Professional Documents
Culture Documents
M156 5 BORA OTN A4 E Screen
M156 5 BORA OTN A4 E Screen
The present document and its contents may change in the course of time or may not be suitable in a specific
situation. Consequently, they are recommended as suggested guideline only.
OTN Systems NV hereby disclaims any liability for any damages that may result from the use of the present
document unless it is used with respect to the operation and maintenance of equipment originally manufac-
tured by OTN Systems NV and covered by its standard warranty.
Open Transport Network BORA-OTN Network Card
1. INTRODUCTION ......................................................4
1.1 General ..........................................................4 Figure 1 BORA-OTN Side View (Straps + DIP Switches) ... 5
1.2 Reference Documents ...................................4 Figure 2 Clr NVRAM Strap .................................................. 5
Figure 3 Normal Reconfiguration, QUICK = „0‟ .................... 6
2. CARD DESCRIPTION ..............................................4 Figure 4 Fast Reconfiguration, QUICK = „1‟ ........................ 6
2.1 Functional Operation .....................................4 Figure 5 Functional Operation of the TRMs ......................... 7
2.1.1 Network Card Tasks ......................................4 Figure 6 BORA-OTN Front Panel ........................................ 9
2.1.2 Clr NVRAM Strap...........................................5 Figure 7 Example1: OTN Stand-Alone Clock .................... 14
2.1.3 DIP Switches .................................................5 Figure 8 Example 2: OTN Slaved to an External Clock ..... 14
2.1.4 TRMs .............................................................7 Figure 9 SDH or SONET Frames Locally .......................... 15
2.1.5 FPGA .............................................................7 Figure 10 SDH or SONET Frames Everywhere ................ 15
2.1.6 Microprocessor ..............................................7 Figure 11 Compatible with BORA+STR150 ...................... 16
2.1.7 Communication with the Interface Cards .......8
2.1.8 Temperature Sensor ......................................8 List of Tables
2.1.9 Alarm Contact ................................................8
2.1.10 Engineering Order Wire (EOW) .....................8
2.1.11 OMS Interface................................................8 Table 1 Reference Documents ............................................ 4
2.2 Visual Indications & Connectors on Front Table 2 OMS Connector: LED Description .......................... 8
Panel .............................................................8 Table 3 Meaning of the TRM LEDs ................................... 10
2.2.1 LED Indications..............................................8 Table 4 OMS Connector: Pin Allocations .......................... 10
2.2.2 Alphanumeric Display ....................................9 Table 5 Overview of Alarm Connector Specifications ........ 10
2.2.3 Connectors .................................................. 10 Table 6 Overview of Alarm Connector Pin Numbers ......... 10
2.3 Card Specifications ...................................... 13 Table 7 Display Data on The Network Card during Normal
Operation............................................................. 11
3. INSTALLATION GUIDELINES ............................... 13 Table 8 Display Data on The Network Card during Self-test
or in The Case of Errors ...................................... 12
4. LIMITATIONS ......................................................... 13
Table 9 Clock / Loop Timing Settings Example 1 .............. 14
5. ERROR LOCATION ............................................... 13 Table 10 Clock / Loop Timing Settings Example 2 ............ 14
Table 11 LT1/LT2/SDH Settings ........................................ 15
6. CLOCKING AND LOOP TIMING ........................... 14
6.1 What is Loop Timing (LT)? .......................... 14
6.2 OTN stand-alone clock (=no LT) .................. 14
6.3 OTN slaved to an external clock signal (=no
LT) ............................................................... 14
6.4 SDH/SONET integrated in OTN (=possible
LT) ............................................................... 14
8. LIST OF ABBREVIATIONS.................................... 16
AD-M156-E-5 Page 3 of 16
BORA-OTN Network Card Open Transport Network
This document describes the BORA-OTN network card. The BORA-OTN network card can be used in an OTN-150
The BORA-OTN can operate in existing OTN-150/600 or OTN-600 network.
networks with existing OMS (OTN Management System)
Versions (OMS < V6.1). The BORA-OTN is fully supported There are 4 different types of BORA-OTN network cards,
in OMS as of OMS V6.1. Before OMS V6.1, this is card is each of which can be used in an 8-slot (N20 or N22) or 4-
displayed in OMS as BORA-150 or BORA-600. slot (N215) nodes.
Depending on the type, this network card can replace one - Type 1: BORA-OTN150 (X101/X102).
of the following network cards: - Type 2: BORA-OTN600 (X103/X104).
- Type 3: BORA-OTN155 (X105/X106):
- BORA150 (S30824-Q80-X). - Compatible with STR150.
- BORA600 (S30824-Q87-X). - STM1/OC3 compatible.
- BORA (FB-52432-1A) + STR150L/L2 (S30824-Q43-
X/X100). - Type 4: BORA-OTN150/155 (X109); BORA-OTN155/
150 (X110)
The BORA-OTN, equipped with two TRMs (Transmit/ - X109: TRM1 = OTN; TRM2 = SDH/SONET.
Receive Modules), represents the central control block of - X110: TRM1 = SDH/SONET; TRM2 = OTN.
an OTN node, controls communication between the - Designed for an 8-slot node (but also operates in a
interface cards and the optical ring and provides the 4-slot node).
interface to the OMS.
2.1.1 Network Card Tasks
The TRMs are hot-pluggable SFP (Small Form Factor
Pluggable, see Ref. [7] in Table 1) type OTRs that can be a. I/O with the Line Interface Units (LIU)
replaced from the front, without having to remove the
Status and control data of SFP modules and SDH
BORA-OTN card from the node.
framers, such as the SFP type and SDH/SONET
This network card allows for faster reconfigurations in case alarms, are exchanged between the Line Interface
of a single fiber break. Units and the FPGA and/or the microprocessor.
This network card (types X105, X106, X109, X110) can b. I/O with the Interface Cards
also process SDH (STM1) and SONET (OC3) framing.
The network card is responsible for status and control
bit processing and transports interface card data to and
from the ring.
1.2 Reference Documents
c. I/O with the OMS
Table 1 is an overview of the documents being referred to
in this document, „&‟ refers to the language code and „*‟ If the OMS is locally connected to the network card,
refers to the document issue. then the network card communicates with the OMS via
the 10/100 BASE-T Ethernet interface. The network
card communicates with the OMS via the ring if the
OMS is connected to another network card. Either a
Table 1 Reference Documents „straight-through‟ or a „cross-over‟ cable can be used
(automatic MDI/MDIX crossover).
Ref. Number Title
d. Alarming
[1] AA-D100-&-* OTN Product Description When the network card does not receive synchroniza-
tion signals from other nodes in the ring, two digital
[2] AA-M921-&-* ESD Regulations contacts on the front panel can be switched to report
this error situation. See also §2.1.9.
[3] AG-M330-&-* OMS – User Manual
e. Status and Control Data of the Node
[4] AD-M132-&-* BORA150/600 Network Cards
The network card can both read node status data
[5] AD-M131-&-* BORA Network Cards (maximum 8 status bytes) and send control data to the
node, provided extra provisions are made to this end.
[6] AF-M127-&-* STR150L/L2 Network Cards
f. Optical Ring Management
[7] AD-M155-&-* OTN TRM Modules The network card manages the optical ring by carrying
out the following tasks.
[8] AD-M205-&-* OTN Installation & Operation
Manual - Frame generation (in the master node).
- Start-up and synchronization of both rings.
- Determination of the master node .
- Node reconfiguration in error situations.
- Transfer of error indications to neighboring nodes.
- Extensive self-tests.
Page 4 of 16 AD-M156-E-5
Open Transport Network BORA-OTN Network Card
See Figure 1 for a side view with straps of the BORA-OTN. The BORA-OTN has three DIP switches (see Figure 1).
Make sure to power off the network card before changing
When the power supply of a network card is switched off, one of the switches.
the NVRAM ensures that existing services and IFC control
data can be recovered upon reboot. Once in the 'off' state, a. Node Number (NODE NR)
the network card can hold its existing services forever,
because these are stored in a FLASH EEPROM or NVRAM This DIP switch sets up the Node Number. The most
(=NON VOLATILE RAM) upon switching off. left-hand switch (number 8) is the MSB (=Most
Significant Bit). A switch in the upper position indicates
When the power supply of the network card is switched on a logical „1‟. Valid node numbers are [1..250].
(reboot), the „Clr NVRAM‟ strap setting determines what is
going to happen: You can use the (scientific) calculator on your PC via
Start Programs Accessories, to convert a „deci-
a. When the strap is in the „Clear‟ mode (strap up, Clr mal‟ node number into a „binary‟ number. This binary
MEM), the NVRAM is initialized with default system result is the setting of your Node Number DIP switch.
values, i.e. existing services and IFC control data are E.g. node number „137‟ (DEC) = „10001001‟ (BIN).
lost. The network card shows „E2‟ on the front panel
display (see §2.2.2) and the backplane is disabled. b. Card Issue
After switching off the network card, setting the strap This DIP switch indicates the hardware edition of the
back to its normal position (strap down) and switching network card. The user is not allowed to change these
on the network card again, it still shows „E2‟. The settings. A switch in the upper position indicates a
backplane stays disabled until the OMS writes its logical „1‟. MSB is the most left-hand switch. The card
programmed services back onto the network card. issue is also read out by the OMS.
b. When the strap is in the normal position (strap down), c. Network Configuration Switch
all existing services and IFC control data are recovered
- LT1 (see also §6)
after a power failure and remain operational.
Set LT1 to „1‟ when TRM1 of the BORA-OTN must
slave its clock to an SDH or SONET sub-network.
LT1 is only functional with BORA-OTN type 3, 4.
LSB
0
„0‟ in all nodes. This switch is only functional with
BORA-OTN type 3 and 4.
- QUICK
ATTENTION!
SPARE0
SPARE1
SPARE2
SPARE3
QUICK
NODE NR
1 1
network cards are in the ring that do not have
MSB
LSB
0 0
the QUICK dipswitch onboard !!! If QUICK has
to be set to ‘1’, make sure all the network cards
in this ring have set this QUICK setting to ‘1’.
Figure 1 BORA-OTN Side View (Straps + DIP Switches) Additional:
When using BORA-OTN600 (X103/X104), and
switch QUICK=’1’, SPARE1 and SPARE2 MUST
Clr MEM Clr MEM be set to ‘1’ as well !!!
NVRAM
NVRAM
AD-M156-E-5 Page 5 of 16
BORA-OTN Network Card Open Transport Network
swap from the active to the passive ring, which - SPARE1 = Enhanced (601) Framing in TRM1
takes approximately 120 ms. See Figure 3. When the optical signal between source and
destination node is getting poor (e.g. due to long
„1‟ = fast reconfiguration (< 50 ms); if a single fiber distances), the enhanced (601) framing is
fiber break occurs in the active ring (e.g. primary able to detect bit errors faster than normal (600)
ring), the adjacent nodes to the fiber break go in framing. As a result, enhanced (601) framing will
loopback. This means that only these adjacent lead to a more accurate CVA indication and
nodes change their data flow states, e.g. from PP counting than normal (600) framing.
to PS and from PP to SP (see also §d). The other
nodes keep their data flow state PP, but show LB When there is plenty of optical signal, both framing
(=loopback) on the display; When there is no fiber types are equally effective.
break, PPqk is shown on the display. See Figure 4.
The more nodes in the network, the bigger the „1‟ = TRM1 sends out enhanced (601) framing.
reconfiguration time, with a worst case of 50 ms for
„0‟ = TRM1 sends out normal (600) framing
very large networks (110 nodes, 1000 km fiber).
(factory default setting) which is necessary when
A double fiber break always results in loopback this network card communicates with older BORA
mode, either in normal or fast reconfiguration. network cards without the QUICK switch and 601
framing.
- SPARE0
Set to „0‟;
Normal Reconfiguration
QUICK = ‘0’, 120 ms reconf ig. time
PP PP SS SS
OTN OTN
PP PP SS SS
single fiber break secondary ring
on active ring becomes active
Fast Reconfiguration
QUICK = ‘1’, <50 ms reconf ig. time
PPqk PPqk LB LB
OTN OTN
SP
PPqk PPqk PS
ring in
single fiber break loopback
on active ring adjacent adjacent
node node
Page 6 of 16 AD-M156-E-5
Open Transport Network BORA-OTN Network Card
Optical
ATTENTION! Previous Transmitter
Node
AD-M156-E-5 Page 7 of 16
BORA-OTN Network Card Open Transport Network
At the end of an OMS firmware download, programmed The EOW interface provides power for the analog/digital
services in this node are disrupted very briefly (a few conversion (PCM), and detects whether a microphone is
milliseconds). plugged in.
2.1.7 Communication with the Interface Cards A fixed bandwidth is reserved on the ring for the EOW
function, which therefore must not be programmed via the
For communication with the interface cards, the backplane OMS.
is equipped with busses.
2.1.11 OMS Interface
a. Data Bus
The OMS is connected via a 10/100 BASE-T Ethernet
The data bus contains, among other things, address interface on the front panel. The microprocessor and the
lines for the selection of the proper interface card and connected OMS communicate via an Ethernet controller
user, and data lines for data transport to and from the and a proprietary protocol. Each network card has another
interface cards. Via this bus, the FPGA passes the Ethernet address. The address is stored in the fixed part of
data flow of the TRM modules to the proper interface the master flash EPROM. When switching on the power
cards. Simultaneously, it multiplexes the interface data supply, the microprocessor reads this address and passes
in the same transmission channels. An LS and HS data it on to the Ethernet controller.
bus interfaces with the backplane. LS stands for Low
Speed addressing. HS stands for High Speed
addressing. 2.2 Visual Indications & Connectors on Front Panel
b. Status/Control Bus The network card front panel (Figure 6) is equipped with
the following:
The FPGA can request a number of status data from
the interface cards, such as the card type. In turn, the - LED indications.
OMS can read out and interpret this data. - an alphanumeric display.
- connectors.
In the opposite direction, the OMS can set a number of
parameters on the interface card via this FPGA and the 2.2.1 LED Indications
control bus.
The network card front panel houses the LEDs R, T, EOW,
Maj, Min, SY2, SY0, OSL/SDH, CVA/BER and CLK.
2.1.8 Temperature Sensor
During start-up (self-test) and in the case of an error, the
As excessive temperatures may reduce the life of LEDs do not have the functions as indicated below. During
components, the network card holds a temperature sensor, the self-tests, the LEDs flash alternately.
which indicates whether the temperature exceeds 65 °C ±
4 °C (139 °F ± 7 °F). The microprocessor reports high a. R, T
temperatures to the OMS.
R and T are bi-color LEDs on the OMS connector. See
Table 2 for the meaning of the colors.
2.1.9 Alarm Contact
b. EOW
The network card is equipped with two solid state relays to
The EOW LED is lit when an EOW station has plugged
indicate abnormal operation.
in the headset microphone somewhere.
One relay “MAJOR ALARM” shows that the node is not
c. Maj, Min
receiving synchronization signals from neither of the rings.
A lit Maj (Major alarm) LED shows that the network
The second relay “MINOR ALARM” shows that the node is
card has raised a major alarm and that neither of the
not receiving synchronization signals from at least one ring.
two rings is in the SYNC2 state.
If the node is switched off (no power) a major and minor
A lit Min (Minor alarm) LED indicates that a minor alarm
alarm situation occurs as well.
has been raised by the network card and that at least
one ring is in the SYNC0 state.
2.1.10 Engineering Order Wire (EOW)
Table 2 OMS Connector: LED Description
A headset with microphone (S26361-F2D87-L1) can be
plugged into the 3.5mm jacks (EOW connector) on the LED Color Status
network card front panel.
R&T Orange Link down
If a microphone (red connector) is plugged in, LED EOW is
lit on every network card in the network. R&T Not lit, dark Link up
If in one other node the microphone and headphone (black R Green Link up, Ethernet packets are
connector) are plugged in, point-to-point communication being received at the front panel
between both nodes is possible. Only these nodes can
speak and listen to each other. Other nodes can listen to T Green Link up, Ethernet packets are
this conversation as well when only the headphone is being transmitted at the front
plugged in at that node. This function is for example used panel
during installation or maintenance activities.
Page 8 of 16 AD-M156-E-5
Open Transport Network BORA-OTN Network Card
g. LED CLK
AD-M156-E-5 Page 9 of 16
BORA-OTN Network Card Open Transport Network
d. The node configuration and Link Alarm / Local Alarm. and one for transceiving optical signals (Si, Po) with
next node.
- The node configuration indication (PP, PS, SP, SS
or LB) indicates the direction of the data through e. a BNC connector for the connection of an external TTL
the node: clock signal. An external clock signal of 2.048 MHz or
36.864 MHz is required. When the network card
- PP: from the primary input (Pi) to the primary concerned is the master (lowest node number), the
output (Po). clock will be slaved to this external clock.
- PS: from the primary input (Pi) to the
secondary output (So). Table 3 Meaning of the TRM LEDs
- SP: from the secondary input (Si) to the
primary output (Po). BORA Type CVA/BER
- The Link Alarm (Li) occurs when the neighboring Type 4 (X110) BER CVA
nodes report that they have not received anything
at the input coming from this node.
Table 4 OMS Connector: Pin Allocations
- The Local Alarm (Lo) occurs when invalid frames
are being received.
Pin No. Signal
e. The Optical Line Interface: 150/600/601/155: In case of
a cabling failure, the word „Link‟ will flash on the display 1 Transmit output (+)
(600 = normal framing, 601 = enhanced framing); 2 Transmit output (-)
f. The SFP type, for TRM1 and TRM2: 3 Receive input (+)
SFP type in SDH notation: M, I, S1, S2, L1, L2 4,5 ---
Page 10 of 16 AD-M156-E-5
Open Transport Network BORA-OTN Network Card
4 3 2 1
2 < Node number Number of previous node compared to the transmission direction on
the data carrying ring
3 > Node number Number of next node compared to the transmission direction on the
data carrying ring
4 PP/PS/SP/SS/LB qk/Li/Lo <empty> Node configuration qk = This node has switched on the
(see §2.2.2.d) „quick reconfiguration setting‟ and
there is no fiber break. See §2.1.3c
for more info.
5 ()150/600/601/155() (Link) Depending on the network card type that is used (X101…X110),
the appropriate framing or speed is displayed.
If TRM1 and TRM2 use a different framing, then an additional arrow is
displayed. Find an overview in the table below:
TRM1 TRM2
Card Type DISPLAY
Framing Framing
X101/X102 150 OTN-150 OTN-150
X103/X104 600 OTN-600, norm. OTN-600, norm.
X103/X104 601 OTN-600, enh. OTN-600, enh.
X103/X104 601 OTN-600, norm. OTN-600, enh.
X103/X104 601 OTN-600, enh. OTN-600, norm.
X105/X106 155 STM1 STM1
X109 155 OTN-150 STM1
X110 155 STM1 OTN-150
Enh. = Enhanced (601) framing within OTN-600
Norm. = Normal (600) framing within OTN-600
Enhanced and Normal framing can be set by using the SPARE1
and SPARE2 switches of the network configuration switch.
See §2.1.3c for more info.
AD-M156-E-5 Page 11 of 16
BORA-OTN Network Card Open Transport Network
Table 8 Display Data on The Network Card during Self-test or in The Case of Errors
Cycle 1 Cycle 2
TEST TEST The node starts up and carries out a self-test. If the display does not change Replace the network card.
after a while, the system is unable to test itself (error on the network card).
If TEST is displayed, followed by a code, the OMS is unable to communicate with the network card, and the node is
not switched into the ring.
TEST IRAM Error in the internal RAM. Replace the network card.
TEST XRAM Error in the external RAM. Replace the network card.
TEST CRC1 Error in the CRC test of the flash 1 boot part. Replace the network card.
TEST PGR Error in the program part. The flash 1 and flash 2 program code is invalid. Replace the network card.
If FAIL is displayed, followed by a code, communication with the OMS is possible via the local Ethernet port, but
the node is not switched into the ring.
FAIL ERMS Error in interrupt mechanism of ERM1 and/or ERM2. Replace the network card.
FAIL ERM1 Problem with gate array ERM1. Replace the network card.
FAIL ERM2 Problem with gate array ERM2. Replace the network card.
FAIL TRM1 Synchronization error in the electrical loopback with TRM1 in «daisy chain». Replace the network card.
FAIL TRM2 Synchronization error in the electrical loopback with TRM2 in «daisy chain». Replace the network card.
FAIL TRMS Synchronization error in the electrical loopback of both TRMs in «dual ring». Replace the network card.
FAIL N215 A network card for a 4-slot node is plugged into an 8-slot node. Place the network card in
a N215 node.
If one of the following error codes is displayed, following the data (cycles) sequentially listed in Table 7, then the
node is switched into the ring, and communication with the OMS is still possible via the optical ring. The local
Ethernet may be defective.
E0 E0 CRC error in the flash 2 boot part. The flash 1 boot and program part is OK. Replace the network card.
E1 E1 The «boot» version numbers of the flash EPROMs differ. Replace the network card.
E3 E3 Error in the Ethernet internal loopback (local Ethernet port defective). Replace the network card
if the OMS port is used.
E4 E4 Error in the Ethernet Dual Port RAM (local Ethernet port defective). Replace the network card
if the OMS port is used.
E5 E5 Synchronization error in the electrical loopback with TRM1 in «dual ring» or Replace the network card.
error in TRM1 status control, or unknown type.
E6 E6 Synchronization error in the electrical loopback with TRM2 in «dual ring» or Replace the network card.
error in TRM2 status control, or unknown type.
E7 E7 Error in the Ethernet external loopback (local Ethernet port defective). Replace the network card
if the OMS port is used
E8 E8 Status and control RAM error in ERM2: no bandwidth can be accessed. Replace the network card.
E9 E9 Error in the CRC test of the flash 1 program part. Download new loadware.
If the error persists,
replace the network card.
E10 E10 Error in the CRC test of the flash 2 program part. Download new loadware.
If the error persists,
replace the network card.
Page 12 of 16 AD-M156-E-5
Open Transport Network BORA-OTN Network Card
- Operation:
-20 °C to +55 °C
-4 °F to +131 °F ATTENTION!
- Start-up:
-10 °C to +55 °C With all installation activities, ESD recommendations
+14 °F to +131 °F regarding the handling, transportation, and storage of
cards must be observed (see ref. [2] in Table 1).
- Storage and shipping:
-20 °C to +70 °C Plugging the network card into a slot other than the
-4 °F to +158 °F network card slot will damage the network card.
b. Relative Humidity (non-condensing)
This network card is NOT HOT-PLUGGABLE
- Operation: 20 % to 80 % at 25 °C (+77 °F)
(node surrounding) CHECK THE QUICK SETTING.
c. Weight 4. LIMITATIONS
- approx. 440 g - A fast reconfiguration (see §2.1.3c) is not possible in a
mixed network. A mixed network is a network that has
d. MTBF at +25 °C (+77 °F) older network cards (S30824-Q80 or S30824-Q87 or
- 63.8 years (=1789 FITs) S30824-Q43) mixed with this BORA-OTN network
card (S30824-Q134).
e. Electromagnetic Compatibility
- This BORA-OTN network card can only be connected
- Emission: EN 61000-6-4, EN 55022, Class B with the OTR150(MD) and OTR600(MD) card if the
eye protection is deactivated (both software and
- Immunity: EN 61000-6-2 hardware) on the OTR cards. To make sure that the
eye protection is still deactivated after reboot of the
f. Power Consumption (with two SFPs) card, make sure that at least firmware v3.023 is used
on the BORA cards.
- +5 V: 1.85 A
g. OMS Connection
5. ERROR LOCATION
- Via a twisted pair RJ45 connector for 10/100
When switching on the supply voltage and during the
BASE-T Ethernet interface.
optical connection, check the LEDs and the alphanumeric
h. Certification display on the network card. Solve errors, if any.
- FCC Part 15 CIA Pending a. If no LED is lit on the network card, then check:
j. Optical Data Rate c. If the green SY2 LEDs on the network card are not lit,
the node is not synchronized.Check the optical
- OTN-150 184.32 Mbps connections.
- OTN-600 737.28 Mbps d. If the red SY0 LEDs on the network card are lit, the
node is not synchronized.Check the optical
- OTN-155 155.52 Mbps connections.
AD-M156-E-5 Page 13 of 16
BORA-OTN Network Card Open Transport Network
6. CLOCKING AND LOOP TIMING Table 9 Clock / Loop Timing Settings Example 1
The SDH setting in the table below is irrelevant, even if the LT2 „0‟ all nodes
setting has different values in different nodes. LT1 „0‟ all nodes
The OTN clock will be the node with the lowest node OTN
number, and can be any node in the ring (not necessarily
nodes connected to the external subnetwork).
Page 14 of 16 AD-M156-E-5
Open Transport Network BORA-OTN Network Card
TRM1
TRM2
TRM1
TRM1
TRM2
TRM1
TRM2
10 20 10 20
40 30 40 30
OTN OTN
TRM2
TRM1
TRM1
TRM1
TRM2
TRM1
TRM2
10 20 10 20
40 30 40 30
STM1 OC3
AD-M156-E-5 Page 15 of 16
BORA-OTN Network Card Open Transport Network
TRM1
TRM2
TRM1
TRM2
TRM1
TRM2
TRM1
10 20 10 20
STR
STR
STR
STR
STR
STR
STR
40 30 40 30
OC3
STM1
SDH SONET
8. LIST OF ABBREVIATIONS
AC Alternate Current
BER Bit Error Rate
BORA Broadband Optical Ring Adapter
CVA Code Violation Alarm
CVR Code Violation Rate
DC Direct Current
EOW Engineering Order Wire
ERMx ERIA Mode x
HS High Speed
LB Loopback
LED Light Emitting Diode
LS Low Speed
MCP Mode Conditioning Patch
MSB Most Significant Bit
MTBF Mean Time Between Failures
NVS Non Volatile Static
OMS OTN Management System
OSL Optical Signal Loss
OTN Open Transport Network
OTR Optical Transmitter and Receiver
RX Receive
TX Transmit
TRM Transceiver Module
Page 16 of 16 AD-M156-E-5