rerwane Pumps and Fans | Energy-Models.com
Become an Instructor Blog About
Pumps and Fans
Back to
In order to move a mass (solids, liquids or gases) you have to apply an external Course
force (energy). Fluids (gases and liquids) can be made to move from say point-A
to point-B by creating a difference in pressure between point-A and point-B,
The difference in pressure between the two points in the "System" is required to
‘overcome the resistance in the system from (1) friction from ductwork and Course
piping, (2) fittings such as elbows, valves/pipes, dampers/ducts, etc., and (3) Lessons
equipment such as heating and cooling coils.
Mechanical devices such as fans are used to move gases and pumps are used to Piping and
move liquids. The mechanical devices are driven by electric motors. (Pumps are Ductwork
sometimes driven by diesel or gas engines as in the case of automobiles). Systems
Fans and pumps are selected so that they will increase the pressure of the fluid Pumps and
flowing through it. The increase in pressure must be sufficient to drive the fluid Fans
through the terminal unit or outlet with the greatest pressure difference (or loss
in the system up to the terminal or outlet). The quantity of fluid that the fan or
pump must move per unit time (CFM or GPM) is the sum (or the simultaneous
Refrigeration
Time Value
peak sum) of the fluid required at all the terminals. of Money
Work Lighting
(NASA)
Work measurement was established arbitrarily and by tradition in the same way
as length, weight, time, heat, temperature and pressure. In IP units a unit of Duct Sizing
work is done when 1Ib mass is lifted vertically against gravity through a distance Charts &
of 1 foot. The unit is called foot-pound (ft-lb). Similarly, when 1 kilogram mass is Tables
lifted vertically against gravity through a distance of 1 meter then the work done
is 1kilogram-meter. Work done is Force x Distance. Pipe Sizing
Charts
‘lb weight resting on a surface area of 1 square foot exerts a pressure or force of Tables
‘lb per square foot. Force is pressure per unit area. In the Figure below force,
behind a piston, is applied to a gas in a cylinder, moving the cylinder a certain BOILERS
distance and compressing the gas. So work has been done. The Figure shows Centifugel
that the work done is the area under the curve from pressure-volume condition 1 Chilter-
to pressure-volume condition 2. The process is not usually a straight line. Fundamentals
HEATING
hipsleneraymodels.compumes-anc-fans 10vera Pumps and Fans | Energy: Models.com
AND
Work Done on Gases Work dos
resin PA Aven ani OOLING
Piston — PV curseSYSTEM
eal an
= cas
0%
chtiters
Volume=VI=A*LI
Pressure ~ P—F/A_or Fosce on Piston ~ F - Chiller Plant
‘Work Done = Force * Distance = P* A (L112) =P * (A*L1-A*L2)=P #(VI-V2) Design
. Pv
Figure - Modeling in
eQUEST
Energy Introduction
Energy is defined as the capacity to do work. So energy can exist in many forms to
such as nuclear, chemical, electrical, fossil fuel, solar, wind and geothermal. The Photovoltaic
basic forms of energy are potential, kinetic, mechanical, heat, internal, and systems
electrical.
How Solar
Potential energy is due to position or state. For example a mass raised to some Electric
height above a reference level such as the earth's surface can be made to do Technology
work by letting it fall. A compressed spring possesses potential energy because Works
it can do work when it is released.
Basic
Mechanical energy is possessed by any mass which is in motion. It is also Photovoltaic
referred to as kinetic energy. Kinetic energy is the energy possessed by a body Principles
in motion. Electrical energy is obtained from electrical generators and batteries and
and consists of the flow of electrons in an electrical circuit. Methods
Heat energy is the result of the kinetic energy possessed by the atoms and Photovoltale
(PV) Tutorial
molecules which make up the mass. Internal energy of a gas is a function of
‘temperature only and is independent of changes in pressure and volume and
the symbol used is U. This is known as Joule’s Law.
‘When one mass loses X btu of heat then the heat content of other masses must
increase by the same X btu, There is no such thing as heat or any form of
energy just disappearing into nothing, Energy is transferred from one object to
another or just stays where itis.
Energy can be converted from one form to another. The heat energy from fossil
fuel can be converted into mechanical energy to drive turbines. The mechanical
energy of turbines can be converted to electrical energy using generators.
Electrical energy can be converted to mechanical energy using motors or
converted to heat energy asin the case of resistance heaters.
Power
hipsleneraymodels.compumes-anc-fans 20arveon Pumps and Fans | Energy Models.com
The same amount of work can be done over different time periods. Moving
1000 Ibs through a distance of 1000 feet in 100 hours is not the same as moving
the same 1000 Ibs through the same distance of 1000 feet in 1 hour. Power is
defined as work done per unit time or the rate at which work is done.
A unit of work commonly used in |-P units is the Horse-Power (HP) which is
defined as 33,000 foot-pounds per minute or 550 foot-pounds per second. This
is used in mechanical engineering calculations, The electric HP is equivalent to
33,013.282 ft-bs and boiler HP is 33,472.12 ft-lbs. The metric HP is 32,548.5623
‘ft-lbs per minute or 542.476 ft-lbs per second,
However the unit of power commonly used in S-I units is the watt which Is
derived from electrical units, Electrical force (E volts) = Current (I amperes) x
Resistance (R ohms) and Power (P watts) = E x |. The watt is a small unit so the
term corresponding to HP is Kilowatts (KW) where 1 KW = 1000 watts. 1 KW =
4,253.7 ft-lbs = 1.340483 HP and 1HP = 0.746 KW,
Pump and Fan Laws of Operation
PUMPS
(1) GPM-2
GPM-1
Q) H-2
Hel =
(3) BHP-2
BHP-1
(1) GPM = Gallons per Minute. CFM = Cubic Feet per Minute. RPM = Revolutions
per Minute The flow (gpm or cfm) increases with the RPM of the pump or fan.
(2) H= Pump Pressure Head (feet H20). P= FTP = Fan Total Pressure (inches
H,0) The pressure delivered by the pump increases as the square of the RPM
ratio
(3) BHP = Brake Horse Power. This is the mechanical energy required. It
depends on the flow (gpm or cfm) and pressure (feet or inches H20) resistance
across which the fluid is moved.
Brake Horse Power (BHP) = ( GPM x 8.35 x SPGR x H) / (33,000 x
PUMPS:
(PENO0))
Brake Horse Power (BHP) = ( CFM x FTP x 5.2) / (33,000 x (FE/100) )
FANS: _ SPGR = Specific gravity of liquid. PE = Pump Efficiency. FE = Fan
Efficiency.
MOTORS: Motor Horse Power (MHP) = BHP / ME, ME = Motor Efficiency
hipsleneraymodels.compumes-anc-fans anoroeveoe Pumps and Fans | Energy: Models.com
PUMP OPERATION
Pump
Pressure
Head
At this pressure (flow resistance) there is uo flow
H feet
The pump is off
Pump Carve
H2
GPM-2 GrM-1
Pump Flow Capacity GPM
‘When the piping system pressure is H-1 the flow through the given pump is GPM-1
‘When the piping system pressure is H-2 the flow through the given pump is GPM-2
The flow can be reduced from GPM-1 to GPM-2 by increasing the pressure by.
for example, throttling down a valve
The flow can be reduced from GPM-1 to GPM-2 by reducing the pump speed (RPM)
using variable speed / frequency motor drives,
Pumps in Parallel
Ose Pymp ON
Tre?
ps On
200 GPM
200 G>M. Supply
He Return
100 &
Too PM Too GPM
Pump: in Series
He Twe Pump: On
200 # 100 GPM.
Reture
ae
100 &
Oxe Pump ON
To) GPM
(sites/alttes/advancee-pages-31023/pumps-and-fans-4,png)
hipsleneraymodels.compumes-anc-fans anoverve ‘Pumps and Fans | Energy-Models.com
Example of Primars-Secondary Piping Network System
Terminal Units 100 gpm exch)
(pttpsvenergy-models.convsites/alfiles/advanced-pages-31023/pumos-and-fans-5.png)
Typical System
hipsleneraymodels.compumes-anc-fansroeveoe ‘Pumps and Fans | Energy-Models.com
spp
i BOILER PLANT
Popol
yamary
Hot Water
Pumos
HWS
|AHU Heating Coils
awe FT Re ER
AHU Cooling cot
Condenser
Water Loop
(CHILLER PLANT
Typical System
hipsleneraymodels.compumes-anc-fans enoroeveoe Pumps and Fans | Energy: Models.com
Ontiooe HY, Sipm CHR W,Stam Sta
hi Pq or Has Vo cree | SAF Satie
1
OA + Press Gin)=4.0
A eupha=20F
a
esr A
b ps. Pay Ar
Retief As 7
u Bie ———_-
ter Zanes Paw Oba Zou
PA Pinay A
8 ‘SLE (80%)
caw] cael War Zea [acd (Seconda) —
EW | Fortier sir(Celing 7820") Es
PHC | Prteat Cal 1B: VAV Box Banta
cc Cooling Cail ‘wath Heatg Coil
EC | Heaing Cal
Fun | Fimsaer
u
Sem fesar | toe [eee
razemar | 1 | sr | nae] ow
om Zana rT) FA fom
wasters coer Zones
I BUILDING
I
Usites/altfes/advancee-pages-31023/pumps-and-fans-8,png)
hipsleneraymodels.compumes-anc-fansvera Pumps and Fans | Energy: Models.com
PUMP PERFORMANCE Examples Calculated by Program:
DESCRIPTION ‘Pump-2] Pump-3
Tdentification Data
Pump Identification Name Pow | PHW
Service cw HW
Description ‘Cond Wat | Hot Wat
Location {DbI Suction|DbI Suction|End Suction
Fluid Type Glycol. Fuel Oil. et Water | Water
Fluid Specific Gravity i
Piping System Typ Closed
“A Pressure Loss ( Pipe & Fittin;
Pipe Frictional
Pipe Fittings (bends, valves, ete
Pipe Equipment (meters. etc.)
Static Lift
Miscellaneous
(2) Sub-Total
(2) Pressure Loss (Equipment)
Chiller / Evaporator
Condenser / Condensing Unit
Cooling Tower
Cooling Coil
Boiler
Heat Exchanger
Heating Coil
Terminal Unit (radiators. ete.)
Tanks
Miscellaneous
Pump Total Head = (1) +2)
‘Pumping Station
‘Total Flow (GPM)
Number of Pumps in Parallel
Flow G P Meach Pump =pivior_ | 2DIvior
‘Number of Pumps in Series
Pressure Head of each P =pivio | 2pivo1
Horse Power (Each Pump)
Pump Efficiency (%)
Pump Brake Horse Power (BHM Divo! | #DIvior
Motor Efficiency (%) 90
Motor Horse Power (Calculated| i =bivior_ | @DIv/or
Standard Motor Horse Power
[300300 soo
(sites/altiles/advanced-pages-31023/pumps-and-fans-9.png)
Brake HorsePower (BHP) =( GPM x 835 x SPGR x H)/( 33,000 (PE/ 100)
Motor HorsePower (MHP) = BHP/(ME/ 100) GPM (ooling) = (Tons x 12000) / (500 x WTD)|
SPGR = Specific Gravity of fluid GPM (heating) = (MBH x 1000) / (500 x WID)
GPM = Gallons Per Minute H= Pump Pressure Hea WTD = Water Temp Difference
PE = Pump Efficiency (6) = 85% _ME = Motor Efficiency (%) = 90%
hipsleneraymodels.compumes-anc-fansroeveoe ‘Pumps and Fans | Energy-Models.com
(sites/altifies/advanced-pages-31023/pumps-and-fans-tlpng)
FAN PERFORMANCE (Estimating Form) Calculated by Program
Identification Data
Fan Identification Name, Sa RI Ed 32
‘Description High Pr. |" Remum | Toilet Exh |" Low Pr
Location MechRm | MechRm | MechRm | Floor
Service Firs 10-30 | Firs 10-30 | Firs-10-30 | Restaurant
(2) Pressure Losses ( Ductwork )}
Frictional Losses 09 05 05 o4
Fittings Losses 15 05 06 05
‘Special Losses 05 03 OL
Fan Inlet & Outlet 03 02 02 Oo
‘Miscellaneous Losses| 02 02 Or
1) Total] 34 17 13 12 00
(2) Pressure Losses (Equipment)
INLET : Diffuser / Register 02 02
‘OUTLET : Diffuser / Register 02 02
Terminal Box 03 03
Sound Attenuator (Fan Inlet) 03
‘Sound Attenuator (Fan Outlet) 03
Filters (Pre-Filter + Main-Filter) 11 10
‘Cooling Coil 1 1.0
Heating Coil 04 O4
Reheat Coil 03 03
‘Dampers 03 03 03
‘Louvers 02 02
‘Miscellaneous equipment Losses [0.1 1
2) Total] a6 38 oxy
Static Press (FSP) = (1) + @) 8.0 2.3 1s 5.0 0.0
‘Outlet Velocity (FPM) 2.500 1,200 1,000 1,500
‘Vel. Press. (VP) = (FPM/4004)2_ [0.39 0.09 0.06 014 0.00
‘Total Press. (FTP)=FSP+VP | 3.39 2.39 1.56 S14 0.00
“Multiple Fan Stations
‘Number of Fans in Parallel 2 1 1 1
Flow C F Mof each Fan 35,000 [90,000 | 20,000 | 20,000
‘Number of Fans in Series 1 1 1 1
Total Pressure of each Fan 839 239 156 3.14__| aDIvior
Horse Power (Each Fan)
Fan Efficiency (%) 30 75 oS 85
Fan Brake Horse Power (BHP) 90.9 45.2 76 19.1 | #DIvior
‘Motor Efficiency (%) 90 90.00 90.00 90.00
‘Motor Horse Power (Calculated) [101.0 50.2 84 212 | #DIvior
Standard Motor Horse Power_| 125.0 60.0 10.0 25.0
Total Motor Horse Power 250, 60. 10 25 a
(/sites/alvfiles/advancee-pages-31023/pumps-and-fans-t2.png)
‘Brake HorseDawer (BHP) =( CFMxFIPx52)7(33000x (FE FIP=Fan Total Preseure
‘Motor HorsePower (MHP) = BHP / (ME / 100)
CEM = SHG /[ 1.08 (Tr -Ts) ] Tr=Room Temp ME = Motor Efficiency (%)
SHG = Room Sensible Heat Gain__Ts = Supply Temp
hipsleneraymodels.compumes-anc-fans anoroeveoe ‘Pumps and Fans | Energy-Models.com
(sites/allifies/advanced-pages-31023/pumps-and-fans-14.png)
(sites/altifles/advanced-pages-31023/pumps-and-fans-15.png)
Course 2 Lesson (/advanced-training/course-2-systems-and-plants/course-2-lesson)
About the Author
(/content/varkie-thomas)
Varkie C. Thomas, Ph.D., P.E. Research Professor
College of Architecture Illinois Institute of
= Technology Chicago, Illinois, USA
Varkie Thomas taught graduate courses in Energy Efficient Building Design,
Building Energy Performance Analysis and advised doctoral candidates (1996-
2008) as an Adjunct Professor at Illinois Institute of Technology (IIT) from SOM.
He is currently a Research Professor with the Ph.D. program at IIT, He was a
member of the UN Technical Program to China in 1991 and a Visiting Professor
from Purdue in Malaysia in 1996/97 funded by the World Bank.
Academic: B.Sc. (Honors) in Mathematics from St. Xavier's College Bombay
University; Post-Graduate Diploma in Environmental Engineering from London
South Bank University; Post-Graduate Diploma (with Distinction) and Ph.D. in
Industrial Management from Strathclyde University Glasgow. Registered
Professional Engineer (P.E.) and Certified Energy Manager (CEM - Association
of Energy Engineers),
Instructors (/category/aboutussinstructors)
hipsleneraymodels.compumes-anc-fans sono