WATER COOLED DX 407C CHILLER RATING

Page 1 of 1

Project 50TR @ Oprtg Date : 4/24/2013


Customer BPCL
Location Mumbai

Model Specifications
Model No. XWC4S-052AR2
Actual Capacity 43.99 TR
Compressor Input power 44.02 KW
Refrigerant R-407C

Evaporator
Leaving Temperature 7.00 °C
Entering Temperature 12.00 °C
Delta T 5.00 °C
Flow Rate 26.64 cmh
Pressure Drop 37.71kpa
Max Operating Pressure 150 psig (Water Side)
Fouling Factor 0.000180 M2 °K/W

Condenser
Leaving Temperature 37.00 °C
Entering Temperature 33.00 °C
Delta T 4.00 °C
Flow Rate 42.78cmh
Pressure Drop 34.92kpa
Max Operating Pressure 350psig (Water Side)
Fouling Factor 0.0003520 M2 °K/W
Total Heat Rejection 56.51 TR

Electrical Data
Volts/Phase/Hertz 400/3/50
Full Load Current 79.24 A
Starting Current 244.00 A
Voltage Range 380-420 V

Physical Data
Operating Weight 2050 kg
Refrigerant Charge 34 kg
Length 2250 mm
Width 1234 mm
Height 1956 mm
Compressor Type Scroll
Compressor Quantity 4
Compressor Motor Speed 2900 rpm

Part Load Data (Rated in accordance with ARI standard 550/590-2003)

% LOAD COND. INTEMP( °C) CAPACITY (TR) COMPR (KW) IKW/TON


100.00 33.00 43.99 44.02 1.00
75.00 25.66 32.99 28.05 0.85
50.00 18.33 22.00 17.55 0.80
25.00 18.33 11.00 8.77 0.80
NPLV = 0.820
This Unit is outside of the scope of AHRI certification, but is rated in accordance with AHRI Standard 550/590

Blue Star Chiller Selection Software Version (1.0 )