106.2 - Transformers
106.2 - Transformers
106.2 - Transformers
• LOSSES IN THE
TRANSFORMER
• HIGH EFFICIENCY
VS. STANDARD
• CONFIGURATION
• LOCATION
LOSSES IN THE
TRANSFORMER
• SUM OF THE EXCITATION LOSSES (CORE
LOSSES) AND LOAD LOSSES (COPPER LOSSES)
98.2 15
25
98
37.5
97.8
50
97.6
75
97.4
97.2
97
100 75 50 25
PERCENT LOAD
Source: Westinghouse Electric Corp., Style A7322 Hi 7200/12470Y, low 240/480
TRANSFORMER LOCATION
12,470 V
LONG
UNDERGROUND
WIRE
480 V
SHORT
UNDERGROUND
WIRE
TRANSFORMER
LOCATION
EXAMPLE: 80HP LOAD, 50 FT UNDERGROUND VS. 1000 FT UNDERGROUND,
1/0 WIRE
80 HP x .746 = 59.68kW
@ 12, 470 VOLTS THE CURRENT (I) IS
2.91 AMPS (for 3 phase power, .95 PF)
@ 480 VOLTS THE CURRENT (I) IS
75.56 AMPS (for 3 phase power, .95 PF)
TRANSFORMER LOCATION
EXAMPLE: 80HP LOAD, 50 FT UNDERGROUND VS. 1000 FT UNDERGROUND,
1/0 WIRE
Summary:
Locate transformers close to
unit but not overhead for safety
considerations.