Controller
MCU 5.0 series
V2.8
WWW.PEAKS.CN
1. Application
MCU 5.0 three-position switch controller is used for controlling the operation of motor-driven three-
position switch or two-position switch, and preventing the three-position switch from misoperation.
2. control logic
2.2.1 Normal position input signals (List in Table 2.1) detected, stop motor.
2.2.2 When motor starts, no any changeover of normal position signal detected after 5 s, then stop motor.
The blocking current of PZX0/ZX0.2/METRO cabinet 220V is 1.4A, 110V is 2.8A, 48V is 5.6A; The blocking
current of ZX0/2/1.2/1.5-R cabinet 220V is 1.8A, 110V 3.8A, 60V 5.8A, 48V 7.8A.
2.2.3 Time-out time, for PZX0/ZX0.2/METRO cabinet is 10s, for ZX0/2/1.2/1.5-R cabinet is 25s.
2.2.4 Stop motor when blocking.
2.2.5 When the watchdog is triggered, stop the motor.
2.3 If in the close position of the isolated switch, can not execute the command of close the earth
switch.
01
2.4 Alarm
2.4.1 When XOR value of the two input signal of isolation switch is 0, send alarm signal, delay time is
10s,but not alarm in the process of the motor running .
2.4.2 When motor starts, for PZX0/ZX0.2/METRO cabinet, no any normal position signal detected after 10s,
send alarm signal, for ZX0/2/1.2/1.5-R cabinet, no any normal position signal detected after 25s, send alarm
signal.
2.4.3 When motor starts, no any changeover of normal position signal detected after 5 s, send alarm signal.
2.4.4 More than 1 command signals input, send alarm signal.
2.4.5 When the load current detected in the operation of the motor is larger than the blocking current
setting value, send alarm signal.
2.4.6 If motor direction is error, send alarm signal.
2.4.7 When the mechanism is in the middle position, it will alarm after 90s, and self-reset after it is in place.
Reset all output, reset all alarm action. After alarm has been reset, to allow continued operation of the mo-
2.6.1 Only REED closed and ESW closed, to determine the three-position-switch is in the earth-closed
state. (Two-position unrelated)
3. Communication protocol
(please refer to this clause for the product with communication function )
Communication protocol is MODBUS RTU, the baud rate can be set 19200 or 9600, the factory set is 9600.
02
STATUS_H_2 Isolator open
STATUS_H_1 Isolator close
STATUS_H_0 Remote enable
STATUS_L_7 Not defined
STATUS_L_6 Total operation permission
STATUS_L_5 ESW operation permission
STATUS_L_4 Isolator operation permission
STATUS_L_3 ESW open position
STATUS_L_2 ESW close position
STATUS_L_1 Isolator open position
STATUS_L_0 Isolator close position
Communication frame description:
Read status command frame : Address、Function code 03,Status address H 00, Status address L 02(0002),
Register count H 00, Register count L 01, CRC_L, CRC_H
Return information: Address, Function code 03, information byte count 02、Status information H 8bit,
Status information L 8 bit, CRC_L, CRC_H
Wrong information flame: Address, Function code 83, Wrong information byte, CRC_L, CRC_H
4. Terminal definition
Terminal
Definition Description
number
3 Motor+ To motor +
4 Motor- To motor -
7、8 Output for fault NO. Closed and keep when alarm affair happened , off after reset.
Use the circuit breaker open position contact. Forbid operation and
stop motor when the input is disconnected (the interlock is not met)
13 Total interlocking
Switch cover plate open contacts in series into the main interlock loo
p, when the switch cover plate open the main interlock disconnect
03
17 ESW open instruction (Two-position unrelated)
5. Terminal layout
1 2 3 4 5 6 7 8 24 25
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1 2 3 4 5 6 7 8 24 25
A B
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
04
6. Front panel layout
Note:The above indicator lights, in addition to the alarm indicator light is red, the other lights are green.
05
7. Dimension
Unit: mm
8. Technical parameter
9. Model explanation
MCU 5.0 - □ -□ P - □ - □
Design code
Product code
06
Product Disposal considerations:
It should be recycled as recyclable electrical and electronic products, the discard work of this product should be in accordance with
local waste disposal environmental regulations. This will help prevent a negative impact on the environment and human health due
to improper handling of the products.