Professional Documents
Culture Documents
Book - 2-345-423
Book - 2-345-423
Book - 2-345-423
May not be reproduced in any form without permission from the publisher, except fair uses
Relay R2 R1
a) Name the relay which must operate to clear this fault? Determine its time.
b) If the relay in a) fails, name the relay which must operate to clear this fault?
Determine its time.
References
Hileman, A.R. Insulation Coordinationfor Power Systems. New York, USA: Marcel Dekker Inc.,
1999.
Golde, R.H. (Ed). Lightning, Vol. 1: Physics ofLightning; Vol. [1: Lightning Protection. London:
Academic Press, 1977.
Schonland, B.F.I. "Progressive Lightning, IV. The Discharge Mechanism." Proc. Ray Society,
Series A, 164 (1938), 132.
Abdel—Salam, M.; El—Morshedy, A.; Anis, H. and Radwan, M.R. High Voltage Engineering:
Theory and Practice. New York, USA: Marcel Dekker Inc., 2000.
Malik, N.H.; Al—Arainy, AA. and Qureshi, M.I. Electrical Insulation in Power Systems. New
York, USA: Marcel Dekker Inc., 1997.
Qureshi, M.l.; A1-Arainy, AA. and Malik, N.1-l. "Performance of Protective Rod Gaps for
Medium Voltage Networks in the Presence of Dust Particles Under Lightning Impulses." IEEE
Trans. on Power Delivery, 14, No. 4 (October 1999), 131 1—1316.
Regaller, K. (Ed) Surges in High Voltage Network. New York, USA: Plenum Press, 1980.
High Voltage Technologies Ltd. Dimensioning and Application of Metal Oxide Surge Arresters in
Medium Voltage Networks. ABB Wettingen, Switzerland, 1994.
[9] EPRI UHV Book. Transmission Line Reference Book, 345 kV and above. California, USA: EPRI,
1982.
[10] Glover, J .D. and Sarma, M.S. Power System Analysis and Design. 3"d ed., Brooks/Cole, 2002.
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
APPENDIX
Basic Circuits
When such a voltage is applied across a load, the load impedance Z and phasor
current I are related as Z = W]. For individual circuit elements such as resistance,
inductance and capacitor, the impedance values are given as follows, where j =
J: : 1 fl .
Z=R for a resistance of R (Q).
Z : jooL for an inductance of L (H).
Z = -j/(DC for a capacitance of C (F).
Z @ where Z refers to magnitude of the impedance in ohms and (I) is the phase
angle of the impedance. Value of (I) depends upon circuit elements and lies in the
range of—90o S (1) S 90°.
Knowing the phasor voltage and impedance, one can easily calculate the
phasor current I.
347
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Then V (A. l)
The sinusoidal variation with time of this current can be expressed as:
i= x/E%sin(wt+6—¢)=\/EISiD(®t+9—¢) (A2)
S=VI*=(V@)(I/—6+¢=VI@ (A.3)
Hence, the complex power depends upon the rms values of voltage and current
as well as the phase angle of impedance. The real part of S is the average power P
dissipated in the impedance and is given as:
The imaginary part of S is the reactive power Q supplied to the impedance and
is given as:
The term cos (1) is known as the powerfactor of the load and its value is S 1. If
(I) is positive, power factor is said to be lagging which implies currents lagging the
voltage in the circuit. This is a behavior of an inductive circuit. If (1) is negative,
power factor is leading since current leads the voltage in this case which is typical
for a capacitive circuit.
permitted under U.S. or applicable copyright law.
For both positive and negative values of (I), the average power P is always
positive. However, when (1) is positive, or power factor is lagging, Q is said to be
positive whereas when (I) is negative, or power factor is leading, Q is said to be
negative. Since power systems have all basic circuit elements, both P and Q are
important and must be studied. P determines the useful power in any circuit,
whereas Q determines the charging power required for capacitors and cables, etc. or
the magnetizing power requirements of inductors, machines and transformers, etc.
Following examples illustrate the basic power calculations in a single phase AC
circuit.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Appendix 349
Example A. I
Suppose a voltage V = «/2 X 120 sin (377 t + 30°) is applied to a single phase
load, and the resulting current is i = J2 X 10 sin (377 t— 30°).
(i) Find complex power S, average power P, reactive power Q and the circuit
power factor.
(ii) Find a simple series circuit which exhibits this behavior.
(iii) Find a simple parallel circuit that will exhibit this behavior.
Solution
V: 120 E V
I: 10 fl A
or 27.57 mH.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Example A.2
Repeat parts (ii) and (iii) of Example A.1 assuming that P = 600 W and Q =
1039 VAR are given.
Solution
P=12R R=Ezflz6o
12 100
Q _ 1039.23
Q : 12XL XL : 1—2 210.399
(iii) For the parallel circuit configuration, P and Q are related to V, R and XL as:
2 2
:V_ R:V_=M=24 Q
R P 600
Q:_ XL=V—=
2
120X120=13.86§2
Q 1039.23
Example A.3
A load consists of R = 10 Q, XL = 10 Q, and XC = 20 Q, all connected in
parallel across a 100 V source. Find the complex power delivered to the load, the
load power factor as well as the total current drawn by the load.
Solution
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Appendix 35 1
Total P : 1000 W
Total Q = 1000 , 500 = 500 VAR
Load power factor = cos 2657" = 0.894 lagging since Q is positive in case of
lagging power factor.
. P 1 .
Altematlvely power factor = E = % = 0.894 lagging
I
*
: E _M 211.18 126.570
v 100g
I = 11.18 /— 26.570 A. Thus current lags the voltage by 26.570 and therefore
power factor is equal to cos (26.57) : 0.894 lagging.
Three—phase windings can be connected into either star (Y) or delta (A)
configurations. Figure A.1 shows the connection arrangements for both of these
configurations. In a star configuration, one end of all three windings are joined
together to form the common or the neutral point 'n'. In a A configuration, neutral
point is not available.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a)
(b)
Fig. A.]. 3-phase generator connections (a) Y-connection; (b) A-connection.
In both types of connections, there are phase voltages, i.e. Va, V1,, V6 (or
voltages across each phase winding of the generator) and line voltages (or voltages
across two lines such as Va,n Vbc, V8”). The magnitude of such voltages is VL
whereas the magnitude of phase voltages is V.
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Appendix 3 53
Therefore, the system is generally balanced. Such a balanced system can be easily
analyzed by considering the circuit of one phase only as will be illustrated later in
this section. In such a balanced system, the three currents also exhibit 120o phase
shift and if phase a current is I/—¢ , currents in phases b and c are I/— (j)—120o and
In such a 3-phase balanced system, each phase has the same magnitude of
voltage, current and power factor. Thus, all phases have the same power. If one
phase has phasor voltage = V E and its impedance is Z /¢, then the phasor
53¢:3v1 /¢ :3v1cos¢+j3v1sin¢ VA
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Example A4
A 3—phase, Y—connected generator has balanced voltages such that Va = 120
/30° . It supplies a 3-phase balanced, Y-connected load with per phase impedance
of 8 + j6 Q. The impedance of line connecting the generator to the load is 0.1 + jl
Q per phase. Assuming a phase sequence of a,b,c, calculate:
(i) Currents in all phases.
(ii) Neutral current In.
(iii) Generator and load phase and line voltage magnitudes.
(iv) Power factor of the load.
(v) Total 3—phase active, reactive and complex powers of load.
(vi) Total 3—phase active, reactive and complex powers of line.
(v) Total 3—phase active, reactive and complex powers supplied by the generator.
Solution
(i) The circuit for phase a will be as shown in Fig. eA.3.
0.1+'1.0
permitted under U.S. or applicable copyright law.
120430062) 8+”
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Appendix 355
TotalZ:0.l+j1+8+j6:8.l+j7210.7l /40.83O Q.
Thus, I“ —_ 120/30
—=ll.20 /—10.830 A
10.71 /40.83°
II, and IL. will be only shifted in phases by 1200 each and are:
[C =11.20 /109.17° A
Phase b and c voltages will be similar, except for the phase shifts.
(iv) Power factor of the load = cos (I) = cos 36.870 = 0.8 lagging
permitted under U.S. or applicable copyright law.
(v) Three-phase load power P3¢ = 73 VL IL cos (I) = (J3) (194) (11.2) (0.8) =
3010.6 W
Similarly, Q34) = fl vL 1L sin (1) = (fi) (194) (11.2) (0.6) = 2257.9 VAR
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
It is important to note that the total complex power supplied by the generator is
also given as:
The small difference between the two values of S34, is due to rounding off
error. It is clear from this example that the conservation of active power as well as
the reactive power holds in AC systems.
Example A.5
If in the above example, the same generator and connecting lines are used.
However, the same impedances are connected in A instead of Y. What will be
complex power supplied by the generator in this case?
Solution
Using A—Y transformation, the per phase, Y—connected equivalent load
impedance will be:
2 1 . .
ZY=?A=§ (8+J6)=2.67+J2§2
Hence, ,, 120/30
,— — = 29.41 /—17.28° A
4.08 /47.28° —
The total three—phase complex power supplied by the generator will be:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Appendix 3 57
It is obvious that the power supplied in this case is different from that of the
last example which signifies the effect of load connections. This example also
illustrates how a A-connected load with Y-connected generator can be analyzed. If,
however, we have a A-connected generator, we can convert it into an equivalent Y-
connected generator and use the above procedure to analyze the circuit as illustrated
in the next example.
Example A.6
Suppose that a A-connected generator has Vab = VL fl , and phase sequence
of a,b,c (i.e. Vbc = VL /—120° and Va, = VL /120°). Find an equivalent Y—
connected generator which has the same line voltages.
Solution
Let the voltages of Y—connected generator be V“, VI, and Vc. The two possible
connections of Fig. A.l are equivalent if they produce the same line voltages.
Assume that the Y—connected generator has voltages Va : x Q , V1, : x / 6 —120°
and V6 = x /—9+120° where x and 9 should be such that the line voltages in
equivalent Y—connected generator should be the same as those given in the A—
connected generator. From Fig. A.1a, it can be seen that
VuiVabiVb=0
XE -VL fl—x/G—IZOO =0
xfl-x/G—DOO =VLE
J3 x /e+30° =vL Q
Thus \/§ x=VL orx= i. Moreover, 6+30°=00r6=-30°
J?
Thus, if Val, = VL fl and we have a,b,c as the phase sequence, the equivalent
. V 0 V o
Y-connected generator Wlll have V" = —L /—30 , V,, = —L /—150 and Vc =
permitted under U.S. or applicable copyright law.
J3 fl
% /9OO . If, however, generator voltages have phase sequence of a, c, b, the
. . V o V
voltages of equivalent Y-connected generator Will be Va = —L / 30 , V], = TL
J? 3
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(0 Average power.
(M Power factor.
(Vi) Impedance.
(a) A single phase load draws 5 MW at 0.7 lagging power factor from a
440—V line. Determine:
(i) The load current.
(ii) The load reactive power.
(iii) The load complex power.
(0 Load current;
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Appendix 3 59
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Chapter 1
361
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
A transformer can:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
15. Transient studies are used to determine transient overvoltages and currents in a
system due to:
16. An energy control center is required in a modern power system due to:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Chapter 2
1. A generating station:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) a generator.
(b) a motor.
(c) any rotating machine.
((1) Step—up transformer.
(a) directly.
(b) through a resistor.
(c) through an inductor.
(d) any of the above.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
10. Transmission voltage level in a modern and large power system is in the range
of:
13 . The highest operating voltage for underground cables in Saudi Arabia is:
(a) 220—380 kV
(b) 66—132 kV
(C) 6.6—36 kV
(d) 220-600 kV
permitted under U.S. or applicable copyright law.
(a) 220 kV
(b) 400 kV
(C) 765 kV
(d) 380 kV
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
18. When the GCC power systems are interconnected, it will form a:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Chapter 3
1. Major types of fuels used in Saudi Arabia for electric power generation are:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) 60 r.p.m.
(b) 120 r.p.m.
(c) 3600 r.p.m.
(d) 1800 r.p.m.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) a large power system with practically constant voltage at one bus.
(b) a power source with infinite power output.
(c) represented by an ideal voltage source.
((1) a and c.
(a) is fixed.
(b) is controllable.
(0) depends on load power factor.
(d) none of the above.
25. In a balanced power systems, current passing through the neutral wire is equal
to:
26. In steady state, power systems are operated with power angle around:
permitted under U.S. or applicable copyright law.
(a) 10°
(b) 30°
(c) 70°
(d) 80°
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
27. A synchronous machine having E = 1.1 p.u. is feeding an infinite bus with a
terminal voltage of 1 p.u. If the transfer reactance is 0.5 p.u., the steady state
power flow limit is:
29. The active power output of an AC generator connected to an infinite bus can be
control by:
30. The reactive power output of an AC generator connected to an infinite bus can
be controlled by:
Chapter 4
permitted under U.S. or applicable copyright law.
(a) always less than the receiving end power of this line.
(b) always more than the receiving end power of this line.
(0) always equal to the receiving end power of this line.
((1) can be greater or less than the receiving end power depending on line
parameters.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) frequency.
(b) temperature.
(c) resistivity of conductor.
(d) all of these.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
For overhead transmission lines, the geometric mean radius (GMR) depends
on:
For overhead transmission lines, the geometric mean distance (GMD) depends
on:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
15. For over—head transmission lines, the geometric mean radius (GMR) depends
on:
16. For overhead transmission lines, the geometric mean distance GMD depends
on:
(a) frequency.
(b) line length.
(c) conductor radius.
permitted under U.S. or applicable copyright law.
((1) a and b.
19. The number of subconductors in each phase of EHV lines in Saudi Arabia is:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
22. The ratio of the diameters of an ACSR conductor and a copper conductor for
the same resistance per unit length is:
(a) equal to 1.
(b) greater than 1.
(0) less than 1.
(d) none of these.
23. For a stranded conductor, the ratio of (GMR) to actual radius is:
(a) equal to 1
(b) equal to 0.7788
(c) less than 0.7788
((1) none of these.
(a) increases.
(b) decreases.
(0) remains constant.
((1) can be any of the above.
(a) increases.
(b) decreases.
(0) remains the same.
((1) becomes zero.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) decreases.
(b) increases.
(c) remains the same.
((1) all of the above.
29. As the spacing between the phase conductors increases, the line resistance:
(a) increases.
(b) decreases.
(0) remains the same.
(d) depends on inductance.
30. As the spacing between the phase conductors increases, the line inductance:
(a) increases.
(b) decreases.
(c) remains the same.
(d) depends on frequency.
31. As the spacing between the phase conductors increases, the line capacitance:
(a) increases.
(b) decreases.
(0) remains the same.
((1) changes with resistance.
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) R.
(b) 1.05 R.
(c) 1.2 R.
((1) none of these.
35. For a line with conductor spacings of 6m, 6m and 12 rn, c is:
(a) 7.56 m.
(b) 10.23 m.
(c) 8.02 m.
((1) none of these.
36. For a single circuit 3-phase line, the inductance per phase per km is of the
order of:
(a) 1 mH.
(b) 10 mH.
(c) 0.2 mH.
(d) none of these.
37. For a single circuit 3—phase line the capacitance per phase per km is of the order
of:
permitted under U.S. or applicable copyright law.
38. For a 380—kV line, the spacing between phase conductors is around:
(a) 1 m.
(b) 8 m.
(c) 24 m.
(d) 50 m.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Chapter 5
(a) long transmission lines to improve voltage under light load on the line.
(b) short transmission line to improve voltage under light load on the line.
(0) long transmission lines to improve voltage under heavy load on the line.
((1) short transmission line to improve voltage under heavy load on the line.
(a) greater than 100% at light loads and less than 100% at heavy loads.
(b) equal to 100% for short lines.
permitted under U.S. or applicable copyright law.
(0) less than 100% for all load conditions and line models.
(d) greater than 100% for long lines at light loads.
4. The real power flow on a transmission line having a sending end voltage
VS/ESs and a receiving end voltage VR/SR is principally controlled by
changing:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Avg
PR max 2 %Sin (B—S)— sin (B—(l)
(a)
B
vv s
(>
b P R max : B
S B
R_ _ —R Sin (B — a
)
Avfi
13R max : %COS (B_5)— COS (B—(X)
(C)
B
Vs VR AV§
(d) PRmaX : C—TCOS (fl—a)
B
After using 30% series compensation with a line having a series inductive
reactance of "X" means that the line's effective series reactance becomes:
(a) B=0
(b) B = 20+ YZ/Z)
(c) B = 1+ ZY/4
(d) B=2
permitted under U.S. or applicable copyright law.
(a) A<l
(b) A>1
(c) A=l
(d) A=0
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
ll. The maximum power flow through a transmission line can be increased by
installing:
12. When the load on a transmission line is equal to its surge impedance loading,
the receiving end voltage is:
13. In a long transmission tine under no load condition, the receiving end voltage is:
(a) the current at receiving end is lower than the current at sending end.
(b) the current at receiving end is higher than the current at sending end.
(C) the voltage at receiving end is lower than the voltage at sending end.
(d) the voltage at receiving end is higher than the voltage at sending end.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
16. Assume the A-constant of a long transmission line is given by |Al /_0L then:
(a) W <1
(b) lAl>1
(C) W =1
(d) W =0
17. Assume the B-constant of a long transmission line is given by [B] / B then:
18. Assume the C—constant of a long transmission line is given by |C| / X then:
21. For nominal n-model of a transmission line, the constant B is given by:
(a) B= 1
(b) B = 2(1+ YZ/4)
(c) B = 1+ZY/4
(d) B:Z
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
L
(a) (b) J; (c) x/E (d) none of these.
C
(a) VS is lagging VR
(b) VS is leading VR
(c) VS is in—phase with VR
(d) Vs = VR
24. The effect of shunt compensation of a transmission line is to decrease:
(a) increase.
(b) decrease.
(c) not change.
((1) depend upon load power factor.
26. The real power flow in a transmission line having a sending end voltage VS / 55
and a receiving end voltage VR / 5R is mainly increased by:
(a) increase.
(b) decrease.
(c) not change.
((1) depend upon generator regulation.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) increases.
(b) decreases.
(c) remains the same.
((1) depend upon series compensation.
(a) decreases.
(b) increases.
(0) remains the same.
((1) depend upon load power.
31. As compared to the sending end voltage, the receiving end voltage of a short
line under no load condition is:
(a) higher.
(b) lower.
(c) the same.
((1) much higher.
32. As compared to regulation at unity power factor, the regulation at 0.8 leading
power factor is:
(a) higher.
permitted under U.S. or applicable copyright law.
(b) lower.
(c) the same.
((1) much higher.
33. The regulation of a line at full load 0.8 power factor lagging is 11%. The
regulation at full load 0.8 power factor leading can be:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
34. For a long line, the receiving end voltage under no load condition is:
35. The shunt admittance of a line is y Siemens per unit length. The shunt
admittance for a length 6 Will be:
(a) W
(b) y12
(C) y/1
(d) yl/2
36. For a good voltage profile under load conditions, a long line needs:
37. For a good voltage profile under no load condition, a long line needs:
38. The surge impedance loading for a single circuit 220 kV line is around:
(a) 120 MW
(b) 90 MW
(c) 220 MW
permitted under U.S. or applicable copyright law.
((1) 484 MW
39. The surge impedance of a single circuit high voltage line is of the order of:
(a) 400 o
(b) 300 Q
(c) 500 Q
(d) 200 Q
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) V
(b) V
(c) N
(d) In V
42. The real power transfer over a line mainly depends on:
(a) power—angle.
0?) NJ - lVrl
(C) Vs
(d) Vr
43. The velocity of propagation of electromagnetic waves on overhead lines is:
44. A 25—km long overhead line has a surge impedance of 400 Q. For 100 km
length of such a line, the surge impedance will be:
(a) 100 Q
(b) 400 o
(c) 1600 Q
permitted under U.S. or applicable copyright law.
(d) 25 Q
45. The series compensation:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
46. A synchronous generator is feeding an infinite bus through a line. At the middle
of the line a shunt capacitor is added. The stability limit will:
(a) increase.
(b) decrease.
(c) remain the same.
((1) none of the above.
47. A synchronous generator is feeding an infinite bus. At the infinite bus a shunt
capacitor is added. The stability limit will:
(a) increase.
(b) decrease.
(0) remain the same.
((1) none of the above.
(a) increase.
(b) decrease.
(c) remain the same.
(d) none of the above.
(a) 20%
(b) 50%
(c) 80%
(d) 10%
Chapter 6
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
In a coaxial cable:
(a) the maximum electric stress is at the surface of the inner conductor.
(b) the maximum electric stress is at the surface of the outer conductor.
(C) the average electric stress depends on voltage and insulation thickness.
(d) a and c.
The maximum dielectric stress in a single core coaxial cable is decreased when
W62
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) increase.
(b) decrease.
(c) not change.
((1) conductor should be made less smooth.
(a) increase its charging current and reduce its dielectric losses.
(b) reduce its charging current and increase its dielectric losses.
(0) reduce both its charging current and its dielectric losses.
(d) increase both its charging current and its dielectric losses.
10. A single core cable has a conductor radius of X cm. The insulation thickness is
also X cm. The insulation resistance for 1 km length of the cable is R. If the
insulation thickness is doubled, the new insulation resistance is:
1 l. The insulation resistance for 1 km length of single core cable is R. If the cable
length is reduced to 500 m, the new insulation resistance will be:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
14. The insulation resistance of a 2—km long cable is 150 M9. For a length of 20
km of the same cable the insulation resistance will be:
(a) 1500 M9
(b) 150 MS)
(C) 15 M9
(d) none of these.
15. The value of leakage current in the cable insulation depends on:
16. The maximum dielectric stress in a single core cable is increased by:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
22. As the outside diameter of cable increases, the dielectric stress at conductor
surface will:
(a) increase.
(b) decrease.
(c) not change.
24. The insulation resistance of the single core cable is increased as:
(a) the thickness of the insulation material is reduced with fixed conductor
diameter.
(b) the conductor diameter is increased with fixed cable diameter.
(c) the length of the cable is increased.
permitted under U.S. or applicable copyright law.
25. Consider a 3—phase, 43—kV, 3—core cable. For each core the conductor diameter
is 2 cm and the outer diameter is 5 cm. The maximum electric stress of the core
is:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
26. The capacitance per unit length for the above cable when 8r : 3:
(a) XLPE.
(b) oil impregnated paper.
(0) porcelain.
(d) a and b.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
34. When delivering the same power cost ratio of a 220—kV underground cable to
that of 220 kV overhead transmission is:
(a) cos 5
(b) sin 8
(c) tan 8
(d) 1 — cos 8
36. To obtain the minimum value of stress in cable the R/r ratio should be:
37. In a cable the sheath radius is R and conductor radius is r. As r changes from
0.5 R to 0.25 R, the maximum voltage gradient in the dielectric:
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) 300 Q
(b) 50 Q
(c) 5 Q
(d) 2Q
Chapter 7
(a) glass.
(b) polymers.
(0) porcelain.
(d) all of the above.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) increase.
(b) decrease.
(0) remain the same.
(d) be 100%.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
13. Pin insulators can be used for overhead lines having voltages up to:
(a) 33 kV
(b) 220 kV
(c) 380 kV
(d) 675 kV
14. If the cross arm of the tower are made longer, the insulator string efficiency:
(a) increases.
(b) decreases.
(0) remains the same.
(d) is 100%.
15. The wet flashover voltage at power frequency as compared to the dry flashover
voltage:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
18. A string of insulators for a 380-kV line is composed or 15 units. The voltage on
the unit near to the cross arm is 1.23 kV while the voltage on the unit near to
conductor is 59.48 kV. The per unit efficiency of the string is:
(a) 0.246
(b) 0.426
(c) 1 1.9
(d) none of these.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
23. The insulator string efficiency is less than one due to the existence of:
(a) >1 (b) = 1 (0) <1 ((1) can have any value.
25. The flashover test is done for insulator to make sure that its value is:
27. The data obtained from testing an insulator are: impulse flashover voltage = 50
kV, power frequency flashover voltage = 40 kV, puncture voltage = 70 kV.
The impulse ratio for this insulator is:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
30. As compared to power frequency dry flashover voltage, the power frequency
wet flashover voltage of an insulator is:
(a) higher.
(b) lower.
(c) the same.
((1) only 5 kV.
(a) epoxy.
(b) silicon rubber.
(c) XLPE.
(d) a and b.
(a) flashover.
(b) puncture.
(0) crack in it.
((1) b and c.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Chapter 8
(a) voltage.
(b) current.
(0) power.
(d) a and b only.
3. The flux linking with primary and secondary windings of an ideal transformer:
(a) is same.
(b) is different.
(c) has no relation.
((1) is zero.
5. A single phase ideal transformer is loaded such that it takes 5 kVA at 1 kV. It
has a turns ratio N1 /N2 = 10. Its output current is:
(a) 5 A.
(b) 50 A.
(c) 0.5 A.
(d) 10 A.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) 1 kV.
(b) 0.1 kV.
(c) 10 kV.
((1) none of these.
(a) 10 k9.
(b) 20 kg).
(0) 200 Q.
((1) none of these.
For the transformer of question 5, the input impedance of transformer after the
load is connected is:
(a) 20 k9.
(b) 2 Q.
(c) 5 k9.
(d) 1 k9.
A practical transformer has:
10. A single phase transformer is rated 100 V/400 V. Its total winding resistance
and leakage reactance measured on the low voltage winding are IQ and 49,
respectively. The winding resistance referred to the high voltage winding will
be:
permitted under U.S. or applicable copyright law.
(a) 4 Q.
(b) 2.5 (2.
(c) 1 Q.
(d) 16 Q.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
11. For the transformer of question 10, the leakage reactance referred to the high
voltage winding will be:
(a) 4 Q.
(b) 2.5 o.
(c) 64 Q.
(d) 16 Q.
12. As compared to 3—single phase transformers, a three—phase transformer will
require:
13. Three identical single phase transformers having N1/N2 = 10 are used to form a
single, three-phase bank. The primary windings of this bank are connected in
Y whereas the secondary windings are connected in A. The ideal transformer
used in the equivalent current of this system will have a turns ratio of:
(a) 10:1.
(b) 1:10.
(c) fixioa.
(d) 10:\/§.
14. Assume the transformer of question 13 is connected as a A—Y unit. Then the
ideal transformer used in the equivalent circuit will have a turns ratio of:
(a) 10:1.
(b) 1:10.
(c) 6x104.
permitted under U.S. or applicable copyright law.
15. There is a 300 phase shift between the primary and secondary voltages of a:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) n-model.
(b) ¢-model.
(c) Z—model.
(d) Y-model.
21. A three-phase, Y-connected load takes 20 MVA, at 13.8 kV (line) and power
factor of 0.8 lagging. The per phase load current is:
(a) 836.7 A.
(b) 1045.9 A.
(c) 1449.3 A.
(d) 1811.6 A.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
22. For the load of question 21, the line to neutral load voltage is:
23. For the load of question 21, the reactive power is:
(a) 10 MVAR.
(b) 20 MVAR.
(c) 12 MVAR.
(d) 6.93 MVAR.
24. For the load of question 21, the per phase load impedance has a value of:
Chapter 9
1. In per-unit conversion, if the MVA base is doubled while keeping the same kV
base, the new per—unit impedance is:
(a) halved.
(b) doubled.
(c) multiplied by 4.
((1) divided by 4.
permitted under U.S. or applicable copyright law.
In per-unit conversion, if the kV base is doubled, while keeping the kVA base
the same, the new per-unit impedance is:
(a) doubled.
(b) halved.
(c) multiplied by 4.
((1) divided by 4.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
5. Assume the reactance of a 50—MVA, 13.8—kV generator is 10%, then the actual
reactance is:
7. The per unit impedance of a line, to a 50-MVA, 132-kV base is 0.4. The per
unit impedance to a 100 MVA, 132 kV base will be:
(a) 0.2.
(b) 0.4.
permitted under U.S. or applicable copyright law.
(c) 0.8.
(d) 1.0.
(a) 0.9.
(b) 2.7.
(c) 0.3.
(d) 8.1.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) 54.45 Q.
(b) 108.9 Q.
(c) 12.12 (2.
(d) 24.24 (2.
10. A three—phase transformer bank is made using three similar single phase units
each rated at 10 MVA, 10 kV / 220 kV. The 3—phase transformer is connected
in A-Y. If base voltage on the low voltage side is selected as 11 kV, the base
voltage on high voltage side will be:
(a) 1.92 Q.
(b) 5.76 o.
(c) 0.192 9.
(d) 0.576 Q.
permitted under U.S. or applicable copyright law.
13. A transformer is rated as 35 MVA, 220 Y / 13.8 kVA, X = 10%. Its reactance
is:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
15. The p.u. impedance of a transformer is supplied by the manufacturer based on:
16. The p.u. impedances of the same type of equipment of differing MVA ratings is:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Chapter 10
(a) 2%.
(b) 5%.
permitted under U.S. or applicable copyright law.
(c) 10%.
(d) 15%.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
13. Compared to a radial type distribution system, a loop type distribution system
has:
15. The ring distribution system, when compared to radial system, has:
16. A single phase underground cable has rated voltage Vr, a total conductor
resistance of R, and a total series reactance of X. The cable supplies a load
current of I at a power factor of cos d) leading. Its voltage drop can be
approximated by:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) 0.06 l
(b) 0.21 I
(c) 0.14 l
((1) none of these.
(a) generators.
(b) transformers.
(c) motors.
(d) all of these.
23. The factors affecting the voltage drop in short line are:
Chapter 11
(a) is sandy.
(b) is wet.
(c) is dry.
(d) a and c.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) R<RN<R/N
(b) RN:R/N
(C) R>RN>R/N
(d) RN=NR
The effect of the diameter of rod electrode on its grounding resistance is:
(a) minor.
(b) significant.
(C) the most important.
((1) no effect.
10. The advantage of using copper instead of iron in grounding electrodes is to:
11. The foot to foot equivalent resistance for a body having a resistance of Rb and a
ground having a resistivity of pS is:
(a) 3pS
(b) Rb‘l’ljps
(C) Rb+3ps
(d) Rb+6ps
12. When measuring the grounding resistance using fall-of—potential method the
condition for obtaining correct reading for the grounding resistance is:
permitted under U.S. or applicable copyright law.
(a) the current rod must be outside the effective resistance area of the tested
electrode.
(b) the potential probe must be outside the effective resistance area of the
tested electrode.
(c) a and b.
((1) none of these.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) s : Vtw
14. The minimum body current leading to possible ventricular fibrillation is:
(a) 15 mA
(b) 30 mA
(c) 0.116x/TA
(d) 0.116/x/TA
15. When increasing the length of rod electrode, its grounding resistance will:
(a) increase.
(b) decrease.
(c) no change.
((1) be 10 Q.
17. The equivalent resistance for a body during touch voltage (body resistance = Rb
& resistivity of soil = ps ) is:
(a) 3 ps
permitted under U.S. or applicable copyright law.
(b) Rb +1-5 pg
(C) Rb + 3 133
(d) Rb + 6 ps
18. The grounding resistance of a plate electrode can be decreased by:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
(a) 1kg
(b) 10 m
(c) 100 kg
((1) 1000 kg
20. Ground resistivity can be measured using:
(a) P3
(b) 2P5
(0) 133/2
(01) 271135
23. Tolerable touch voltage depends on:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
25. The total ground resistance (RP) of two identical parallel rods each having a
resistance RS is:
m) Rp=RJ2
w) RP<RJ2
@) RP>R42
m) Rp=Ry
26. In the fall of potential method, we need:
(a) 3 rods.
(b) 2 rods.
(0) 4 rods.
((1) 1 rod.
@) >309.
m) <1oo.
@) <59.
m)=:moo.
28. The ground wires used to protect the transmission lines from lightning are
placed:
Chapter 12
2. Rod gaps are used for overvoltage protection since they are:
(a) cheap.
(b) simple and reliable.
(c) a and b.
((1) none of the above.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
The main disadvantage of a rod gap when used for overvoltage protection is:
Switching surges are important for power system when the system's nominal
voltage is:
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
10. For medium and high voltage lines, the most important surge overvoltages are
caused by:
(a) lightning.
(b) switching.
(c) a and b.
((1) none of these.
(a) 5 us.
(b) 50 us.
(0) 1.2 us.
((1) 250 us.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
15. To avoid damaging the high voltage equipment by surge voltages, the following
actions are needed:
18. The following electrodes are used for surge overvoltage protection:
((1) a and b.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
23. The standard rated secondary current of a current transformer (CT) is:
(a) l A.
(b) 2 A.
(c) 3 A.
(d) 5 A.
24. The standard rated secondary voltage of a voltage transformer (VT) is:
(a) 110 v.
(b) 220 v.
(c) 115 v.
(d) 127 v.
25. A differential relay cannot be used as a backup relay because:
26. If the current tap (Ip) setting of an over current relay is increased, its operating
time will:
(a) increase.
(b) decrease.
(c) remain the same.
(d) be variable.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
27. If the time dial setting (TDS) of an over current relay is increased, its operating
time will:
(a) increase.
(b) decrease.
(C) remain the same.
(d) be variable.
29. A circuit breaker having rated maximum voltage 36 kV, can be used in a
system with having rated voltage of:
30. A circuit breaker having rated short-circuit current of 22 kA, at rated maximum
voltage of 34.5 kV, voltage range factor K: 1.65. The maximum short circuit
current for this breaker is:
(a) 23 kA.
(b) 25 kA.
(C) 30 kA.
(d) 36 kA.
permitted under U.S. or applicable copyright law.
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
INDEX
Bluejay 67
Breaker 6, 13-15, 18, 32
AAAC 53 double 234, 236
AAC 84,98,101-103 bundle 52, 64-66, 72-75, 82, 83, 374,
ABCD constants 85, 86, 94 376
ac circuits 347—359 bus 13-15, 171
single—phase circuits 347—351 double 234—236
three—phase circuits 351—357 main 235
ac generators 4, 11-13, 36-45, 171-172 ring 234, 236
active power control 43-45 scheme 234-236
cylindrical rotor type 36-37 single 234, 235
field or excitation control 37—43 transfer 234, 235
frequency control 37
induced emf 37 C
interconnections 41—43
principle of operation 36—38 cables (see power cables)
reactive power control 44—45 Cardinal 67
salient pole type 37 calculation examples in simple system
terminal voltage of 39 187-192, 212-218
ACSR 53,60, 64, 65, 67,74, 75, 100, capacitance 54, 68—75, 79, 99, 100, 117
374, 375, 377 challenges of interconnection 20, 21
Admittance 52, 68, 71, 79, 84, 90, 100, characteristic impedance 92, 101
101-103, 349 charge 68, 69, 74
advantages of interconnection 19, 20 charging current 118
AGC 7 Chickadee 67
Alloy 53 compensation
Aluminum 23, 53, 57, 64, 75, 109, 374 series 97, 98, 380-383, 387, 388
Ampere’s law 55, 56, 58 shunt 97, 99, 380, 384, 385
attenuation constant 92, 102 choice of transmission voltage 21, 22
circuit breaker 6, 13—15, 18, 32, 236,
B 239, 307, 312, 314—319, 321, 334,
permitted under U.S. or applicable copyright law.
423
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708
Copyright © 2012. Academic Publishing and Press, King Saud University. All rights reserved. May not be reproduced in any form without permission from the publisher, except fair uses
Index 425
Harmonics 309
EBSCO Publishing : eBook Arabic Collection (EBSCOhost) - printed on 10/30/2019 2:42 AM via THE RESEARCH COUNCIL
AN: 1820919 ; Abdulrahman Ali Al-Arainy, Nazar Hussain Malik, Saad Mubarak Al-Ghuwainem.; Fundamentals of electrical power engineering
Account: ns240708