Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Copyright by the Diriyah Gate Development Authority (DGDA). All rights reserved.

This document may not, in whole or in part, be


reproduced, stored, transmitted or distributed in any form or by any means, whether electronic, mechanical, by photocopy, recording
or otherwise, without the prior written permission of DGDA. Except where otherwise expressly agreed in writing by DGDA, DGDA
shall have no responsibility or liability for any loss (direct, consequential or otherwise) which may arise from reliance on or use of this
document or the information contained therein.

DO NOT SCALE THIS DRAWING.

NOTES
1. THIS DRAWING SHOULD BE READ IN CONJUCTION WITH
OTHER RELEVANT ARCHITECTURAL, STRUCTURAL,
625kVA GENERATOR
PROVISION FOR SEC SUPPLY (STAND BY)
MECHANICAL , ELECTRICAL & AS BUILT DRAWINGS AND ALL
(PERMANENT SOURCE) RELEVANT SECTIONS OF THE SPECIFICATION.

2. THE ELECTRICAL SYMBOLS IN THE DRAWING ARE NOT TO


SCALE.

3. FOR ELECTRICAL GENERAL LEGEND AND NOTES REFER TO


DRAWING NUMBER WS004-JCB-UT-IRR-PL-ZZZ-P01-124400
(SEE NOTE No.10)

4. CAPACITORS SHALL REMAIN OFF DURING SUPPLY FROM


GENERATOR. CAPACITOR BANK IS CONSIDER AS PROVISION
IN THIS DESIGN SINCE TEH SUPPLY IS FROM GENERATOR. IN
CASE TEH POWER IS IS CHANGE TO BE FED FROM GRID (
3X4C *300 Cu/XLPE/PVC+ AUTHORITIES POWER) THE CAPACITOR BANK IS REQUIRED.
ATS 2X1C *150Sqmm ECC
5. CABLE AND BREAKERS SIZES SHALL BE FINALIZED BASED ON
THE APPROVED ACTUAL EQUIPMENTS LOAD BY THE
MCC-01 CONTRACTOR AND APPROVED BY THE ENGINEER
3X4C *300 Cu/XLPE/PVC+
2X1C *150Sqmm ECC
CONTRACTOR SHALL LIAISE WITH ELECTRICAL AUTHORITY
TOTAL CONNECTED LOAD 496.56 kW FOR POWER SUPPLY AND NECESSARY APPROVALS
INCLUDING CALIBRATION OF KWH/CTS (IF REQUIRED)
MAXIMUM DEMAND LOAD 494.56kW

6. CONTRACTOR TO VERIFY THE CABLE DUCT ARRANGEMENT


TO SUIT INCOMING / OUTGOING CABLE DETAILS. MCC
FORM OF CONSTRUCTION : FORM 4, TYPE-7 ELECTRICAL KIOSK ARRANGEMENT AND LOAD ARE
INGRESS RATING : IP54 INDICATIVE ONLY. FINAL MCC ARRANGEMENT, KIOSK
INSTALLATION : FLOOR MOUNTED
CABLE ENTRY : BOTTOM
DIMENSION AND LOAD SHALL BE CONFIRMED AND SUPPLIED
BASED ON KIOSK MANAFACTURE SPECIALIST.

R Y B
7. PUMP VFD/SS SHALL BE STAND ALONE LOW HARMONIC TYPE/
1000A 4P HZ OR HARMONIC FILTERS TO BE PROVIDED AS PER IEEE
A A A 519-2014 FOR THD AT PCC.
MCCB
V MFM PF HZ WITHDRAWABLE
TYPE
8. CONTRACTOR TO SELECT THE AMPERE FRAME TO FIT THE
S/S SIZE OF CABLE.

9. FP-02 (FEEDER PILLAR) WILL BE FED FROM FP-01 AND


RESPECTIVE CABLE CONNECTION FROM FP-01 TO FP-02 WILL
BE PROVIDED BY OTHERS.

1000A, TPN+E BUS BAR, 400V, CU, 60HZ,50kA 3 SEC 10. INCOMING CABLES FROM TEMPORARY SEC SUPPLY TO BE
SIZED AFTER COORDINATION WITH SEC.
1 2 3 4 5 6 7 8 9 10 10 12 13

63A TP 63A TP 40A TP 40A TP 20A SP 40A TP 40A TP 40A TP 800A TP 40A TP 40A TP 40A TP 630A TP
MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB MCCB

ELR ELR ELR ELR ELR

415V/110V
R Y B R Y B R Y B CONTROL
TRNS.
A A A

S/S S/S S/S


PLC UPS
SEE SEE SEE
NOTE 10 NOTE 10 NOTE 10 ICA CONTROL
PANEL
VFD VFD VFD

ICA CONTROL
PANEL
TCL=5.0 kW Rev. Reason For Issue Date Chk. App.
MD=5.0 kW
4C x 10 mm² XLPE/SWA/LSF +

4C x 10 mm² XLPE/SWA/LSF +
3C x 25 mm² XLPE/SWA/LSF +

3C x 25 mm² XLPE/SWA/LSF +

3C x 10 mm² XLPE/SWA/LSF +

1C x 150 mm² Y/G PVC CABLE

3x4C x 300 mm² XLPE/SWA +


2C x 4 mm² XLPE/SWA/LSF +

4C x 95 mm² XLPE/SWA +

4C x 95 mm² XLPE/SWA +
Client DIRIYAH GATE DEVELOPMENT AUTHORITY

4C x 10 mm² XLPE/SWA+
7747 OUD DUNES

3x1C x 150 mm² ECC


AMR ALDAMRI STREET
AL SAFARAT-UNIT No:2
1C x 16 mm² ECC

1C x 16 mm² ECC

1C x 10 mm² ECC

1C x 10 mm² ECC

1C x 10 mm² ECC

1C x 10 mm² ECC

1C x 50 mm² ECC

1C x 50 mm² ECC
RIYADH 12512,KINGDOM OF SAUDI ARABIA
1C x 4 mm² ECC

TEL : 0096 69200 02622


FAX :
EMAIL: info@dgda.sa

Project Management & Cost Consultant

63A TP 63A TP 40A TP


AL Fazary Plaza, C-10, Diplomatic Quarters, Riyadh 11693, P.O Box 94255
Tel: +966 920003395, Fax: 966 11 2883813, Riyadh, KSA
Principal Consultants
M M M

FIRE ALARM CONTROL KIOSK-DB-01 PUMP ROOM-DB-02 EXTERNAL SMDB EXTERNAL FP-01 EXTERNAL STREET EXTERNAL STREET SPARE APFCP
PUMP-01 PUMP-02 JOCKEY PUMP PANEL (FACP) TCL= 10.7 kW TCL= 15.0 kW FOR OFFICE, TCL=391kW LIGHTING FEEDER LIGHTING FEEDER TCL=16.96 kW 300KVA CH2M Saudi Ltd
TCL=11kW TCL=11kW TCL=0.4kW MD=389kW P.O. Box 8772, Riyadh, 11491,
TCL=0.5kW MD = 10.7 kW MD = 15.0 kW TOILE AND PILLAR -03 PILLAR -04 (PROVISIONAL FOR Kingdom of Saudi Arabia
MD=11kW MD=11kW MD=0.4kW MD=0.5kW (BY OTHERS) CAPACITOR BANK)
STORAGE SHED TCL=10kW TCL=10kW
(DUTY) (ASSIST) (DUTY) [FEEDING POWER SECOND
TCL=15kW MD=10kW MD=10kW SEE NOTE (4)
FEEDER PILLAR FP-02] Civil Defence Registered Consultant
MD=15kW (BY OTHERS) (BY OTHERS)

REF. DWG
WS023-ASR-EL-GEN-GE-ZZZ-000-001006

Project Name and Location

WADI SAFAR INFRASTRUCTURE


Specialist Consultant

Drawing Title
EASTERN VACP TEMPORARY UTILITY COMPOUND
ELECTRICAL SINGLE LINE DIAGRAM

REV-05 REVISION DESCRIPTION: Date Scale NTS


Project No. Drawn By HA
1. MAIN CABLE SIZES HAVE BEEN ADDED Drawing Number Revision

WS-WSI-690-3100-JCB-DWG-IR-100-0000177 05
DATUM
NORTH
GEODETIC DATUM: WGS-84
SHEET: 01
POINT PROJECT SYSTEM: UTM OF: 01
ZONE: 38N

For Approval

FILE PATH: WS-WSI-690-3100-JCB-DWG-IR-100-0000177.dwg

You might also like