 kVA Q = 1669.03 [kvar] Sn = 5.00 kVA Q = 1002.98 [kvar] Sn = 5.00 kVA Q = 1693.24 [kvar] Sn = 5.00 kVA Q = 1693.24 [kvar] Sn = 5.00 kVA Q = 658.34 [kvar] Sn = 5.00 kVA Q = 995.37 [kvar] Sn = 5.00 kVA
Q = 4.78 kvar Q = 4.76 kvar Q = 4.76 kvar Q = 4.76 kvar Q = 4.71 kvar Q = 4.77 kvar Q = 4.71 kvar Q = 4.71 kvar Q = 4.75 kvar Q = 4.76 kvar
IB = 6.0 A IB = 6.0 A IB = 6.0 A IB = 6.0 A IB = 6.0 A IB = 6.0 A IB = 6.0 A IB = 6.0 A IB = 6.0 A IB = 6.0 A