Safety Precautions
Read before installation and performing electrical work
Thoroughly read the following safety precautions prior to installation.
Observe these safety precautions for your safety.
This equipment may have adverse effects on the equipment on the same power supply system.
Contact the local power authority before connecting to the system.
Indicates that caution must be taken with rotating parts. (This Precautions for handling units for use with R410A
symbol is on the main unit label.) <Color: Yellow>
Indicates that the parts that are marked with this symbol pose
a risk of electric shock. (This symbol is on the main unit label.) CAUTION
<Color: Yellow>
Do not use the existing refrigerant piping.
- A large amount of chlorine that may be contained in the residual refrigerant
and refrigerator oil in the existing piping may cause the refrigerator oil in the
WARNING new unit to deteriorate.
Carefully read the labels affixed to the main unit. Use refrigerant piping materials made of phosphorus deoxidized cop-
per. Keep the inner and outer surfaces of the pipes clean and free of
such contaminants as sulfur, oxides, dust, dirt, shaving particles, oil,
WARNING and moisture.
- Contaminants in the refrigerant piping may cause the refrigerator oil to de-
Ask your dealer or a qualified technician to install the unit. teriorate.
- Improper installation by the user may result in water leakage, electric shock, Store the piping materials indoors, and keep both ends of the pipes
or fire. sealed until immediately before brazing. (Keep elbows and other joints
Properly install the unit on a surface that can withstand its weight. wrapped in plastic.)
- Unit installed on an unstable surface may fall and cause injury. - Infiltration of dust, dirt, or water into the refrigerant system may cause the
Only use specified cables. Securely connect each cable so that the ter- refrigerator oil to deteriorate or cause the compressor to malfunction.
minals do not carry the weight of the cable. Use a small amount of ester oil, ether oil, or alkyl benzene to coat flares
- Improperly connected cables may produce heat and start a fire. and flanges.
Take appropriate safety measures against wind gusts and earthquakes - Infiltration of a large amount of mineral oil may cause the refrigerator oil to
to prevent the unit from toppling over. deteriorate.
- Improper installation may cause the unit to topple over and cause injury or Charge the system with refrigerant in the liquid phase.
damage to the unit. - If gaseous refrigerant is drawn out of the cylinder first, the composition of the
Only use accessories (i.e., air cleaners, humidifiers, electric heaters) remaining refrigerant in the cylinder will change and become unsuitable for
recommended by Mitsubishi Electric. use.
Do not make any modifications or alterations to the unit. Only use R410A.
Consult your dealer for repair. - The use of other types of refrigerant that contain chloride may cause the re-
- Improper repair may result in water leakage, electric shock, or fire. frigerator oil to deteriorate.
Do not touch the heat exchanger fins with bare hands. Use a vacuum pump with a check valve.
- The fins are sharp and pose a risk of cuts. - If a vacuum pump that is not equipped with a check valve is used, the vac-
In the event of a refrigerant leak, thoroughly ventilate the room. uum pump oil may flow into the refrigerant cycle and cause the refrigerator
- If gaseous refrigerant leaks out and comes in contact with an open flame, oil to deteriorate.
toxic gases will be generated. Prepare tools for exclusive use with R410A. Do not use the following
Properly install the unit according to the instructions in the Installation tools if they have been used with the conventional refrigerant: gauge
Manual. manifold, charging hose, gas leak detector, check valve, refrigerant
- Improper installation may result in water leakage, electric shock, or fire. charge base, vacuum gauge, and refrigerant recovery equipment.
Have all electrical work performed by an authorized electrician accord- - If the refrigerant or the refrigerator oil that may be left on these tools are
ing to the local regulations and the instructions in this manual. Use a mixed in with R410A, it may cause the refrigerator oil in the new system to
dedicated circuit. deteriorate.
- Insufficient power supply capacity or improper installation of the unit may re- Infiltration of water may cause the refrigerator oil to deteriorate.
sult in malfunctions of the unit, electric shock, or fire. Leak detectors for conventional refrigerants will not detect an R410A leak
Keep electrical parts away from water. because R410A is free of chlorine.
- Wet electrical parts pose a risk of electric shock, smoke, or fire. Do not use a charging cylinder.
Securely attach the control box cover. - If a charging cylinder is used, the composition of the refrigerant in the cylin-
- If the cover is not installed properly, dust or water may infiltrate and pose a der will change and become unsuitable for use.
risk of electric shock, smoke, or fire.
Only use the type of refrigerant that is indicated on the unit when install-
HWE18160
i GB
HWE18160.book ii ページ 2019年2月18日 月曜日 午前9時59分
Exercise special care when handling tools for use with R410A.
- Infiltration of dust, dirt, or water into the refrigerant system may cause the
refrigerator oil to deteriorate.
HWE18160
ii GB
HWE18160.book 1 ページ 2019年2月18日 月曜日 午前9時59分
CONTENTS
I Features
[1] Features.................................................................................................................................... 1
II Components and Functions
[1] Components and Functions...................................................................................................... 2
III Specfications
[1] Specifications............................................................................................................................ 5
1.Specfications .......................................................................................................................... 5
2.Electrical component specifications........................................................................................ 7
HWE18160 GB
HWE18160.book 2 ページ 2019年2月18日 月曜日 午前9時59分
HWE18160 GB
HWE18160.book 1 ページ 2019年2月18日 月曜日 午前9時59分
[ I Features ]
I Features
[1] Features
HWE18160 -1- GB
HWE18160.book 2 ページ 2019年2月18日 月曜日 午前9時59分
(A)
(A) Air
(A)
HWE18160 -2- GB
HWE18160.book 3 ページ 2019年2月18日 月曜日 午前9時59分
2. Remote Controller
[PAR-40MAA]
Once the operation mode is selected, the unit will remain in the selected mode until changed.
4 3 2 1
Function buttons
7 8 9 10
1 [ON/OFF] button The functions of the function buttons change depending on the screen.
Press to turn ON/OFF the indoor unit. Refer to the button function guide that appears at the bottom of the LCD for
the functions they serve on a given screen.
2 [SELECT/HOLD] button When the system is centrally controlled, the button function guide that
Press to save the setting. corresponds to the locked button will not appear.
4 [MENU] button
Press to bring up the Main menu.
5 Backlit LCD
Operation settings will appear. 7 8 9 10 7 8 9 10
When the backlight is off, pressing any button turns the backlight on and it will
Menu screen
stay lit for a certain period of time depending on the screen. Function guide
When the backlight is off, pressing any button turns the backlight on
and does not perform its function. (except for the [ON/OFF] button)
6 ON/OFF lamp
This lamp lights up in green while the unit is in operation. It blinks while the 7 8 9 10
remote controller is starting up or when there is an error.
7 Function button [F1]
Main display: Press to change the operation mode.
Menu screen: The button function varies with the screen.
HWE18160 -3- GB
HWE18160.book 4 ページ 2019年2月18日 月曜日 午前9時59分
The main display can be displayed in two different modes: “Full” and “Basic.”
The factory setting is “Full.” To switch to the “Basic” mode, change the setting on the Main display setting.
23 12 13 14 15 16 17 18 23 2
22 3 22 3
6 19
7
8
9 20
10 4
1
1 4
11
21 2
5
5
1 Operation mode 15
Appears while the units are operated in the energy-save mode. (Will not
2 Preset temperature appear on some models of indoor units)
16
3 Clock Appears while the outdoor units are operated in the silent mode.
See the Installation Manual.
17
4 Fan speed Appears when the built-in thermistor on the remote controller is activated to
monitor the room temperature ( 11 ).
5 Button function guide
Functions of the corresponding buttons appear here. appears when the thermistor on the indoor unit is activated to monitor the
room temperature.
6
18
Appears when the ON/OFF operation is centrally controlled.
Indicates the vane setting.
7
19
Appears when the operation mode is centrally controlled.
Indicates the louver setting.
8
20
Appears when the preset temperature is centrally controlled.
Indicates the ventilation setting.
9
21
Appears when the filter reset function is centrally controlled.
Appears when the preset temperature range is restricted.
10
22 Centrally controlled
Indicates when filter needs maintenance.
Appears for a certain period of time when a centrally-controlled item is operated.
11 Room temperature
23 Preliminary error display
See the Installation Manual.
An error code appears during the preliminary error.
12
Appears when the buttons are locked. Most settings (except ON/OFF, mode, fan speed, temperature) can
be made from the Main menu.
13
Appears when the On/Off timer, Night setback, or Auto-off timer function is
enabled.
14
Appears when the Weekly timer is enabled.
HWE18160 -4- GB
HWE18160.book 5 ページ 2019年2月18日 月曜日 午前9時59分
[ III Specfications ]
III Specfications
[1] Specifications
1. Specfications
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 33°CDB/28°CWB, Outdoor 33°CDB. The set temperature of the remote controller is 18°C.
Heating: Indoor 0°CDB/-2.9°CWB, Outdoor 0°CDB/-2.9°CWB. The set temperature of the remote controller is 25°C.
*2 The values in ( ) show the height of unit with leg.
*3 The external static pressure is set to 10Pa at factory shipment.
*4 The noise level in operation is measured at 1.5m apart from the front side and the bottom side of the unit in anechoic room.
(Noise meter A-scale value) Connect the duct of 1m in length to the air outlet.
HWE18160 -5- GB
HWE18160.book 6 ページ 2019年2月18日 月曜日 午前9時59分
[ III Specfications ]
*1 Cooling/Heating capacity indicates the maximum value at operation under the following condition.
Cooling: Indoor 33°CDB/28°CWB, Outdoor 33°CDB. The set temperature of the remote controller is 18°C.
Heating: Indoor 0°CDB/-2.9°CWB, Outdoor 0°CDB/-2.9°CWB. The set temperature of the remote controller is 25°C.
*2 The values in ( ) show the height of unit with leg.
*3 The external static pressure is set to 10Pa at factory shipment.
*4 The noise level in operation is measured at 1.5m apart from the front side and the bottom side of the unit in anechoic room.
(Noise meter A-scale value) Connect the duct of 1m in length to the air outlet.
HWE18160 -6- GB
HWE18160.book 7 ページ 2019年2月18日 月曜日 午前9時59分
[ III Specfications ]
HWE18160 -7- GB
Note 1. Use an M10 screw for the wall and floor mounting bolt (field supply).
HWE18160
2. This drawing is for PFFY-P63VCM-E model, which have 4 fans.
PFFY-P40·50VCM-E models have 3 fan.
PFFY-P20·25·32VCM-E models have 2 fan.
HWE18160.book 8 ページ
Right side
view
C
23 B(Wall mounting hole pitch) 200
[ IV Outlines and Dimensions ]
51 A 150 25
20 D(Duct) 100 15
2×2-ø2.9 holes 136.5
100×(E-1)=F
[1] Outlines and Dimensions
23
10
50.5
Duct mounting holes
2 Refrigerant piping
Brazing connection (liquid)
94
1 Refrigerant piping
172
Brazing connection (gas)
274
2019年2月18日 月曜日 午前9時59分
22
655
615
-8-
Terminal block
(Power source) Knockout hole ø28
(Power source wiring)
1. PFFY-P20, 25, 32, 40, 50, 63VMC-E Bottom suction ꞏ wall mounting
Terminal block
4-14×30 Slot
Wall mounting holes Air inlet Control box
Bottom view
Air filter
GB
[Maintenance access space]
HWE18160
Secure enough access space to allow for the maintenance, inspection,
and replacement of the motor, fan, heat exchanger, drain pan and control box.
HWE18160.book 9 ページ
≤20
[ IV Outlines and Dimensions ]
≥240 ≥240
≥1000
2019年2月18日 月曜日 午前9時59分
-9-
Maintenance space
≥0
Maintenance space
≥75
Unit: mm
GB
Top view 100 Note 1. Use an M10 screw for the wall and floor mounting bolt (field supply).
HWE18160
2. This drawing is for PFFY-P63VCM-E model, which have 4 fans.
PFFY-P40·50VCM-E models have 3 fan.
PFFY-P20·25·32VCM-E models have 2 fan.
HWE18160.book 10 ページ
Right side
view
C
23 B(Wall mounting hole pitch) 200
51 H 150 25
20 D(Duct) 100 15
[ IV Outlines and Dimensions ]
50.5
view
23
10
Duct mounting holes
2 Refrigerant piping
Brazing connection (liquid)
94
1 Refrigerant piping
172
22 615
713
Terminal block
(Power source) Knockout hole ø28
- 10 -
(Power source wiring)
Terminal block
4-14×30 Slot
Wall mounting holes Air inlet Control box
25 A
J
Bottom view
10 G(Floor mounting hole pitch)
2-12×16 Slot
Floor mounting holes
100
Air filter
Model A B C D E F G H J 1 Gas pipe 2 Liquid pipe
PFFY-P20 · 25 · 3 2VCM-E 700 756 802 660 7 600 730 700 750
ø12.7 ø6.35
PFFY-P40 · 50VCM-E 900 956 1002 860 9 800 930 900 950
PFFY-P63VCM-E 1100 1156 1202 1060 11 1000 1130 1100 1150 ø15.88 ø9.52
Unit: mm
GB
[Maintenance access space]
HWE18160
Secure enough access space to allow for the maintenance, inspection,
and replacement of the motor, fan, heat exchanger, drain pan and control box.
HWE18160.book 11 ページ
≤20
[ IV Outlines and Dimensions ]
≥240 ≥240
2019年2月18日 月曜日 午前9時59分
≥1000
- 11 -
Maintenance space
≥0
Maintenance space
Unit: mm
GB
V Wiring Diagram
TO OUT DOOR UNIT TO NEXT INDOOR UNIT
BC CONTROLLER
HWE18160
FUSE(16A) BREAKER(16A)
TO MA REMOTE M-NET REMOTE CONTROLLER POWER SUPPLY
CONTROLLER DC24-30V AC220,230,240V
PULL BOX 50/60Hz
HWE18160.book 12 ページ
I.B. 21 CND 1 3 5
3456
2 SW14 (Red)
789
F0 1
AB
SW1 CN32 C DE
(BRANCH No.) CN2M SA
ZNR002
2 3
4
(White) SW12 (Blue) OFF
0 1
SW2
9
5 6
7 8
(10ths digit) SWE U
SW3 SW4 2 3
4
ON
1. PFFY-P20,25,32,40,50,63VCM-E
SW11
0 1
9
5 6
7 8
(1s digit) LED1 CN105(Red) ZNR001
SW21
U F1
CN52 SW22
(Green)
(White) CN90(White)
CN51 CN60 DC280-340V
(White) 1 Rectifier circuit *Only for PFFY-P63VCM-E
2 (Red) (White)
3 CN20 CN44
4
2019年2月18日 月曜日 午前9時59分
- 12 -
1 3 1234 1 4567
t° t° t°
M
LEV TH21 TH22 TH23 M
3~
MF NOTE)1. Symbols used in wiring diagram are
: Connector, : Terminal,
SYMBOL EXPLANATION (Heavy dotted line): Field wiring,
SYMBOL NAME SYMBOL NAME SYMBOL NAME
(Thin dotted line): Optional parts.
ACL AC reactor(Power factor improvement) I.B. Indoor controller board I.B. Indoor controller board
MF Fan Motor SA Arrester SW1 Switch (for mode selection) 2. Have all electric work done by a licensed electrician
LEV Electrical linear expansion valve F1 Fuse AC250V 6.3A SW2 Switch (for capacity code) according to the local regulations.
TB2 Power source terminal block ZNR001 Varistor SW3 Switch (for mode selection) 3. Earth leakage circuit breaker should be set up on the wiring
TB5 Transmission terminal block ZNR002 Varistor SW4 Switch (for model selection) of the power supply.
TB15 Transmission terminal block CN22 Connector (Optional Thermistor) SW11 Switch (1s digit address set)
TH21 Thermistor (inlet air temp. detection) CN32 Connector (Remote switch) SW12 Switch (10ths digit address set)
TH22 Thermistor (piping temp.detection/liquid) CN41 Connector (HA terminal-A) SW14 Switch (BRANCH No.)
TH23 Thermistor (piping temp.detection/gas) CN51 Connector (Centrally control) SW21 Switch (for static pressure selection)
CN52 Connector (Remote indication) SW22 Switch (Wireless pair No.)
CN90 Connector (Wireless) SWE Connector (emergency operation)
CN105 Connector (IT terminal) LED1 LED(Power supply)
LED2 LED(Remote controller supply)
GB
HWE18160.book 13 ページ 2019年2月18日 月曜日 午前9時59分
(A)
(B)
(G)
(D)
(H) (C)
(F)
(E) (E)
(I)
HWE18160 - 13 - GB
HWE18160.book 14 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
VII Troubleshooting
[1] Troubleshooting
1. Check methods
1. Component and check points
(1) Thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22)
Gas pipe thermistor (TH23)
Disconnect the connector and measure the resistance between terminals with a tester.
(Ambient temperature 10°C - 30°C)
Normal Abnormal
4.3k - 9.6k Open or short
(Refer to the thermistor characteristic graph below.)
Low-temperature thermistor
Room temperature thermistor (TH21)
Liquid pipe thermistor (TH22) 50
Gas pipe thermistor (TH23)
Thermistor R0 = 15 k 3%
Multiplier of B = 3480 k 2% 40
Rt = 15 exp { 3480( 1 1 )}
273+t 273
30
0°C 15k
(B)
10°C 9.6k
20°C 6.3k
25°C 5.2k 20
30°C 4.3k
40°C 3.0k
(A) Temperature (°C)
10
(B) Resistance (k )
0
-20 -10 0 10 20 30 40 50
(A)
HWE18160 - 14 - GB
HWE18160.book 15 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
12VDC
(J) (A) 6
(C) 5
4 (I)
(A) (C) 4
M 6
(E) (D) 3
5 2
1 (E) 2
3
(F) (B) (D)
(F) 1
(H)
HWE18160 - 15 - GB
HWE18160.book 16 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
2) LEV operation
(a) Close
(b) Open
(b)
(c)
(d)
(e)
When the power is turned on, a pulse signal of 2200 pulses is output (valve closure signal), to bring the valve to position A.
When the valve is operating normally, it is free of vibration noise. If the valve locks or when it goes from point E to A in the
figure, it makes louder noise than would be heard when there is an open phase.
Check for abnormal sound/vibration by placing the metal tip of a screwdriver against the valve and the handle side against
your ear.
3) Troubleshooting
HWE18160 - 16 - GB
HWE18160.book 17 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
(A)
LEV
Normally, the LEV is fully closed while the unit is in the FAN mode. If the valve is
leaky, liquid pipe thermistor reading will be lower than normal. If it is significantly
lower than the inlet temperature on the remote controller, valve closure failure is
suspected. If the amount of leakage is insignificant, replacement of LEV is unnec-
essary unless it is causing a problem.
Misconnections of Perform a visual check for disconnected connectors. Disconnect the
connectors or con- Perform a visual check of lead wire color. connectors on
tact failure the control board
and perform a
continuity test.
HWE18160 - 17 - GB
HWE18160.book 18 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
2. Troubleshooting
Symptom: Indoor unit fan does not run.
Yes
15VDC (same with the voltage between fan connector 5 (+) and 4(-))
1 - 6.5VDC (same with the voltage between fan connector 6 (+) and 4(-))
[Values for Vsp are the values that are measured with the fan motor in operation.
Vsp is 0V when the fan motor is stopped.]
Yes
Yes
HWE18160 - 18 - GB
HWE18160.book 19 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
789A
SW1
F012
3456
SW4 SW21 SW22
7 8 9 0 1
4 5 6
SW2
2 3
7 8
4 5 6
9 0 1
SW3
2 3
1) Incase using network remote controller, address is set by rotary switches. (SW11,SW12)
It is not necessary setting address in case of using unit remote controller.
3) Setting the address is combination of SW11 (1st digit address setting) and SW12 (2nd digit address setting).
Address " 3 " setting is composed SW11 " 3 " and SW12 " 0 ".
Address " 25 " setting is composed SW11 " 5 " and SW12 " 2 ".
HWE18160 - 19 - GB
HWE18160.book 20 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
CN22
CN20 Thermistor (Inlet temperature)
CNMF1 Fan motor output
CN20 1 - 4: 294 - 340 VDC
5 - 4: 15 VDC
6 - 4: 0 - 6.5 VDC
7 - 4: Stop 0 or 15 VDC
Run 7.5 VDC
CN32 (0 - 15 pulse)
(*1)
VFG Voltage on 3 of PC352 and the (-)
CN3A side of C081
(Same with the voltage between 7
(+) and 4 (-) of CNMF)
SW1 SW2 SW3 CN52 CN51 CN41 VCC Voltage between the C084 pins
SW4 SW21 SW22 15 VDC
(Same with the voltage between 5
(+) and 4 (-) of CNMF)
Vsp Voltage between the C351 pins
0VDC (with the fan stopped)
1 - 6.5VDC (with the fan in opera-
tion)
(Same with the voltage between 6
(+) and 4 (-) of CNMF)
HWE18160 - 20 - GB
HWE18160.book 21 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
PFFY-
ON ON ON ON ON ON ON
P20VCM-E
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 OFF
PFFY-
ON ON ON ON ON ON ON
P25VCM-E
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 OFF
PFFY-
ON ON ON ON ON ON ON
P32VCM-E
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 OFF
PFFY-
ON ON ON ON ON ON ON
P40VCM-E
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 OFF
PFFY-
ON ON ON ON ON ON ON
P50VCM-E
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 OFF
PFFY-
ON ON ON ON ON ON ON
P63VCM-E
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 1 2 3 4 5 6 7 8 1 2 3 4 OFF
ON
The figure at left shows that the switches 1 through 5 are set to ON and 6 through 10 are set to OFF.
1 2 3 4 5 6 7 8 9 10
6. Function setting
(1) SW1
HWE18160 - 21 - GB
HWE18160.book 22 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
(2) SW3
Note:
When the static pressure setting was set from the remote controller, the actual setting and the switch setting on the
control board may not match because the latest setting from the remote controller overrides the previous setting. To
check the latest static pressure setting, check it on the remote controller, not on the switch.
If the static pressure setting for the duct is lower than that for the unit, the fan of the unit may repeat start/stop, and
the outdoor unit may remain in a stopped state. Match the static pressure settings for the unit to that for the duct.
To set the external static pressure with the switches on the control board
To set the external static pressure from the function selection screen on the remote controller
Follow the instructions below and the instructions detailed in the remote controller manual for how to set the switches.
1. Set the function setting No. 32 (Switch setting/Function selection) to “2”.
2. Set the function setting No. 8 and No. 10 to appropriate values, according to the external static pressure.
40 Pa 2 1
60 Pa 3 1
HWE18160 - 22 - GB
HWE18160.book 23 ページ 2019年2月18日 月曜日 午前9時59分
[ VII Troubleshooting ]
8. Setting addresses
(Be sure to operate with the main power turned OFF.)
There are two types of rotary switch setting available: setting addresses 1 to 9 and over 10, and setting branch numbers.
Factory setting
Factory setting
The rotary switches are all set to “0” when shipped from the factory. These switches can be used to set unit addresses and
branch numbers at will.
The determination of indoor unit addresses varies with the system at site. Set them referring to the Data Book.
CAUTION
When the setting is enabled, the stopped fan may start operating.
HWE18160 - 23 - GB
HWE18160.book 24 ページ 2019年2月18日 月曜日 午前9時59分
HWE18160 - 24 - GB
HWE18160.book 25 ページ 2019年2月18日 月曜日 午前9時59分
(C) (B)
Fig.3
HWE18160 - 25 - GB
HWE18160.book 26 ページ 2019年2月18日 月曜日 午前9時59分
3. Drain pan
Be careful removing heavy parts.
(E)
Fig.4
3. Remove the fixing screws on the control box (F), to re-
move it. (Fig. 5)
(F)
Fig.5
4. Removing the drain pan
(1) Drain the water out of the drain pan before removing it. (a) Drain pan
(2) Pull out the drain pan in the direction of the arrow.
(Fig. 6)
(a)
Fig.6
Note:
To avoid dew condensation, use insulated screws in
the places marked with circles in Fig. 7. (a) Insulation material
(a)
(D)
Fig.7
HWE18160 - 26 - GB
HWE18160.book 27 ページ 2019年2月18日 月曜日 午前9時59分
Fig.8
2. Removing the liquid pipe and gas pipe thermistor.
(1) Remove the front plate (E) with procedure [1]-3.
(2) Remove the control box (F) with procedure [1]-3.
(3) Pull out the drain pan with procedure [1]-3.
(4) Remove a fixing screw on the heat exchanger cover (G)
to remove it. (Fig.9) (G)
Fig.9
(5) Remove the thermistor (H) from the thermistor holder (J)
on the copper tube. (Fig.10)
Fig.10
HWE18160 - 27 - GB
HWE18160.book 28 ページ 2019年2月18日 月曜日 午前9時59分
Fig.11
2. Removing the fan casing (bottom half)
(1) Squeeze the tabs on the fan casing to remove it in the di- (a) Tab
rection of arrow. (Fig. 12)
(a)
Fig.12
3. Removing the motor cable
(1) Remove the motor cable threw the rubber bush.
(L)
Fig.13
(3) Remove the fan case fixing screws to take the top half of
the fan casing off. (Fig. 14)
Fig.14
HWE18160 - 28 - GB
HWE18160.book 29 ページ 2019年2月18日 月曜日 午前9時59分
6. Bearing
P40, P50, P63 models only.
Be careful removing heavy parts.
(M)
Fig.15
(2) Remove the two bearing retainer screws to remove the
bearing. (Fig. 16)
Fig.16
HWE18160 - 29 - GB
HWE18160.book 30 ページ 2019年2月18日 月曜日 午前9時59分
7. Heat exchanger
Be careful removing heavy parts.
Fig.18
(P)
Fig.19
Fig.20
HWE18160 - 30 - GB
HWE18160.book 31 ページ 2019年2月18日 月曜日 午前9時59分
Note:
In order to attach and fix the heat exchanger, insert the (a)
hook (a) on the heat exchanger (Fig. 21) to (b) (Fig. 22).
Fig.21
(b)
Fig.22
HWE18160 - 31 - GB
HWE18160.book 32 ページ 2019年2月18日 月曜日 午前9時59分
HWE18160 - 32 - GB
HWE18160.book 33 ページ 2019年2月18日 月曜日 午前9時59分
9. Sensor position
Gas sensor
Gas sensor
Liquid sensor Liquid sensor
HWE18160 - 33 - GB