Method Statement HydroTest of Sprinkler Network

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 10

as 

per NFPA 13, SBC 801 & Civil Defense Guidance 

MSC Client & Consultant Office (187 Desk) 
Red Sea Project 

Wet Pipe Sprinkler System 

Prepared & Compiled by: 

Thimar Electronics Co. Ltd
DISCLAIMER 

This technical document is prepared, composed, catalogued and produced by the Engineering Department 

of Thimar Electronics Co. Ltd.  The instructions, directory, and information presented herewith are valid and 

accurate  as  of  the  time  of  writing.  Any  changes/update  occurred  or  made  by  the  standards,  listing  and 

approval body (NFPA, UL, FM e.g.), and manufacturer, thereafter is beyond the control of Thimar Electronics 

and so will not be held responsible for any incident, damage, additional work or material supply resulting to 

such.        

For any clarification, assistance or inquiries regarding this document refer to below contact details: 

Thimar Electronics Co. Ltd. 
Ash Shaikh Abdullah Al Anqari,  
Salah Ad Din POBox 41651  
Riyadh 11531 K.S.A 

Head Office: 

Telephone nos.   :   011 477 7690  


Fax nos.  :   011 476 8345 
Email    :  sales@thimar.net 

Contact Person: 

Khaled Sultan 
Sales Manager 
+966 540286061

1 | P a g e
DESCRIPTION OF INSTALLATION 

Reference Standards

The firefighting system of the project is designed, supplied, installed, tested and commissioned in strict 
observance and compliance to the following standards: 

NFPA 10 Standard for Portable Extinguishers 
NFPA 13 Standard for the Installation of Sprinkler Systems 
NFPA 14 Standard for the Installation of Standpipe and Hose Systems 
NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection 
NFPA 24 Standard for the Installation of Private Fire Service Mains and Their Appurtenances 
NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water‐Based Fire Protection Systems  
Saudi Building Code 801‐ Fire Protection 

Water Supply and Pumps 
The scope of works is provided by others 

Below‐ground piping, Main Valves and Private Mains 
The scope of works is provided by others... 
Locally, the system is provided with Alarm Check Valve Assembly with Fire Department Connection (inline).  

Aboveground piping and Pipe end connections 
All above‐ground piping network are Galvanized Steel Pipe Sch. 40 ERW, ASTM A53, Gr. B. 
Pipe connections are threaded for sizes below 2”, grooved‐end fittings for 2‐1/2” and larger, flanged and 
welded connection as per field and equipment required.   

Building Fire Sprinkler 
All sprinkler head below false ceiling shall be recessed pendent 5.6K sprinkler, Quick Response, Standard 
Coverage, 68ºC Temperature, Chrome plated finish with escutcheon.  

Fire Hose Cabinet 
Fire Hose shall be Class II with 30m Ø1” rubber hose in a reel, house in a surface mounted mild steel red 
painted dual‐door cabinet. 

Portable Fire Extinguisher 
6kg ABC Dry Powder extinguishers are provided on most area. And CO2 4.5kg are also provided on special 
hazard rooms, 

System 
The  system  shall  be  Wet  Pipe  Sprinkler  System  on  a  standard  tree  piping  layout  hydraulically 
designed to meet protection for Light Hazard occupancy as per NFPA and relevant standards 

2 | P a g e
Hydrostatic Test 
Wet Pipe Sprinkler System 
 
 
METHOD STATEMENT 

Hydrostatic Tests 

1. Prior to any performance of hydrostatic test. The installer must acquire the approval of request for inspection 

(RFI) for the installation of piping and support works for the network. 

2. The request for inspection (RFI) for performance of hydrostatic test must be accompanied with an accurate as‐

built drawing showing the piping network and support as field installed.  

3. All piping and attached appurtenances shall be hydrostatically tested at 200 PSI (14 bar) and shall maintain that 

pressure without loss for 2 hours. (NFPA 13‐2019 28.2.1.1) 

4. Loss in pressure shall be determined by a drop in the gauge pressure or visual leakage. (NFPA 13‐2019 28.2.1.2) 

5. Portions of system normally subjected to system working pressures in excess of 150 psi (10 bar) shall be tested 

as described in 28.2.1.2 at a pressure of 50 psi (3.4 bar) in excess of system working pressure. (NFPA 13‐2019 

28.2.1.3) 

6. When systems are being hydrostatically tested, tests shall be permitted to be conducted with pendent or 

horizontal sidewall sprinklers or plugs installed in fittings. Any plugs shall be replaced with pendent or horizontal 

sidewall sprinklers after the test is completed. (NFPA 13‐2019 28.2.1.8) 

 
7. During the pressurization of the system and hydrostatic test pressurization. The installer shall be allowed to 
install a temporary means of air vent using valve to purge the system of excessive air. 
 
 
8. An additional air pressure leakage test or any other form of test or method shall not be required to be performed 
further unless provided for by the NFPA 13, SBC 801 (Saudi Fire Code), Civil Defense guidance, and/or agreed by 
Thimar through a variation order. 
 
3 | P a g e  
 
Piping and Support Installation
Wet Pipe Sprinkler System 
METHOD STATEMENT
PIPING & SUPPORT INSTALLATION
HSE GUIDELINES

TOOLS & EQUIPMENT

Pipe Grooving Machine


Pipe Threading Machine
Vice Table
Drill Machine
Grinding Machine
Measuring Tape
Level Bar
Pipe Wrenches
Wrench set (socket, open, close)
Screw Drivers
Pliers
Hammers
Plumb bob
Steel Brush
File
Tool box
Others tools as required

MATERIAL PREPARATION

All material while unloading shall be lowered to the ground either manually or with crane. Pipes

shall be stacked on a flat surface with timber supports beneath at equal distance. Stacking

of pipe shall ensure that pipes of bigger sizes are placed below and smaller sizes on top.

All other items such as valves, gauges, switches, etc.… shall be kept on rack on a site store and

shall be segregated as per size, model, type etc. for easy retrieval. Any items found damaged

or not suitable shall be removed from site.

4|Page
METHOD STATEMENT
PIPING & SUPPORT INSTALLATION
HSE GUIDELINES

SHOP DRAWING

1. An approved scale drawing must be posted at the wall on field for easy reference of

the installers. This must be replaced accordingly should there is an official revision.

2. Field adjustment, confirmation and coordination shall be performed by the supervisor

at all times to avoid unnecessary clashing on other trades and facilitate smooth

progress of work.

3. A3 red-line drawing must be updated and accomplished daily to prepare for the as-

builts drawing upon completion of the installation.

PRE-INSTALLATION

1. Permanent location of the equipment and power sources shall be located and

coordinated by the supervisor on Day 1.

2. The supervisor shall ensure that Safety induction (if required), PPE & HSE policies

information are conveyed to the worker on Day 1.

SUPPORT INSTALLATION

1. Fix supports and hangers with approved material, as per approved layout drawings

and schedule.

2. Cut all excess hanger rods and leave enough length below the support for final

adjustment of levels

5|Page
METHOD STATEMENT
PIPING & SUPPORT INSTALLATION
HSE GUIDELINES

FABRICATION & INSTALLATION OF THREADED PIPE (Ø2” AND SMALLER)

1. The pipe surfaces shall be thoroughly clean with damp cloth and let dry.

2. A mild wire brush shall be use to remove foreign materials remaining on the surface.

3. The installer/operator shall inspect the threading machine and dies before starting

the work and ensure it is in good condition.

4. The pipes shall be square cut with a pipe cutter and threaded on both sides.

5. The thread ends shall be cleaned using steel brush and file.

6. All threading residuals shall be removed to restore full inside diameter.

7. The jointing compound, abaca hemp and/or thread sealant/tape shall be applied

on the portion of the threaded for fitting assembly.

8. The sprinkler branches and drops shall be either assembled at the workshop or at field

as required.

FABRICATION & INSTALLATION OF GROOVED PIPE (Ø2½” AND LARGER)

1. The pipe surfaces shall be thoroughly clean with damp cloth and let dry.

2. A mild wire brush shall be use to remove foreign materials remaining on the surface.

3. The installer/operator shall inspect the grooving machine and roller for wear and tear

before starting the work and ensure it is in good condition.

4. The pipes shall be square cut with a pipe cutter and roll-grooved on both ends.

5. The grooved ends shall be cleaned using steel brush and file.

6. All residuals shall be removed from the grooved joints and plain end must be ensured

before proceeding.

7. The installer shall lubricate the rubber and pipe amply before any fitting installation

8. The sprinkler mains shall be either assembled at the workshop or at field as required.

6|Page
METHOD STATEMENT
PIPING & SUPPORT INSTALLATION
HSE GUIDELINES

HEALTH & SAFETY

1. Before commencement of any work, the installation team shall follow the

manufacturer’s, customer’s, and occupational safety hazard standard practices and

recommendation for preparation, handling and use of the materials/equipment and

ensure all involved personnel shall be aware of the same.

2. The general safety guidelines shall be as follows:

a. All PPEs must be worn at all times.

b. When working at a high level (in excess of 1.5m), the appropriate harness shall

be used and secured while working and extra care and measure shall be taken

while using tools at the same to prevent dropping.

c. Ensure that all work area is safe and clean

d. Ensure sufficient lighting is available during all stages of installation & testing

e. Ensure that all necessary permits (work, hot work, electrical isolation, area

isolation, and area access, … etc.) are obtained and valid before proceeding

to any work.

f. Ensure that all workers are not exposed to extreme high temperature and well

hydrated.

g. All accidents must be reported to the Safety Officer on duty no matter how

trivial or negligible it might be.

h. Basic first-aid kit or emergency medical facility must be accessible & available

at the nearest possible location during work hours.

7|Page

You might also like