NOTES
1. THIS DRAWING SHOULD BE READ IN CONJUCTION WITH
OTHER RELEVANT ARCHITECTURAL, STRUCTURAL,
625kVA GENERATOR
PROVISION FOR SEC SUPPLY (STAND BY)
MECHANICAL , ELECTRICAL & AS BUILT DRAWINGS AND ALL
(PERMANENT SOURCE) RELEVANT SECTIONS OF THE SPECIFICATION.
R Y B
7. PUMP VFD/SS SHALL BE STAND ALONE LOW HARMONIC TYPE/
1000A 4P HZ OR HARMONIC FILTERS TO BE PROVIDED AS PER IEEE
A A A 519-2014 FOR THD AT PCC.
MCCB
V MFM PF HZ WITHDRAWABLE
TYPE
8. CONTRACTOR TO SELECT THE AMPERE FRAME TO FIT THE
S/S SIZE OF CABLE.
1000A, TPN+E BUS BAR, 400V, CU, 60HZ,50kA 3 SEC 10. INCOMING CABLES FROM TEMPORARY SEC SUPPLY TO BE
SIZED AFTER COORDINATION WITH SEC.
1 2 3 4 5 6 7 8 9 10 10 12 13
63A TP 63A TP 40A TP 40A TP 20A SP 40A TP 40A TP 40A TP 800A TP 40A TP 40A TP 40A TP 630A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB
415V/110V
R Y B R Y B R Y B CONTROL
TRNS.
A A A
ICA CONTROL
PANEL
TCL=5.0 kW Rev. Reason For Issue Date Chk. App.
MD=5.0 kW
4C x 10 mm² XLPE/SWA/LSF +
4C x 10 mm² XLPE/SWA/LSF +
3C x 25 mm² XLPE/SWA/LSF +
3C x 25 mm² XLPE/SWA/LSF +
3C x 10 mm² XLPE/SWA/LSF +
4C x 95 mm² XLPE/SWA +
4C x 95 mm² XLPE/SWA +
Client DIRIYAH GATE DEVELOPMENT AUTHORITY
4C x 10 mm² XLPE/SWA+
7747 OUD DUNES
1C x 16 mm² ECC
1C x 10 mm² ECC
1C x 10 mm² ECC
1C x 10 mm² ECC
1C x 10 mm² ECC
1C x 50 mm² ECC
1C x 50 mm² ECC
RIYADH 12512,KINGDOM OF SAUDI ARABIA
1C x 4 mm² ECC
FIRE ALARM CONTROL KIOSK-DB-01 PUMP ROOM-DB-02 EXTERNAL SMDB EXTERNAL FP-01 EXTERNAL STREET EXTERNAL STREET SPARE APFCP
PUMP-01 PUMP-02 JOCKEY PUMP PANEL (FACP) TCL= 10.7 kW TCL= 15.0 kW FOR OFFICE, TCL=391kW LIGHTING FEEDER LIGHTING FEEDER TCL=16.96 kW 300KVA CH2M Saudi Ltd
TCL=11kW TCL=11kW TCL=0.4kW MD=389kW P.O. Box 8772, Riyadh, 11491,
TCL=0.5kW MD = 10.7 kW MD = 15.0 kW TOILE AND PILLAR -03 PILLAR -04 (PROVISIONAL FOR Kingdom of Saudi Arabia
MD=11kW MD=11kW MD=0.4kW MD=0.5kW (BY OTHERS) CAPACITOR BANK)
STORAGE SHED TCL=10kW TCL=10kW
(DUTY) (ASSIST) (DUTY) [FEEDING POWER SECOND
TCL=15kW MD=10kW MD=10kW SEE NOTE (4)
FEEDER PILLAR FP-02] Civil Defence Registered Consultant
MD=15kW (BY OTHERS) (BY OTHERS)
REF. DWG
WS023-ASR-EL-GEN-GE-ZZZ-000-001006
Drawing Title
EASTERN VACP TEMPORARY UTILITY COMPOUND
ELECTRICAL SINGLE LINE DIAGRAM
WS-WSI-690-3100-JCB-DWG-IR-100-0000177 05
DATUM
NORTH
GEODETIC DATUM: WGS-84
SHEET: 01
POINT PROJECT SYSTEM: UTM OF: 01
ZONE: 38N
For Approval